18
Installation
XG0199 - 170223
Notes Wall Mounted Terminations: REAR VENT
• All dimension lengths for vertical or horizontal runs are measured
from center of the vent pipe.
• Venting runs must fall within the limits set by the venting graphs,
see Figure 9 or 9.b
• Fireplace must be converted to Rear Vent configuration prior to
running vent, see Figure 5 and 5.b (Page 11)
Example A: (Acceptable Installation)
If the vertical dimension from the hearth is 120" and the horizontal
run to the wall flange of the vent termination is 144", this would be an
acceptable installation.
Example B: (Unacceptable Installation)
If the vertical dimension from the hearth is 36" and the horizontal run
to the wall flange of the vent termination is 84", this would not be an
acceptable installation.
Example C: (Unacceptable Installation)
If the vertical dimension from the floor of the fireplace is 60" and the
horizontal run to the wall flange of the vent termination is 144", this
would not be an acceptable installation.
Rear Venting Graph P38, PL38:
Measure the vertical height from the fireplace hearth to the centre of
the termination and the horizontal run from the fireplace flue collar
to the wall flange of the termination. Plot on the Venting Graph Figure
9 or 9.b with an 'X'.
If the 'X' falls on or above the top boundary of the shaded area, the
installation is acceptable.
NATURAL GAS VENT RUN
PROPANE GAS VENT RUN
Figure 9.
PL38DF* Rear Vent Venting Graph for NG wall mounted terminations.
Figure 9.b
PL38DF* Rear Vent Venting Graph for Propane wall mounted terminations.
Figure 9.c
Straight run, Rear Vented, wall mounted termination. Note: Straight through the wall
rear vent available for
Natural Gas only.
Figure 9.d
Rear Vented, wall mounted Multi-elbow termination installation for NG or Propane.
Installation must comply with the Venting Graph for Rear vent, wall mounted terminations, Figure
15 or 15a.
0
HEARTH
12
12
0
60
36
84
120
24
72
108
48
96
132
Vertical Height (In.)
Horizontal Run (In.)
36
60
84
108
132
156
24
48
72
96
120
144
168 180
0
HEARTH
12
12
0
60
36
84
120
24
72
108
48
96
132
Vertical Height (In.)
Horizontal Run (In.)
36
60
84
108
132
156
24
48
72
96
120
144
168 180
Acceptable vent run
within non-shaded area.
Acceptable vent run
within non-shaded area.
Unacceptable vent run
within shaded area.
Unacceptable vent run
within shaded area.
A
A
B
B
C
C
26 3/8”
PXT Extension
RHS101 Heat
Shield
Termination
Hearth
Exterior
Wall
12” MAX.
30” Max.
49” Min NG
12”
Max.
Flex or Rigid
Section
26 3/8”
63” Min LP
RHS101
Heat Shield
PXT Extension
Hearth
Termination
30'' Max.
for minimum
vertical
49'' Min. NG
63'' Min
Propane
26 3/8''
12''
Max.
Flex or Rigid
Section
26 3/8''
12'' MAX
NOTE: 12'' MAX horizontal
run with no vertical lift
Exterior
Wall
63''
42''
26⅜''
12''
49''
42''