XG0223
11
Installation
Figure 5.
Flue cover and collar removal, Top Vented fireplace.
Figure 5.b
Flue cover and collar installation, Side Vented fireplace.
Note: Images are shown without screens for clarity purposes. However,
your fireplace should not be operated without proper installation of
screens.
Flue Collar
8" Outer Flue Collar
8" Outer
Flue Collar
5" Inner Flue
Cover plate
5" Inner Flue
Cover plate
5" Inner
Flue Collar
Outer Flue
Cover plate
8" Outer Flue
Cover plate
Under no circumstances can Montigo flex venting be cut to
accommodate an installation. Use an alternative length to complete
your vent run.
NOTICE
Section 3: Venting
Montigo supplies a variety of direct venting and termination options.
The direct vent termination location MUST be selected such that it is the
highest point in the venting assembly. It should also be selected such
that it provides the shortest vent run possible. Should it be impossible
to ensure that the termination is the highest point or to meet the
venting guidelines laid out below please contact your Montigo dealer
to discuss power venting options.
Notes For Planning Venting:
• Venting can originate from the unit through the top or through the side.
• Venting can terminate through the roof or through an exterior wall.
• Refer to Appendix A - Termination Locations to ensure the planned
termination location is acceptable.
• Once the termination location has been established, refer to the
appropriate section below for installation details
•
All fireplaces shipped from the factory are Top vent.
• Silicone application is NOT required when joining Montigo vent pipes
and components.
Section 3-1: Converting to Side Vent
Use the following instructions to convert a unit for Side Vent use:
1.
Remove the Side flue cover and gasket (5" and 8") on the flue
outlet, as shown in Figure 9.
2.
Next, Remove the Top flue collar's (5" and 8") on the flue outlet,
as shown in Figure 9.
3.
Install the (removed) Side flue cover and gasket material, to the
Top vent outlet. Fasten the cover with included hardware, as
illustrated Figure 9a.
4.
Install the (5" and 8") collars to the Side vent outlet using the
included hardware, as illustrated Figure 9a.