background image

Page 17

Part  No.  XG0106B

MD34-DV-2 Homefire

Maintenance

Troubleshooting

If your fireplace still does not operate correctly, consult your dealer
or  the  manufacturer.

All service and repairs should be performed by a qualified
agency.

All spare parts, optional fans (see optional fan instruction guide),
and  optional  trim  finishes  are  available  from  the  manufacturer  or
your  local  dealer.

HONEYWELL SV 9500 /SV9600

Troubleshooting Sequence

NOTE:

Before Troubleshooting, Familiarize Yourself With

The Startup And Checkout Procedure.

· Turn Gas Supply off

· Set thermostat to

call for heat

SV9500/SV9600

is powered

(24 VAC nominal)

NO

NO

NO

NO

NO

YES

YES

YES

YES

YES

YES

YES

NO

NO

NO

START

Igniter warms up

and glows red.

Pilot Valve opens.

Turn gas on.

Pilot Burner lights?

Main Valve opens?

SYSTEM OK

Unplug Pilot Burner Cable,

Measure Voltage at

SV9500/SV9600 HSI

Terminals (24 VAC

Nominal, See INSET)

Replace Igniter/

Flame Rod Assembly.

Replace Igniter/

Flame Rod Assembly.

Replace SV9500/SV9600

Measure Voltage to SV9500

/SV9600. Voltage must

be at least 19.5 VAC

Discard old Igniter/

Flame Rod Assembly.

Replace Igniter/Flame

Rod Assembly and retain.

Restart Troubleshooting

Sequence. Does main

valve open?

Replace

SV9500/

SV9600

Check

Transformer

Line Volt

Supply

Replace

SV9500/

SV9600.

Save old

Igniter/Flame

Rod Assembly

for service.

INSET

HSI

Terminals

CHECK:

· Line voltage power

· Low voltage transformer

· Limit Controller

· Thermostat

· Wiring

· Air proving switch on

combustion air blower system

· Vent damper (if used) is open

and end switch made

Gas Control Valve

Figure 28. 

Sit Nova 820 

gas valve

.

Pilot  Burner Adjustment

1. Locate Pilot Adjustment Screw. (See figure 28.)

2. Adjust pilot screw to provide properly sized flame as shown in

figure 29).

3. After installing or servicing, leak test with a soap solution with

main burner on. Coat pipe and tubing joints, gasket etc. with
soap  solution.  Bubbles  indicate  leaks.  Tighten  any  areas  where
the  bubbles  appear  until  the  bubbling  stops  completely.

MD34-DV-I-2

Figure 29. 

Pilot Burner

Troubleshooting

The following is a troubleshooting chart of possible problems:

PROBLEM

CORRECTIVE ACTION

Noisy  Pilot  Flame

Locate pilot adjustement screw on
gas  control  valve.  Flame  is  de-
creased  by  turning  adjustment  screw
clockwise.

Pilot won’t ignite

Disconnect remote wires and try to
light pilot. If pilot now works, remote
connections are faulty. Check wiring
diagram 

figure 

28.

Main  burner  will

1.  Check  wiring  (see figure 28).

not light

2. Check wall switch for proper
connection.

MD34-DV-2

Manifold Pressure
Test Connection

Pilot Adjustment Screw

Inlet
Pressure

Power
Generator

Wall Switch

Содержание Homefire plus MD34-DV-2

Страница 1: ...bor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Warning Improper installation adjustment alteration serviceormaintenancecancause injury or property damage Refer to this manual For assistance or additional information consult a qualified installer service agency or the gas supplier For Your Safety Do not store or use gasoline or othe...

Страница 2: ...ctory built gas fireplaces Installation repairs should be done by a qualified contractor Installations in Canada must conform to the current CAN CGA B 149 1 and 2 Gas Installation Code and local regulations If the optional air circulating fan kit is installed it must be electrically grounded in accordance with CSA C22 1 Canadian Electrical Code Part 1 and or Local Codes Installations in the USA mu...

Страница 3: ...raming depth may be reduced to 15 Framing WARNING When this appliance is installed directly on carpeting tile or any combustible material other than wood flooring it must be installed on a metal or wood panel extending the full width and depth of the appliance Rear Vent Clearances TheMD34 DV 2clearancestocombustiblematerialsare Top Rear Vent 7 Top Top Vent 35 Back 0 Side 1 Floor 0 Mantle 10 Cleara...

Страница 4: ...srequires a minimuminletgassupplypressureof11 W C amanifoldpressureof 10 W C Provision must also be made for a 1 8 N P T plugged tapping andbeaccessiblefortestgaugeconnectionimmediatelyupstreamofthe gassupplycontrolstotheappliance Thefireplacegasconnectionand themainoperatinggasvalveislocatedbehindtheremovablebrasstrim atthebottomoftheunitandneedonlybeattachedtothegasline withan approved fitting a...

Страница 5: ...2 12 12 MOSR 1 Frame the termination opening to 12 x 12 2 Fasten the MOSR frame to the interior side of the studs using a minimum of 4 screws 3 Insert the termination into the MOSR frame as shown here and attach by screwing through the four pilot holes in the termination MSR MTO 3 MTO 3F MTO 3 MTKOG 1 Ensure that the two long mounting brackets are facing the bottom of the termination See inset Thi...

Страница 6: ...s 78 and the horizontal run to the wall flange of the vent termination is 108 this would NOT be an acceptable installation 0 12 24 36 48 60 72 84 96 108 132 120 144 156 168 180 Horizontal Run in Hearth 0 12 24 36 48 60 72 84 96 108 Figure 8 Heat Shield Install by sliding over the vent pipe where it passes through combustible construction Heat Shields Due to high flue temperatures heat shields are ...

Страница 7: ...nstalled directly on the fireplace the height to the center of the termination is 44 Horizontal Venting Figure 9b Typical Top Vent installation The solid sections can be used in various combinations to obtain the desired vent run The vent run must fall within the limits set by the venting graph 90 Elbow MEXT Section Heat Shield Heat Shield MEL 90F F Elbow Termination Example 2 A10 sectionandelbow ...

Страница 8: ...n measured center to center of piping Example Typicalventinstallation 20 verticalvent 2 2 offsets required 25 of 20 5 max offset allowed Thisventingconfigurationmeetsrequirements A Termination MVTK 1 B Flex sections MFL 1 12 section MFL 2 24 section MFL 3 36 section MFL 4 48 section C Solid sections MEXT 1 12 section MEXT 2 24 section MEXT 3 36 section MEXT 4 48 section D Support Ring Plate MSPXT ...

Страница 9: ...e hearth to the center of the termination is 26 1 8 MD34 DV 2 Rear Vent versions are supplied with an 18 extension pipe EXT 18 with female female connections For shorter installations cut the EXT 18 to the desired length For extended installations use the EXT 18 section as supplied for an 18 vent run Note For Rear Vent models maximum horizontal run with no vertical lift must never exceed 18 Flue C...

Страница 10: ...l run to the wall flange of the vent termination is 126 this would be an acceptable installation Example C Unacceptable Installation If the vertical dimension from the floor of the fire place is 78 and the horizontal run to the wall flange of the vent termination is 108 this would NOT be an acceptable installation Figure 19 MD34 DV 2 Rear Vent Venting Graph 0 12 24 36 48 60 72 84 96 108 132 120 14...

Страница 11: ...omponents Sheetrock Drywall Header 3 45 Painting Special care is recommended by the Master Painters and Decora tors Association when painting the fireplace surrounds to select and apply a quality Alkyd sealer prior to the applying of latex paints This is to prevent leaching of water from evaporation and causing a brownish staining effect to paint over coats Top of fireplace Combustible Facing Comb...

Страница 12: ...onal fan kit 115 1 60 Supply G L1 L2 Installing the Log Set Installing the Logs TheMD34 DV 2 issuppliedwithsixceramicfibrelogs Unpackthelogs and handle them very carefully 1 Remove the door cover and the glass door 2 Place the Back log onto the back log rest as shown below in figure 24a The log has lip on the bottom which fits into the slot on the log rest 3 Place the Front log onto the front log ...

Страница 13: ... the tabs past the slots in the bottom of the shell See Inset 2 Store the screws and clamps in a safe place to ensure that they are not lost To re install the insert simply reverse the steps above Figure 25 MD34 DV 2 insert INSET 1 Tab INSET 2 Mounting Bracket Fresh Air Flex 4 dia High temp silicone seal Venting Plate Front Slot Removing and Installing the Door Removing the Door Removethetrim asde...

Страница 14: ...ation Model MD34 DV 2 3 Push in gas control knob slightly and turn clockwise to Off Do not force 4 Flip up lower trim 1 Turn off remote switch 2 Flip down lower trim 1 STOP Read the safety information above on this label 2 Flip down lower trims 3 Push in gas control knob and turn clockwise to OFF 4 Wait five 5 minutes to clear out any gas Smell for gas including near the floor If you then smell ga...

Страница 15: ...y to light any appliance n Do not touch any electrical switch do not use any phone in your building n Immediately call your gas supplier from a neighbour s phone Follow the gas supplier s instructions 1 Turn off remote switch 2 Flip down lower trim 3 Turn the switch on the gas control to Off 4 Flip up trim 1 STOP Read the safety information above on this label 2 Flip down lower trims 3 Turn switch...

Страница 16: ...e glass This is a normal condition and is the result of burning of protective coatings on new metal n Glass must be cleaned periodically to remove any film which is a normal biproduct of combustion which may be visible Film can easily be removed by removing the door as shown on page 13 Handle the door carefully and clean it with non abrasive glass cleaners One of the most effective products is Kel...

Страница 17: ...V9500 SV9600 Check Transformer Line Volt Supply Replace SV9500 SV9600 Save old Igniter Flame Rod Assembly for service INSET HSI Terminals CHECK Line voltage power Low voltage transformer Limit Controller Thermostat Wiring Air proving switch on combustion air blower system Vent damper if used is open and end switch made Gas Control Valve Figure 28 Sit Nova 820 gas valve Pilot Burner Adjustment 1 Lo...

Страница 18: ...cause damage to the Gas Appliance will produce excessive temperatures and will result in a fire hazard Limitations On Liability Limitations On Liability Limitations On Liability Limitations On Liability Limitations On Liability It is expressly agreed and understood that The Companies sole obligation and purchaser s exclusive remedy under this Warranty under any other warranty expressed or implied ...

Страница 19: ...ited States 6 feet 1 8 m minimum in Canada L clearance to nonmechanical air supply inlet to building or the combustion air inlet to any other appliance 16 inches 41 cm minimum for appliances 100 000 BTU H 30kW M clearance to mechanical air supply inlet 6 feet 1 8 m minimum N clearance above paved sidewalk or a paved driveway located on public property 7 feet 2 1 m minimum P clearanceunderveranda p...

Страница 20: ...Canadian Heating Products Inc Langley BC V4W 4A1 Montigo Del Ray Corp Ferndale WA 98248 XG0106B Rev 07 07 02 ...

Отзывы: