Page 4

Part  No.  XG0106B

MD34-DV-2 Homefire

Vent  Installation

This section covers the installation of direct venting and terminations.

Installation Requirements

n

MD34-DV-2 fireplaces are certified for use with Montigo Standard
Series  (4" / 7")  venting  components

n

Minimum  1" clearance to combustibles required  for  vent  pipes

n

Use  only 

certified  Montigo  vent  components.

  (Use  of  other

parts  will  void  the  Montigo  warranty,  and  may  impede  the
operation  of  the  fireplace.)

n

All joints must be secured with a minimum of two screws per joint

n

Vent terminations must not be recessed in walls or siding

n

Horizontal runs must be supported by a minimum of two supports
per horizontal run. A minimusm of one screw on each side of
support is also required

n

Flex vent sections may be stretched up to 50% of their total length
(eg. a 24" section may be stretched to 36")

n

Maximum horizontal run for a flex section with no vertical rise is 3 feet.

n

Flex vent sections over 3 feet must fall within the limits set by the
venting graph and must have a minimum vertical rise of 3 inches
per foot of flex.

n

Solid vent sections may be cut less than half way from the tapered end

n

Venting components can be used in any combination of solid/rigid
pipe or flex pipe and in any orientation (Male connectors can face
in any direction)

Vent Terminations

Selecting A Termination Location

Choosing your vent termination location will help to determine whether
you need to use a top vent or rear vent fireplace. Figure 6, below,
shows typical fireplace locations and the venting options they provide.

For a more detailed diagram of allowed termination locations, see
Appendix B.

Cautions:

Cautions:

Cautions:

Cautions:

Cautions:

Installing The Gas Line

The gas line must be installed before finishing the MD34-DV-2 Fireplace.
Natural Gas requires a minimum  inlet gas supply  pressure of 5.5"
W.C. & a manifold pressure of 3.5" W.C. Propane Gas requires a
minimum inlet gas supply pressure of 11" W.C. & a manifold pressure of
10" W.C. Provision must also be made for a 1/8" N.P.T. plugged tapping
and be accessible for test gauge connection immediately upstream of the
gas supply controls to the appliance. The fireplace gas connection and
the main operating gas valve is located behind the removable brass trim
at the bottom of the unit and need only be attached to the gas line  with an
approved fitting, as required by the applicable installation codes.

Installation

Figure 6.

  

Fireplace locations and vent terminations.

Note:

After gas line is connected, each 

appliance connection

,

valve  and  valve  train

  must  be  checked  while  under

normal operating pressure with either a liquid solution, or
leak detection device, to locate any source of leak. Tighten
any areas where bubbling appears or leak is detected until
bubbling stops completely or leak is no longer detected.
DO  NOT use a flame of any kind to test for leaks.

Installing The Remote Switch

The MD34-DV-2's gas valve, located behind the lower brass trim, may
be connected to a wall switch. The valve generates its own power. This
is a millivolt circuit. Use only low voltage wire, and DO NOT connect any
external power to it.

Refer to Figure 28 for wiring requirements.

Note:  The switch location must not exceed 30' from the fireplace.

Figure 5.  

Gas line access.

During any pressure testing of the gas supply piping that excedes 1/2
psig (3.5 kPa), the appliance and its individual shutoff valve must be
disconnected from gas supply system.

When pressure testing the gas supply piping system at test pressures of
less than or equal to 1/2 psig (3.5 kPa), the appliance must be isolated
from the gas supply piping system by closing its individual manual shutoff
valve.

n

Vent terminations can be very hot. If the termination is less
than 7 feet above a public walkway, it should be fitted with a
certified Montigo Heat Guard. (Part no. MTKOG)

n

Do not obstruct, or attempt to conceal, the vent termination.
These actions will affect the operation of the fireplace, and
may be hazardous.

n

In heavy snow areas, take extra care to prevent snow buildup
from obstructing the vent termination.

Содержание Homefire plus MD34-DV-2

Страница 1: ...bor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Warning Improper installation adjustment alteration serviceormaintenancecancause injury or property damage Refer to this manual For assistance or additional information consult a qualified installer service agency or the gas supplier For Your Safety Do not store or use gasoline or othe...

Страница 2: ...ctory built gas fireplaces Installation repairs should be done by a qualified contractor Installations in Canada must conform to the current CAN CGA B 149 1 and 2 Gas Installation Code and local regulations If the optional air circulating fan kit is installed it must be electrically grounded in accordance with CSA C22 1 Canadian Electrical Code Part 1 and or Local Codes Installations in the USA mu...

Страница 3: ...raming depth may be reduced to 15 Framing WARNING When this appliance is installed directly on carpeting tile or any combustible material other than wood flooring it must be installed on a metal or wood panel extending the full width and depth of the appliance Rear Vent Clearances TheMD34 DV 2clearancestocombustiblematerialsare Top Rear Vent 7 Top Top Vent 35 Back 0 Side 1 Floor 0 Mantle 10 Cleara...

Страница 4: ...srequires a minimuminletgassupplypressureof11 W C amanifoldpressureof 10 W C Provision must also be made for a 1 8 N P T plugged tapping andbeaccessiblefortestgaugeconnectionimmediatelyupstreamofthe gassupplycontrolstotheappliance Thefireplacegasconnectionand themainoperatinggasvalveislocatedbehindtheremovablebrasstrim atthebottomoftheunitandneedonlybeattachedtothegasline withan approved fitting a...

Страница 5: ...2 12 12 MOSR 1 Frame the termination opening to 12 x 12 2 Fasten the MOSR frame to the interior side of the studs using a minimum of 4 screws 3 Insert the termination into the MOSR frame as shown here and attach by screwing through the four pilot holes in the termination MSR MTO 3 MTO 3F MTO 3 MTKOG 1 Ensure that the two long mounting brackets are facing the bottom of the termination See inset Thi...

Страница 6: ...s 78 and the horizontal run to the wall flange of the vent termination is 108 this would NOT be an acceptable installation 0 12 24 36 48 60 72 84 96 108 132 120 144 156 168 180 Horizontal Run in Hearth 0 12 24 36 48 60 72 84 96 108 Figure 8 Heat Shield Install by sliding over the vent pipe where it passes through combustible construction Heat Shields Due to high flue temperatures heat shields are ...

Страница 7: ...nstalled directly on the fireplace the height to the center of the termination is 44 Horizontal Venting Figure 9b Typical Top Vent installation The solid sections can be used in various combinations to obtain the desired vent run The vent run must fall within the limits set by the venting graph 90 Elbow MEXT Section Heat Shield Heat Shield MEL 90F F Elbow Termination Example 2 A10 sectionandelbow ...

Страница 8: ...n measured center to center of piping Example Typicalventinstallation 20 verticalvent 2 2 offsets required 25 of 20 5 max offset allowed Thisventingconfigurationmeetsrequirements A Termination MVTK 1 B Flex sections MFL 1 12 section MFL 2 24 section MFL 3 36 section MFL 4 48 section C Solid sections MEXT 1 12 section MEXT 2 24 section MEXT 3 36 section MEXT 4 48 section D Support Ring Plate MSPXT ...

Страница 9: ...e hearth to the center of the termination is 26 1 8 MD34 DV 2 Rear Vent versions are supplied with an 18 extension pipe EXT 18 with female female connections For shorter installations cut the EXT 18 to the desired length For extended installations use the EXT 18 section as supplied for an 18 vent run Note For Rear Vent models maximum horizontal run with no vertical lift must never exceed 18 Flue C...

Страница 10: ...l run to the wall flange of the vent termination is 126 this would be an acceptable installation Example C Unacceptable Installation If the vertical dimension from the floor of the fire place is 78 and the horizontal run to the wall flange of the vent termination is 108 this would NOT be an acceptable installation Figure 19 MD34 DV 2 Rear Vent Venting Graph 0 12 24 36 48 60 72 84 96 108 132 120 14...

Страница 11: ...omponents Sheetrock Drywall Header 3 45 Painting Special care is recommended by the Master Painters and Decora tors Association when painting the fireplace surrounds to select and apply a quality Alkyd sealer prior to the applying of latex paints This is to prevent leaching of water from evaporation and causing a brownish staining effect to paint over coats Top of fireplace Combustible Facing Comb...

Страница 12: ...onal fan kit 115 1 60 Supply G L1 L2 Installing the Log Set Installing the Logs TheMD34 DV 2 issuppliedwithsixceramicfibrelogs Unpackthelogs and handle them very carefully 1 Remove the door cover and the glass door 2 Place the Back log onto the back log rest as shown below in figure 24a The log has lip on the bottom which fits into the slot on the log rest 3 Place the Front log onto the front log ...

Страница 13: ... the tabs past the slots in the bottom of the shell See Inset 2 Store the screws and clamps in a safe place to ensure that they are not lost To re install the insert simply reverse the steps above Figure 25 MD34 DV 2 insert INSET 1 Tab INSET 2 Mounting Bracket Fresh Air Flex 4 dia High temp silicone seal Venting Plate Front Slot Removing and Installing the Door Removing the Door Removethetrim asde...

Страница 14: ...ation Model MD34 DV 2 3 Push in gas control knob slightly and turn clockwise to Off Do not force 4 Flip up lower trim 1 Turn off remote switch 2 Flip down lower trim 1 STOP Read the safety information above on this label 2 Flip down lower trims 3 Push in gas control knob and turn clockwise to OFF 4 Wait five 5 minutes to clear out any gas Smell for gas including near the floor If you then smell ga...

Страница 15: ...y to light any appliance n Do not touch any electrical switch do not use any phone in your building n Immediately call your gas supplier from a neighbour s phone Follow the gas supplier s instructions 1 Turn off remote switch 2 Flip down lower trim 3 Turn the switch on the gas control to Off 4 Flip up trim 1 STOP Read the safety information above on this label 2 Flip down lower trims 3 Turn switch...

Страница 16: ...e glass This is a normal condition and is the result of burning of protective coatings on new metal n Glass must be cleaned periodically to remove any film which is a normal biproduct of combustion which may be visible Film can easily be removed by removing the door as shown on page 13 Handle the door carefully and clean it with non abrasive glass cleaners One of the most effective products is Kel...

Страница 17: ...V9500 SV9600 Check Transformer Line Volt Supply Replace SV9500 SV9600 Save old Igniter Flame Rod Assembly for service INSET HSI Terminals CHECK Line voltage power Low voltage transformer Limit Controller Thermostat Wiring Air proving switch on combustion air blower system Vent damper if used is open and end switch made Gas Control Valve Figure 28 Sit Nova 820 gas valve Pilot Burner Adjustment 1 Lo...

Страница 18: ...cause damage to the Gas Appliance will produce excessive temperatures and will result in a fire hazard Limitations On Liability Limitations On Liability Limitations On Liability Limitations On Liability Limitations On Liability It is expressly agreed and understood that The Companies sole obligation and purchaser s exclusive remedy under this Warranty under any other warranty expressed or implied ...

Страница 19: ...ited States 6 feet 1 8 m minimum in Canada L clearance to nonmechanical air supply inlet to building or the combustion air inlet to any other appliance 16 inches 41 cm minimum for appliances 100 000 BTU H 30kW M clearance to mechanical air supply inlet 6 feet 1 8 m minimum N clearance above paved sidewalk or a paved driveway located on public property 7 feet 2 1 m minimum P clearanceunderveranda p...

Страница 20: ...Canadian Heating Products Inc Langley BC V4W 4A1 Montigo Del Ray Corp Ferndale WA 98248 XG0106B Rev 07 07 02 ...

Отзывы: