EDVRSPV Vertical Power Vent System

Part No. XG1302 - 101201.2

f i r e   

f e a t u r e 

Installation

Figure 1.  

Typical Venting Installations.

Venting Installation

External Power Vent System must be used with a gas fireplace 

that is equipped with electronic ignition system. When installing 

the venting, the installation must adhere to the Vent Installation 

Section in the  fireplace's Installation Operation and Maintenance 

Instructions, as well as the following guidelines:

■Ensure that the planned termination location is acceptable 

as shown in Appendix A.

■ 

Maximum allowed vent run is 100 feet.

Figure 2.  

Multi-elbow Venting Installations.

Multi-Elbow Installations

Multi-elbow installations are possible up to a maximum of six 90° 

elbows.

V

Restrictor #1

Max V                         Max Elbows                     

100’ feet                             six 90

Elbow 1

Elbow 2

Elbow 3

Elbow 5

Elbow 4

H2

H1

V1

V2

V3

Restrictor #1

Max V1 + H1 +  V2 + H2 +  V3 + H3         Max Elbows                      

100’ feet                                                                  six 90

Installing the Power Vent

Figure 4.

Step 1.

 

        Construct a chase box around the vent penetration with 

exterior dimensions of 17"x 17" x 18"MIN in height. 

17”

17”

18”

Figure 3.  

Downward Venting Installations.

Downward Vertical Venting

Downward venting installations are only possible with gas fire

-

places equipped with electronic ignition system. Battery backup 

cannot be used with a power vent system.

Restrictor #1

Max V1 + H1 + D + H2 +  V3                     Max Elbows                     

100’ feet                                                                  six 90

Elbow 1

Elbow 2

Elbow 3

Elbow 5

H1

V1

D = 6’ foot

 

MAX

V3

H2

Elbow 4

Page 5

Содержание EDVRSPV Series

Страница 1: ...ll times Warning Improperinstallation adjustment alteration serviceormaintenancecancause injury or property damage Refer to this manual For assistance or additional information consult a qualified ins...

Страница 2: ...to address practices not related to personal injury Table Of Contents Important All dimensions and design specifications are subject to approval upon quotation of fire place and associated equipment C...

Страница 3: ...securely fastened and sealed to the flex pipe Fasten the termination to exterior of the building with water tight sealant and the appropriate fasteners General Information This installation guide cove...

Страница 4: ...f i r e f e a t u r e EDVRSPV Vertical Power Vent System Part No XG1302 101201 2 Installation Unit Dimensions Figure 1 EDVRPSV58 Dimensions Figure 1 EDVRPSV Page 4...

Страница 5: ...enting Installations Multi Elbow Installations Multi elbow installations are possible up to a maximum of six 90 elbows V Restrictor 1 Max V Max Elbows 100 feet six 90 Elbow 1 Elbow 2 Elbow 3 Elbow 5 E...

Страница 6: ...Vent Chase Electrical Harness with Connection 2 to 3 MAX Figure 5 Figure 7 Fasten Rough in Kit to framing Step 4 Install fasteners around perimiter of Rough in Kit Holes sup plied for ease of install...

Страница 7: ...stallation of Power Vent Module Figure 11 Installed Power Vent Module Step 8 Install 3 three stainless steel fasteners around Power Vent Module 120 degrees penetrating through the inner stain less ste...

Страница 8: ...em Part No XG1302 101201 2 Installation WARNING If you do not follow these instructions exactly a fire or explosion may result causing property damage personal injury or loss of life Figure 13 Standar...

Страница 9: ...ected to normal use The Gas Appliances are designed to burn gas only Burning conventional fireplace fuels such as wood coal or any other solid fuel will cause damage to the Gas Appliance will produce...

Страница 10: ...A I N A J N A K N A L N A M N A N N A P N A Q Clearance above a roof 24 inches 61 cm minimum Follow Local Codes R Clearance to adjacent walls and neighboring buildings 16 inches 46 cm minimum S N A T...

Страница 11: ...de directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half 1 2 inch in size GAS VE...

Страница 12: ...Canadian Heating Products Inc Langley BC V4W 4A1 Montigo Del Ray Corp Ferndale WA 98248 XG1302 101201 2 f i r e f e a t u r e...

Отзывы: