Monsoon MON-MEVDC400 Скачать руководство пользователя страница 7

 

Product Fiche 

 

 

 

 
 

 

 

 
 

 

 
 

 

 
 

 

 

 
 

 

 
 

 

 

 
 

 

 
 

 

 

 
 

 

 
 

 

 
 

 

 

 

 

 

 
 

 

 

 
 

 

 
 

 

 
 

 

 

 
 

 

Name:  

Monsoon 

Model ID (Stock Ref.) : 

MON-MEVDC400 

MON-MEVDCH400 

SEC Class 

SEC Value ('Average') 

-27.2 

SEC Value ('Warm') 

-11.7 

SEC Value ('Cold') 

-54.3 

Label Required? (Yes/No=Out of scope) 

Yes 

Declared as: RVU or NRVU/UVU or BVU 

RVU/UVU 

Speed Drive 

Multi Speed 

Type HRS (Recuperative, Regenerative, None) 

None 

Thermal Eff: [ (%), NA(if none)] 

N/A 

Max. Flow Rate (m3/h) 

338.8 

Max. Power Input (W): (@Max.Flow Rate) 

43 

LWA: Sound Power Level dB) 

46.4 

Ref. Flow Rate (m3/s) 

0.066 

Ref. Pressure Diff. (Pa) 

201 

SPI [W/(m3/h)] 

0.07 

Control Factor & Control Typology: (CTRL/ Typology) 

 

Control Factor; CTRL 

0.65 

Control Typology 

Local Demand Control 

Declared: -Max Internal & External Leakage Rates(%) for BVUs or carry over (for 
regenerative heat exchangers only), Ext. Leakage Rates (%) for Ducted UVUs; 

<5% Internal, <5% External 

Mixing Rate of Non-Ducted BVUs not intended to be equipped with one duct 
connection on either supply or extract air side; 

N/A 

Position and description of visual filter warning for RVUs intended for use with 
filters, including text pointing out the importance of regular filter changes for 
performance and energy efficiency of the unit 

N/A 

For UVUs (Instructions Install Regulated Supply/Extract Grilles Façade) 

In F&W 

Internet Address (for Disassembly Instructions) 

www.nationalventilation.co.uk 

Sensitivity p. Var20/-20 Pa: (for Non-Ducted VUs) 

N/A 

Air Tightness-ID/OD-(m3/h) (for Non-Ducted VUs) 

N/A 

Annual Electricity Consumption: AEC (kWh/a) 

0.4 

Annual Heating Saved: AHS (kWh/a) 

 

AHS: Average 

28.3 

AHS: Warm 

12.8 

AHS: Cold 

55.4 

Содержание MON-MEVDC400

Страница 1: ...on co uk monsoon domestic energysaver range mev energysaver systems PLEASE READ THIS QUICK START GUIDE IN CONJUNCTION WITH THE ILLUSTRATIONS PLEASE SAVE THIS QUICK START GUIDE IPX2 Quick Start Guide M...

Страница 2: ...gas or other fuel burning appliances This appliance is not intended for use by persons including children with reduced physical sensory or mental capabilities or lack of experience and knowledge unle...

Страница 3: ...1 2 If you need to use flexible ducting make sure that it is fully extended and not crushed sagging or torn 1 3 Try to minimize the use of diffusers valves by having similar length duct runs to the i...

Страница 4: ...his document for details 4 The switched live output 230Vac from any other switch or controller such as a simple latching pullcord or push button switch humidistat or PIR detector can be connected to t...

Страница 5: ...inputs 6 If the unit being commissioned is not fitted with the relevant hardware the associated menu options will not be available SERVICING MAINTENANCE WARNING THE FAN AND ANCILLARY CONTROL EQUIPMENT...

Страница 6: ...purge Purge threshold 1400 1800 PPM 1500 A1LA Analogue 1 low action Low Normal Boost or Purge speed Low A1HA Analogue 1 high action Low Normal Boost or Purge speed Purge A1tL Analogue 1 low threshold...

Страница 7: ...es for BVUs or carry over for regenerative heat exchangers only Ext Leakage Rates for Ducted UVUs 5 Internal 5 External Mixing Rate of Non Ducted BVUs not intended to be equipped with one duct connect...

Страница 8: ...cle where facilities exist Check with your local authority for recycling advice National Ventilation Stathe Road Burrowbridge Somerset TA7 0RY 496354 A 0720 Contact Information Website www nationalven...

Отзывы: