INSTALLATION 

 

Position the unit, taking into consideration the position of the rooms to be ventilated, the exhaust position 

and the electrical services. Ensure there is adequate access for installation and maintenance. 

 
If the unit is sited in the heated void of the dwelling a condensate drain should not be necessary. 

When sited in a cold loft, consideration should be given to fitment of a condensate drain. Alternatively the 

unit and ducting can be externally insulated to minimize condensation within the units housing. 

 

To reduce the system resistance in your duct system, and therefore lower the speed, power consumption 

and noise of the fan, follow these guidelines: 

1.1.

 

Keep the length of duct runs to a minimum, particularly the exhaust duct run. 

1.2.

 

If you need to use flexible ducting, make sure that it is fully extended and not crushed, 

sagging or torn. 

1.3.

 

Try to minimize the use of diffusers/valves by having similar length duct runs to the inlets. 

1.4.

 

The bend radius (measured to the inside of the bend), should be at least 1x the duct 
diameter.  

1.5.

 

Avoid having any bends, filters or other obstructions within 250mm of the fan inlets and 

outlet. 

 

Securely mount the unit through the mounting holes on the casing using appropriate fixings (not supplied) 

for the mounting substrate. Fixings to be capable of securing 4x the weight of the unit. Unit weight: 4.1kg. 
Anti-vibration mounts, acoustic mats or rubber bushes can also be used. 

 

Mounting point dimensions and installation example shown below: 
 

      

 

 

 

 

To maintain the IPX2 rating of the unit, the unit must not be 
mounted with the cover removal slots facing upwards,  

or at an angle where they are visible from above. 

All other orientations are acceptable. 

 

Содержание MON-MEVDC400

Страница 1: ...on co uk monsoon domestic energysaver range mev energysaver systems PLEASE READ THIS QUICK START GUIDE IN CONJUNCTION WITH THE ILLUSTRATIONS PLEASE SAVE THIS QUICK START GUIDE IPX2 Quick Start Guide M...

Страница 2: ...gas or other fuel burning appliances This appliance is not intended for use by persons including children with reduced physical sensory or mental capabilities or lack of experience and knowledge unle...

Страница 3: ...1 2 If you need to use flexible ducting make sure that it is fully extended and not crushed sagging or torn 1 3 Try to minimize the use of diffusers valves by having similar length duct runs to the i...

Страница 4: ...his document for details 4 The switched live output 230Vac from any other switch or controller such as a simple latching pullcord or push button switch humidistat or PIR detector can be connected to t...

Страница 5: ...inputs 6 If the unit being commissioned is not fitted with the relevant hardware the associated menu options will not be available SERVICING MAINTENANCE WARNING THE FAN AND ANCILLARY CONTROL EQUIPMENT...

Страница 6: ...purge Purge threshold 1400 1800 PPM 1500 A1LA Analogue 1 low action Low Normal Boost or Purge speed Low A1HA Analogue 1 high action Low Normal Boost or Purge speed Purge A1tL Analogue 1 low threshold...

Страница 7: ...es for BVUs or carry over for regenerative heat exchangers only Ext Leakage Rates for Ducted UVUs 5 Internal 5 External Mixing Rate of Non Ducted BVUs not intended to be equipped with one duct connect...

Страница 8: ...cle where facilities exist Check with your local authority for recycling advice National Ventilation Stathe Road Burrowbridge Somerset TA7 0RY 496354 A 0720 Contact Information Website www nationalven...

Отзывы: