Item Name Default Range
Description
There are four kind action mode can be selected. Stop
, Trip
,
Alarm
, Indicate
6
Action mode
Indicate
7
Setting
54 Hz
48 ~ 59 Hz 60 Hz system
45 Hz
40 ~ 50 Hz 50 Hz system
8
Timer
6 Sec.
1 ~ 10 Sec.
Minimum detect frequency
9 Checked
box
Checked Checked
/
Un-checked
Checked means enable this function.
10 Setting
30 Hz
10 ~ 45 Hz Low frequency protection will be disabled if frequency is under
this setting.
11 System frequency
60 Hz
50 / 60 Hz
Rated frequency of the generator system.
Sensor
page
Item Name
Default Range
Description
Low fuel level
1 Checked
box
Un-Checked Checked
/
Un-checked
Checked means enable this function.
2
Setting
20 %
6 ~ 55 %
Controller gives an alarm signal when this function is enabled
and the fuel level is under this setting.
Low lubricant pressure
3 Checked
box
Un-Checked Checked
/
Un-checked
Checked means enable this function.
4
Setting
20 PSI
15 ~ 60 PSI Controller gives an alarm signal when this function is enabled
and the value of the lubricant pressure sensor is under this
setting.
High
coolant
temperature
5 Checked
box
Un-Checked Checked
/
Un-checked
Checked means enable this function.
6 Setting
95
℃
85
~
110
℃
Controller gives an alarm signal when this function is enabled
and the value of the coolant temperature sensor is over this
setting.
7 Temperature
unit
℃
℃
/
℉
The unit of the temperature on the LCD display.
8
Pressure unit
PSI
PSI / BAR The unit of the pressure on the LCD display.
Escape lubricant pressure
9 Checked
box
Un-Checked Checked
/
Un-checked
Checked means enable this function.
*
Stop means controller shuts down the engine when the function is activated.
†
Trip means controller gives an open signal via Trip output (Trip output is normal close relay) when the function is activated.
‡
Alarm means controller gives a warning signal via Alarm output when the function is activated.
§
Indicate means controller indicates the fault signal via the indicator of the panel when the function is activated.