background image

34                                                                                                                                                                                 

44D0060

44D0060                                                                                                                                                                                                    

35

OBSERVED PROBLEM

When ignitor button is pressed, 
there is no spark at ODS/pilot.

Appliance  produces  unwanted 
odors.

Appliance shuts off during use.

Gas  odor  even  when  control 
knob is in OFF position.

When ignitor button is pressed, 
there is spark at ODS pilot, but 
no ignition.

POSSIBLE CAUSE

1.  Ignitor electrode positioned wrong.
2.  Ignitor electrode is broken.
3.  Ignitor  electrode  not  connected  to  ignitor 

cable.

4.   Ignitor cable pinched or wet. Keep ignitor cable 

dry.

5.  Broken ignitor cable.
6.  Bad piezo ignitor.

1.  Appliance  burning  vapors  from  paint,  hair 

spray, glues, etc.

2.  Gas leak.
3.  Initial burn off. 

1.  Not  enough  fresh  air  is  available  for  ODS/ 

pilot to operate.

2.  Low line pressure.
3.  ODS/pilot is partially clogged.
4.  Defective Thermopile.

5.  Restrictions in incoming air flow. 

1.  Gas leak.
2.  Control valve defective.

1.  Gas supply turned off or manual shutoff valve 

closed.

2.  Control knob not in PILOT position.
3.  Control knob not pressed in while in PILOT 

position.

4.  Air in gas lines when installed.

5.  ODS/pilot is clogged.

6.  Gas regulator setting is not correct.

REMEDY

1   Replace ignitor.
2.  Replace ignitor.
3.  Reconnect ignitor cable.
4.  Free  ignitor  cable  if  pinched  by  any 

metal or tubing.

5.  Replace ignitor cable.
6.  Replace piezo ignitor.

1.  Ventilate room. Stop using odor causing 

products while heater is running.

2.  Locate and correct all leaks.
3.  Ventilate  room  and  turn  unit  on  high 

until odor is gone. Odor should be gone 
after 2 to 3 hours of continuous use. 

1.  Open window and/or door for ventila-

tion.

2.  Contact local gas company.
3.  Clean ODS/pilot.
4.   Check  wire  connections.  Check  output 

should be 500 milli-volts across TH/TP 
and TP Terminals with ON/OFF switches 
off.

5.   Check  for  bottom  riser  on  glass  door, 

sunken  fireplace,  excessive  lava  rock/
cinders densely packed against grate. 

1.  Locate and correct all leaks.
2.  Replace control valve.

1.  Turn  on  gas  supply  or  open  manual 

shutoff valve.

2.  Turn control knob to PILOT position.
3.  Press  in  control  knob  while  in  PILOT 

position.

4.  Continue  holding  down  control  knob. 

Repeat  igniting  operation  until  air  is 
removed.

5.  Replace  ODS/pilot  assembly  or  get  it 

serviced.

6.  Check incoming pressure. Replace gas 

regulator.

Note: All troubleshooting items are listed in order of operation.

TROUBLESHOOTING

W

ARNING

Turn appliance OFF and allow to cool 
before  servicing.  Only  a  qualified 
service  person  should  service  and 
repair the heater.

W

ARNING

Содержание DEB20

Страница 1: ...o not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electric...

Страница 2: ...Control 21 Milli Volt Thermostat Control 21 Hi Lo Control 21 Electrical Wiring Milli volt 22 Connecting Remote Receiver 23 Installing Thermostat Sensor 23 Operation of Thermostat Sensor 25 Log Placem...

Страница 3: ...reference IMPORTANT Read these instructions carefully before installing or trying to operate this vent free gas heater 1 Due to high temperatures the appliance should be located out of traffic and aw...

Страница 4: ...isappear with continued use 20 Input ratings are shown in BTU per hour and are for elevations up to 2 000 feet For elevations above 2 000 feet input ratings should be reduced 4 percent for each 1 000...

Страница 5: ...Hand held Remote with receiver GETTING STARTED Carefully inspect the contents for shipping damage If any parts are missing or damaged immediately inform the dealer from whom you purchased the applian...

Страница 6: ...20PT THERMOSTAT 28 000 20 000 DEB24PT THERMOSTAT 38 000 30 000 DEB30PT THERMOSTAT 38 000 30 000 NATURAL GAS NOTE An external regulator is required to reduce supply pressure to a maximum of 10 1 2 W C...

Страница 7: ...o desired flame height Milli Volt and T Stat control has four 4 positions OFF All gas to the gas logs is shut off at the valve IGN Valve position to light maintain a standing pilot ON Valve position t...

Страница 8: ...ces installed in that space An unconfined space is defined as a space whose volume is not less than 50 cubic feet per 1 000 BTU per hour 4 8 m3 per kw of the aggregate input rating of all appliances i...

Страница 9: ...ion would be based only on the room with the heater BTU Hr 151 2 x 12 x 8 50 GENERAL INSTALLATION INFORMATION Figure 1 Example of a Large Room with 1 2 Wall Divider Counter Fireplace x 1000 x 1000 528...

Страница 10: ...ure for Gas Fired Decorative Type Unvented Room Heaters per IAS Requirement No 2 97 ANSI Z21 91 2001 typically referred to as a Universal Firebox as long as firebox hearth dimensions meet the minimum...

Страница 11: ...or bottom surface of the unit Refer to Table The log set should be placed against or as near as possible to the rear wall of the fireplace firebox Depth of fireplace firebox Refer toTable Figure 3 Ref...

Страница 12: ...n in Figures 4 through 12 and defined in the fireplace manufacturer s instructions are minimum clearances to maintain when installing this heater Left and right clearances are determined when facing t...

Страница 13: ...ese minimum clearances you must operate the heater with chimney flue damper open Refer to Installing Vented Applications found on page 18 HEAT RESISTANT REQUIREMENTS FOR SAFE INSTALLATION MATERIAL MEA...

Страница 14: ...ed Observe profile side elevations shown in Figure 7 page 15 elevations shown in Figure 9 page 16 8 to less than 12 Install hood and observe profiles shown Install hood and observe profiles shown in F...

Страница 15: ...the wall a maximum of 21 2 at a minimum of 14 above the opening and a maximum of 6 at a minimum of 201 2 above the opening Example A mantel may project from the wall a maximum of 21 2 at a minimum of...

Страница 16: ...um of 10 at a minimum of 28 above the CLEARANCES AND HEIGHT REQUIRMENTS Figure 10 is an example of an unsafe mantel installation This mantel projects 4 at 8 above the opening exceeding the maximum acc...

Страница 17: ...he top surface of carpeting tile etc See Figure 11 OR The gas log heater may be installed nearer to the floor if a minimum of 14 of noncombustible material such as slate or marble is installed between...

Страница 18: ...leaning performed annually after installation Seal any fresh air vents or ash clean out doors located on floor or wall of fireplace If not drafting may cause pilot outage or sooting Use a heat resista...

Страница 19: ...logs function as a system If the fireplace is spilling into the room check with a match or a smoke stick reposition the damper clamp until a positive draft is obtained by opening the damper If negati...

Страница 20: ...at the Pressure Tapping Point May Be Installed Use new black iron or steel pipe Internally tinned copper or copper tubing can be used per National Fuel Code section 2 6 3 providing gas meets hydrogen...

Страница 21: ...place tubing to pressure gauge over test point Use test point OUT closest to control knob After taking pressure reading be sure and turn captured screw clockwise firmly to re seal Do not over torque...

Страница 22: ...t one wire to TP TH and one wire to TH or connect the wall switch thermostat to the two male 0 25 terminals on the left side of the unit The color of the wires does not matter Figure 19 Wiring Diagram...

Страница 23: ...unit See Figure 20 7 Attach remote receiver with velcro pads Control switch must face forward NOTE Heat reduces battery life You can protect the receiver and extend battery life by mounting the recei...

Страница 24: ...sting wiring harness with two 2 0 250 male spade terminals for remote or t stat option See Figures 23 and 24 7 Install knob to shaft of t stat sensor See Figure 23 8 Place thermo bulb in front of the...

Страница 25: ...NTACTS READING TERMINALS SHOULD BE A COMPLETE 2 3 CLOSED MINIMUM SYSTEM 175 B THERMOPILE 1 2 OPEN MINIMUM OUTPUT 500 CHECKING SYSTEM OPERATION The milli volt system and individual com ponents may be c...

Страница 26: ...r five ceramic fiber logs Do not handle these logs with your bare hands Always wear gloves to prevent skin irritation from ceramic fibers After handling the logs wash your hands gently with soap and w...

Страница 27: ...ilot flame If the pilot flame does not touch the thermocouple then the main burner cannot function reliably See Figures 29 and 31 for incorrect shape of pilot flame MILLI VOLT CONTROL AND THERMOSTAT C...

Страница 28: ...oper burning will result During manufacturing fabricating and shipping various components of this appliance are treated with certain oils films or bonding agents These chemicals are not harmful but ma...

Страница 29: ...or s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department C Use only your hand to push in or turn the gas control knob Never use tools If the kno...

Страница 30: ...ping 7 With the control knob pushed in push and release the piezo ignitor button to light the ODS pilot The pilot is located on the left side of the heater behind the middle log and on the back of the...

Страница 31: ...in and release the piezo ignitor button to light the pilot 8 Continue pushing the control knob in for a further 10 seconds to prevent the flame detector from shutting off the gas while the probe is wa...

Страница 32: ...t is located on the left side of the heater behind the middle log and in front of the rear log If piezo ignitor does not light the pilot refer to Match Lighting Instructions page 33 8 Hold the gas con...

Страница 33: ...take holes clean will result in sooting and poor combustion Inspect and clean all burner ports Inspect ODS pilot for operation and accumulation of lint at air intake holes Verify flame pattern and log...

Страница 34: ...2 Replace ignitor 3 Reconnect ignitor cable 4 Free ignitor cable if pinched by any metal or tubing 5 Replace ignitor cable 6 Replace piezo ignitor 1 Ventilate room Stop using odor causing products whi...

Страница 35: ...clogged burner orifices 1 LP regulator shut down due to inlet pressure too high REMEDY 1 Press in control knob fully 2 After ODS pilot lights keep control knob pressed in for 30 seconds 3 Fully open...

Страница 36: ...MENT PARTS Failure to position the parts in accordance with these diagrams or failure to use only parts specifically approved with this appliance may result in property damage or personal injury WARNI...

Страница 37: ...urner Injector 1 44D0200 44D0202 44D0204 44D0206 9 ODS Pilot Assembly 1 26D2529 26D2530 26D2529 26D2530 10 Control Knob 1 18D0603 18D0603 18D0603 18D0603 11 Rear burner Injector 1 44D0201 44D0203 44D0...

Страница 38: ...4D1010K 44D1000K 44D1005K 3 Front Log 1 44D1012K 44D1002K 44D1007K 4 Left Log 1 N A 44D1003K 44D1008K 5 Top Log 1 44D1013K 44D1004K 44D1009K REPLACEMENT PARTS LIST Failure to position the parts in acc...

Страница 39: ...44D0060 39 NOTES...

Страница 40: ...in accordance with the installation instructions The Limited Lifetime Warranty will also be void if the appliance is not operated and maintained according to the operating instructions supplied with t...

Отзывы: