NB18/NB24 Gas Log Set
Monessen • NB18/24 Gas Log Set Installation/Owner's Manual • 81D0107 • Rev E • 04/18
FLOOR CLEARANCE
The gas log heater must be installed at least 1
3
⁄
8
" above
any combustible flooring material, such as carpeting or
tile, which is closer than 14" to the base of the fireplace.
The minimum distance must be maintained from the top
surface of carpeting, tile, etc.
Figure 10
OR
The gas log heater may be installed nearer to the floor if a
minimum of 14" of noncombustible material such as slate
or marble is installed between the base of the fireplace and
the combustible flooring.
Figure 11
Figure 10 -
Minimum Clearance above Combustible Flooring
FP2261
Min comb floor clear
Heater in Fireplace
or Firebox
Combustible
Material
1
3
⁄
8
" Minimum
FP2261
Figure 11 -
Minimum Clearance above Combustible Flooring with
Noncombustible Material Installed at Base of Fireplace
FP2262
Min noncomb floor clearance
14” Minimum
Heater in Fireplace
or Firebox
Combustible
Material
This Distance
May Now be
Less Than 1
3
⁄
8
"
FP2262