V
ENTING
R
EQUIREMENTS
10
Warning: Do not connect this appliance to a chimney flue serving a separate solid fuel burning appliance.
Carbon deposits (Soot) and creosote from solid fuels can clog the vent from the appliance causing
poisonous carbon monoxide to be released into the room in which the appliance is installed.
All vented gas-fired appliances when operating correctly produce small concentrations of carbon monoxide along
with other combustion products. Should something interfere with the operation of the appliance, it is possible for
the appliance to produce deadly quantities of poisonous carbon monoxide. All flue products from this appliance
must be vented to the outside at all times. Never operate an appliance designed to be vented without a correctly
working vent system connected to the appliance.
Warning: Venting of this appliance is one of the most important parts of the installation. Venting systems
must be installed and inspected according to these instructions and local codes or in the absence of local
codes, according to the National Fuel Gas Code Z223.1 - Latest edition, by a licensed or otherwise qualifed
installer.
Your local gas company should have copies of the National Fuel Code Z223.1 or other installation codes applicable
to your area.
Venting requirements and accepted methods vary greatly depending on the particular installation. It is impossible
to thoroughly define all possible installation circumstances in this manual. The following instructions and illustrations
are general guidelines only. All venting material must be instatlled according to local codes, or in the absence of
such codes, according to the National Fuel Gas Code Z223.1.
Warning: An improperly vented gas-fired appliance can lead to death from carbon monoxide posioning.
Venting materials are not provided with this appliance and must be purchased separately.
This appliance must be installed using 4" type “B” vent that has been listed by a nationally recognized testing
agency..
Attach the vent pipe to the appliance using four (4) sheet metal screws.
Vent must maintain minimum rise of ˘ inch per foot of horizontal run.
Venting terminals shall not be recessed into a wall or siding.
53D9015. Rev 1 03/03