50
5-572.10
MAINTENANCE
All heating equipment should be serviced before each heating
season to assure proper operations. The following items may
be required to have more frequent service schedule based on
the environment in which the unit is installed, and the frequency
of the equipment operation.
Electrical Wiring
The electrical wiring should be checked annually for loose
connections or deteriorated insulation.
Blower Assembly
The blower assembly includes the bearings, drive sheaves and belts.
Blower bearings should be checked and lubricated based on
the blower manufacturer’s recommendations. Bearings should
also be checked for any unusual wear and replaced if needed.
Drive sheaves should be checked at the same time the
bearings are inspected. Check to make sure the sheaves are
in alignment and are securely fastened to the blower and motor
shafts.Belt tension should be rechecked shortly after the unit
has been installed to check for belt stretching. After the initial
start-up, monthly checks are recommended.
A = 20'' x 25''
B = 16” x 25”
C = 20” x 16”
D = 15” x 25”
250/300
500/600
A
A
A
A
D
NON-ACCESS
SIDE
FILTER
SPACER
A
A
A
A
A
A
A
FILTER
SPACER
D
B
B
NON-ACCESS
SIDE
C
C
C
350/400
700/800
840/960
A = 20'' x 25''
B = 16” x 25”
C = 15” x 25”
250/300
500/600
A
A
FILTER
SPACER
B
B
C
C
350/400
700/800
FILTER
SPACER
FILTER
SPACER
A
A
A
A
A
A
A
A
A
A
C
C
B
B
B
B
B
B
200/225
100/125
150/175
75
FILTER SPACER TO BE INSERTED
ON NON-ACCESS SIDE OF UNIT
A
A
IMPORTANT
To check most of the Possible Remedies in the
troubleshooting guide listed in Table 55.1, refer to the
applicable sections of the manual.
CAUTION
Do not attempt to reuse any mechanical or electrical
controllers which have been wet. Replace defective controller.
WARNING
When servicing or repairing this equipment, use only factory-
approved service replacement parts. A complete replacement
parts list may be obtained by contacting Modine Manufacturing
Company. Refer to the rating plate on the appliance for
complete appliance model number, serial number, and
company address. Any substitution of parts or controls not
approved by the factory will be at the owner’s risk.
Figure 50.2 - Filter Replacement Arrangement for
EXTENDED Blower Size (Model Digit 16 = I, J, K, or L)
Filters
If the unit is supplied with a dirty filter switch and light, clean or
replace the filters any time the dirty filter light comes on.
Units which do not have a dirty filter warning light should have
the filters checked monthly. Clean or replace if necessary. In dirty
atmospheres, filter maintenance may be required more often.
Figure 50.1 - Filter Replacement Arrangement for
STANDARD Blower Size (Model Digit 16=A through H)