24
switches off -in the event of an alarm- after the pulse time has elapsed (default: 5
seconds). With pulse time
“0” it switches off when the alarm status is canceled.
O
utput behavior “RC” (remote control) means the output is switched on after the
incoming SMS command CODE O1ON (default: 1111 O1ON) and switches back
once the pulse time has elapsed. Switching time
“0” makes it only switches back
after the incoming SMS command CODE O1OFF (default: 1111 O1OFF).
The pulse time is adjustable between 1 and 9999 seconds. By default, the output
behavior is set to "ALARM" and the pulse time to "5" seconds.
5.21 TEST MESSAGE
When using the Mobeye Internet Portal: The Mobeye CML2285 can send regular
test messages (
keep alive
) to the Mobeye Internet Portal, to ensure the proper
functioning of the unit. The message will update the temperature in the status block.
The test message will also be sent if the unit is disarmed. The Mobeye Internet
Portal expects the test message and checks the timely receipt. The monitoring of the
test messages follows
the ‘management by exception’ rule: only if the message was
not received, the ‘service’ contacts will receive a notification.
The timing of the test message can be programmed. Since new settings (options)
will be synchronised after the test message, setting a specific time of the test
message can help the process of remote programming. Example: if you force a daily
test message at 17.30 hrs, you can prepare new settings and be sure they are
loaded into the device before the evening.
The interval between the test messages can be set between 0 days (no message)
and 30 days. The default test interval is set to "7" (weekly test message).
When using your own SIM card: The Mobeye CML2285 can send regular test SMS
messages (
keep alive
) to the first phone number (TEL1), to ensure the proper
functioning of the unit. It will include the actual temperature. The test message
function is only active if the unit is armed. The timing of the test message is
determined by the time of programming. The test time can also be programmed. The
interval between the test messages can be set between 0 days (no test message)
and 30 days. The default test interval is set to "0" (no test message).