•    Connect the luminaire to the mains supply via a suitable junction box (not included) ensuring the correct 

  polarity is observed: L - Live (brown), N - Neutral (blue) 

•    Connect the battery via the plug and socket to the inverter 
•    Place the battery and inverter into the ceiling void ensuring that there is at least 50mm 

  of clearance above and around them 

•    Lift both of the spring clips on the sides of the luminaire and push into the ceiling 
•    Switch on and check for correct operation, ensuring the green indicator LED is illuminated 
•    We recommend, on commissioning the installation, a minimum charge period of 24 hours before carrying 

  out an emergency duration test

•    If the batteries have been left in a discharged state for an extended period, we recommend that one or 

  more charge and discharge cycles are completed which should help to restore the battery capacity

Fig. 1

Содержание ENM5

Страница 1: ...INSTALLATION MAINTENANCE MANUAL ENM5...

Страница 2: ...fitted does not exceed the rating of the circuit cable fuse or circuit breaker Please note the IP Ingress Protection rating of this product when deciding the location for installation Allow 50mm abov...

Страница 3: ...d around them Lift both of the spring clips on the sides of the luminaire and push into the ceiling Switch on and check for correct operation ensuring the green indicator LED is illuminated We recomme...

Страница 4: ...nly do not use aggressive cleaning products or solvents which may damage the product Installing in areas where the temperature consistently drops below 0 C may shorten the battery life This product is...

Страница 5: ...of the batch code will invalidate the warranty If this product should fail within its warranty period it should be returned to the place of purchase for a free of charge replacement ML Accessories do...

Страница 6: ...off circuit breaker Ensure normal supply is restored after test and ensure charge indicator is illuminated Annual three hour duration test simulate a mains supply failure for three hour continuous tes...

Страница 7: ...If the luminaire fails any of the above tests please contact a qualified electrician See below for t sheet 230V 50Hz IP20 Class 2 Non Dim TA 0 45 house D...

Страница 8: ...DCSEPT21_V1 ML Accessories Limited LU5 4LT www mlaccessories co uk 54 INTERNATIONAL CONTACT DETAILS INTERNAT CONTACT D 0 45 C TA...

Отзывы: