Installation: electrical
Alternate installation (Modified S-PLAN)
For heat pumps with a dedicated DHW ON switched live input or
a configurable high temperature (HT) zone switched live input, the
recommended installation is as follows:
1.
Connect cylinder indirect control cable GREEN/YELLOW to HP
interface INDIRECT E.
2.
Connect cylinder indirect control cable BLACK to HP interface
INDIRECT COM.
3.
Connect cylinder indirect control cable BROWN to HP interface
INDIRECT NO.
4.
Connect cylinder indirect control cable GREY to HP interface
INDIRECT NC.
5.
Connect cylinder high limit stat. cable BROWN to HP interface
STAT COM.
6. Connect cylinder high limit stat. cable BLUE/BLACK to HP
interface STAT NC.
7. Connect cylinder exchanger circ. pump L, N, E to HP interface
PUMP L, N, E.
8.
Connect heat pump 3A supply L, N, E to HP interface HEAT PUMP
L, N, E.
9. Connect DHW 2-port diverter valve WHITE to 3A supply L.
10.
Connect DHW 2-port diverter valve BLUE to 3A supply N.
11.
Connect DHW 2-port diverter valve GREEN/YELLOW to 3A
supply EARTH.
12.
Connect DHW 2-port diverter valve BROWN to HP interface
SW_L.
13.
Connect DHW 2-port diverter valve ORANGE to heat pump
DHW ON/HT ZONE ON.
Full schematics for this installation can be found on
.
ENSURE 3-CORE CABLE USED FOR CIRCULATOR
PUMP HAS A MINIMUM CSA OF 0.5 mm
2
AND A
MINIMUM VOLTAGE RATING OF 240 VAC.