Self diagnosis function

We are constantly trying to do better service to our customers by installing such judges that show abnormality of each function as follows:

Outdoor heat exchanger fluid pipe
sensor error

Outdoor temperature sensor error

Trouble of outdoor unit

Over current

Broken outdoor sensor wire, poor connector connection

Compressor locking, open phase on compressor output,

shortcircuit on power transistor, closed service valve

Current cut

Description of trouble

Room temperature sensor error

Cause

Broken heat exchanger sensor wire, poor connector

connection

Indoor fan motor error

Heat exchanger sensor error

2 time flash

6 time flash

TIMER light ON

1 time flash

RUN light

2 time flash

1 time flash

TIMER light

2 time flash

3 time flash

1 time flash

RUN light keeps flashing

Over heat of compressor

Error of signal transmission

5 time flash

6 time flash

RUN light ON

Broken room temperature sensor wire, poor connector connection

Defective fan motor, poor connector connection

Broken heat exchanger fluid pipe sensor wire, poor connector

connection

Broken power transistor, broken compressor wire

Broken discharge pipe sensor wire, poor connector connection

Compressor blockage

Overload operation, overcharge

Gas shortage, defective discharge pipe sensor, closed service

valve

Defective power supply, Broken signal wire, defective in/outdoor

unit boards

2 time flash

RUN light 2 time flash

Rotor lock

Defective compressor

Open phase on compressor

Defective outdoor unit boards

4 time flash

Discharge pipe sensor error

Broken discharge pipe sensor wire, poor connector connection.

Outdoor fan motor error

7 time flash

Defective fan motor, poor connector connection

RKT012A755_En.p65

1/11/06, 5:38 PM

22

Black

Содержание SRK20ZFX-S

Страница 1: ...Deze airconditioner voldoet aan EMC Directive 89 336 EEC LV Directive 73 23 EEC Este acondicionador de aire cumple con la directiva EMC 89 336 EEC LV Directiva 73 23 EEC Este aparelho de ar condiciona...

Страница 2: ...cs of HEAT mode operation 9 Air flow direction adjustment procedure 10 SLEEP operation procedure 11 OFF TIMER operation procedure 11 ON TIMER operation procedure 12 SLEEP operation ON TIMER operation...

Страница 3: ...lectric shock Depending on the place of installation a circuit breaker may be necessary If you don t fit a circuit breaker you may cause an electric shock Do not install near places where inflammable...

Страница 4: ...ide or paint spray near the blower nor aim it directly at the system This may result in a fire Do not place anything containing wa ter like vases on top of the unit Water entering the unit could damag...

Страница 5: ...n be set as desired Page 13 When using the timer to switch on the sys tem should become operational shortly be fore the set time depending on the room temperature so that the desired temperature shoul...

Страница 6: ...gerant piping connection electric flex Up down air flow direction adjustment flap Page 10 Wireless remote control Page 7 Drain hose Drains water from the dehumidified air Left right air flow adjustmen...

Страница 7: ...eaning or others open the panel by 65 degrees and then pull it to this side In emergencies this button can be used for turning on off the unit when re mote control is not available Page 15 Removal ins...

Страница 8: ...FF timer and SLEEP operation RESET switch Switch for resetting microcomputer Page 16 Indication section TEMPERATURE indicator Indicates set temperature Does not indicate temperature when operation mod...

Страница 9: ...0 1 6 When 6 is indicated even if the button is pressed the indicator does not change Each time the button is pressed the switch over occurs in the following order 6 5 1 0 1 6 When 6 is indicated eve...

Страница 10: ...sult in condensation forming on the surface of the indoor unit leading to water drips Characteristics of HEAT mode operation Mechanism and capacity of HEAT mode operation Mechanism The unit draws in h...

Страница 11: ...lap stopped Left right direction can be adjusted with the AIRFLOW LEFT RIGHT button on the remote control Each time when you press this button the mode changes as follows Change to AIRFLOW LEFT RIGHT...

Страница 12: ...e air conditioner Press the SLEEP button 1 1 1 4 Press the OFF TIMER button The indication changes from blinking to steady lighting and the setting is complete The timer light yellow is on h The unit...

Страница 13: ...IMER s time Press the ON TIMER button The indication changes from blinking to steady lighting and the setting is complete The timer light yellow is on h Operation starts 5 to 60 minutes before the set...

Страница 14: ...at that time the operation starts 5 to 60 minutes before the timer is at ON The Amenity facility only func tions for COOL and HEAT op eration mode including AUTO It does not work for DRY mode About S...

Страница 15: ...eating The remote control indicates but the FAN SPEED indication is eraseed NOTE It will go into ECONOMY operation the next time the air condi tioner runs in the following instances 1 When the air con...

Страница 16: ...ter the power has been restored The following settings will be cancelled 1 Timer settings 2 HIGH POWER operations The power blackout auto restart function is set at on when the air conditioner is ship...

Страница 17: ...out old batteries Insert new batteries SUM 4 or R03x2 Close back lid When the indicator shows any abnormal condition Press the reset switch with the tip of a ballpoint pen 1 2 3 Attention to the and m...

Страница 18: ...hanger Stand firmly on a stepladder or other stable object when removing the inlet panel and filter Before maintenance Wipe the unit with a soft dry cloth There s a danger of electric shock Remove the...

Страница 19: ...ter from filter holder and inspect the filter Use a vacuum cleaner to remove any dust or dirt from the allergen clear filter Replace the allergen clear filter if it cannot be cleaned or if it has been...

Страница 20: ...e required Suitable installation position Is there any obstruction in front of the indoor unit preventing proper ventilation and functioning Don t install the unit in any of the following places Where...

Страница 21: ...The three minute protection timer in the microcomputer automatically starts up again Please wait for three minutes If the unit is operated for a long time in high humidity moisture may form on the air...

Страница 22: ...ON OFF but ton is pressed even after turning off the power switch and restarting the operation after 3 minutes the faulty move ment does not disappear A switch does not activate properly You hear a s...

Страница 23: ...time flash RUN light keeps flashing Over heat of compressor Error of signal transmission 5 time flash 6 time flash RUN light ON Broken room temperature sensor wire poor connector connection Defective...

Страница 24: ...Deze airconditioner voldoet aan EMC Directive 89 336 EEC LV Directive 73 23 EEC Este acondicionador de aire cumple con la directiva EMC 89 336 EEC LV Directiva 73 23 EEC Este aparelho de ar condiciona...

Отзывы: