background image

-

 60 

-

 '18 • SRK-T-250

 WARNING

WALL TYPE AIR-CONDITIONER

R32 REFRIGERANT USED

is leaked, together with an external ignition source, there is a 
possibility of ignition.

There is information included in the user’s manual and/or 
installation manual.

The user’s manual should be read carefully.

A service personnel should be handing this equipment with 
reference to the installation manual.

•  The precautionary items mentioned below are distinguished into two levels, 

 WARNING

 and 

 CAUTION

.

 WARNING

 : Wrong installation would cause serious consequences such as injuries or death.

 CAUTION

 : Wrong installation might cause serious consequences depending on circumstances.

 CAUTION

1.  General

•  That the installation of pipe-work shall be kept to a 

minimum.

•  That pipe-work shall be protected from physical 

damage.

•  That compliance with national gas regulations shall 

be observed.

•  That mechanical connections shall be accessible 

for maintenance purposes.

•  Keep any required ventilation openings clear of 

obstruction.

•  Servicing shall be performed only as recommended 

by the manufacturer.

2.  Unventilated areas

•  The appliance shall be stored in a well-ventilated 

area where the room size corresponds to the room 

3. 

•  The staff in servicing operations must hold the 

4.  Information on servicing

4.1  Checks to the area
•  Prior to beginning work on systems containing 

necessary to ensure that the risk of ignition is 
minimised.

•  For repair to the refrigerating system, 4.3 to 4.7 

shall be completed prior to conducting work on the 
system.

4.2  Work procedure
•  Work shall be undertaken under a controlled 

gas or vapour being present while the work is being 
performed.

4.3  General work area
•  All maintenance staff and others working in the 

local area shall be instructed on the nature of work 
being carried out.

• 
•  The area around the workspace shall be sectioned off.
•  Ensure that the conditions within the area have 

4.4  Checking for presence of refrigerant
•  The area shall be checked with an appropriate 

refrigerant detector prior to and during work, to 
ensure the technician is aware of potentially toxic or 

•  Ensure that the leak detection equipment being 

used is suitable for use with all applicable 
refrigerants, i.e.  
non-sparking, adequately sealed or intrinsically 
safe.

4.5 
•  If any hot work is to be conducted on the 

refrigeration equipment or any associated parts, 

available to hand. Have a dry powder or CO

2

extinguisher adjacent to the charging area.

4.6  No ignition sources
•  No person carrying out work in relation to a 

refrigeration system which involves exposing any 
pipe work shall use any sources of ignition in such 

explosion.

•  All possible ignition sources, including cigarette 

the site of installation, repairing, removing and 
disposal, during which refrigerant can possibly be 
released to the surrounding space.

•  Prior to work taking place, the area around the 

equipment is to be surveyed to make sure that 

•  “No Smoking” signs shall be displayed.

4.7  Ventilated area
•  Ensure that the area is in the open or that it is 

adequately ventilated before breaking into the 
system or conducting any hot work.

•  A degree of ventilation shall continue during the 

period that the work is carried out.

•  The ventilation should safely disperse any released 

refrigerant and preferably expel it externally into the 
atmosphere.

4.8  Checks to the refrigeration equipment
•  Where electrical components are being changed, 

•  At all times the manufacturer’s maintenance and 

service guidelines shall be followed.

•  If in doubt consult the manufacturer’s technical 

department for assistance.

•  The following checks shall be applied to 

– the charge size is in accordance with the room 

size within which the refrigerant containing parts 
are installed;

–  the ventilation machinery and outlets are 

operating adequately and are not obstructed;

–  if an indirect refrigerating circuit is being used, 

the secondary circuit shall be checked for the 
presence of refrigerant;

–  marking to the equipment continues to be visible 

and legible. Markings and signs that are illegible 
shall be corrected;

–  refrigeration pipe or components are installed in 

a position where they are unlikely to be exposed 
to any substance which may corrode refrigerant 
containing components, unless the components 
are constructed of materials which are inherently 
resistant to being corroded or are suitably 
protected against being so corroded.

4.9  Checks to electrical devices
•  Repair and maintenance to electrical components 

shall include initial safety checks and component 
inspection procedures.

•  If a fault exists that could compromise safety, then 

no electrical supply shall be connected to the circuit 
until it is satisfactorily dealt with.

•  If the fault cannot be corrected immediately but it 

is necessary to continue operation, an adequate 
temporary solution shall be used.

•  This shall be reported to the owner of the 

equipment so all parties are advised.

•  Initial safety checks shall include:

–  that capacitors are discharged: this shall be done 

in a safe manner to avoid possibility of sparking;

–  that no live electrical components and wiring are 

exposed while charging, recovering or purging 
the system;

–  that there is continuity of earth bonding.

5.  Repairs to sealed components

•  During repairs to sealed components, all electrical 

supplies shall be disconnected from the equipment 
being worked upon prior to any removal of sealed 
covers, etc.

•  If it is absolutely necessary to have an electrical 

supply to equipment during servicing, then a 
permanently operating form of leak detection shall 
be located at the most critical point to warn of a 
potentially hazardous situation.

•  Particular attention shall be paid to the following to 

ensure that by working on electrical components, 
the casing is not altered in such a way that the level 
of protection is affected. 
This shall include damage to cables, excessive 
number of connections, terminals not made to 

•  Ensure that the apparatus is mounted securely.
•  Ensure that seals or sealing materials have not 

degraded to the point that they no longer serve the 

atmospheres.

•  Replacement parts shall be in accordance with the 

NOTE
The use of silicon sealant can inhibit the effectiveness 
of some types of leak detection equipment.
Intrinsically safe components do not have to be 
isolated prior to working on them.

•  Strict compliance of the domestic laws must be 

observed when disposing the appliance.

•  Do not use means to accelerate the defrost operation 

process or to clean, other than those recommended 
by the manufacturer.

•  The appliance shall be stored in a room without 

continuously operating ignition sources (for example: 

operating electric heater. 

•  Do not pierce or burn.
•  Be aware that refrigerants may not contain an 

odour.

•  The indoor unit shall be stored in a room that has a 

minimum area of 4.0 m

2

.

RSA012A061A

C

(3)   Safety precautions in handling air-conditioners with flammable refrigerants

Содержание SRK 25ZS-W

Страница 1: ...Manual No 18 SRK T 250 TECHNICAL MANUAL INVERTER WALL MOUNTED TYPE RESIDENTIAL AIR CONDITIONERS Split system air to air heat pump type SRK20ZS W WB WT 25ZS W WB WT 35ZS W WB WT 50ZS W WB WT...

Страница 2: ...direction adjustment 65 5 Selection of the annual cooling function 64 63 4 Installing two air conditioners in the same room 63 3 Auto restart function 2 Unit ON OFF button 63 1 Operation control func...

Страница 3: ...pacity 2 0kW Model name SRK Wall mounted type SRC Outdoor unit S W 101 11 OPTION PARTS 123 12 TECHNICAL INFORMATION 101 117 1 Wired remote control 2 Interface kit SC BIKN2 E 3 Superlink E board SC ADN...

Страница 4: ...ossible Air filter Quality Quantity Polypropylene net Washable x 2 Shock vibration absorber Rubber sleeve for fan motor Rubber sleeve for fan motor compressor Electric heater Operation control Remote...

Страница 5: ...ir filter Quality Quantity Polypropylene net Washable x 2 Shock vibration absorber Rubber sleeve for fan motor Rubber sleeve for fan motor compressor Electric heater Operation control Remote control W...

Страница 6: ...Air filter Quality Quantity Polypropylene net Washable x 2 Shock vibration absorber Rubber sleeve for fan motor Rubber sleeve for fan motor compressor Electric heater Operation control Remote control...

Страница 7: ...lter Quality Quantity Polypropylene net Washable x 2 Shock vibration absorber Rubber sleeve for fan motor Rubber sleeve for fan motor compressor Electric heater Operation control Remote control Wirele...

Страница 8: ...ossible Air filter Quality Quantity Polypropylene net Washable x 2 Shock vibration absorber Rubber sleeve for fan motor Rubber sleeve for fan motor compressor Electric heater Operation control Remote...

Страница 9: ...ossible Air filter Quality Quantity Polypropylene net Washable x 2 Shock vibration absorber Rubber sleeve for fan motor Rubber sleeve for fan motor compressor Electric heater Operation control Remote...

Страница 10: ...possible Air filter Quality Quantity Polypropylene net Washable x 2 Shock vibration absorber Rubber sleeve for fan motor Rubber sleeve for fan motor compressor Electric heater Operation control Remote...

Страница 11: ...ble Air filter Quality Quantity Polypropylene net Washable x 2 Shock vibration absorber Rubber sleeve for fan motor Rubber sleeve for fan motor compressor Electric heater Operation control Remote cont...

Страница 12: ...uality Quantity Polypropylene net Washable x 2 Shock vibration absorber Rubber sleeve for fan motor Rubber sleeve for fan motor compressor Electric heater Operation control Remote control Wireless rem...

Страница 13: ...possible Air filter Quality Quantity Polypropylene net Washable x 2 Shock vibration absorber Rubber sleeve for fan motor Rubber sleeve for fan motor compressor Electric heater Operation control Remot...

Страница 14: ...ot possible Air filter Quality Quantity Polypropylene net Washable x 2 Shock vibration absorber Rubber sleeve for fan motor Rubber sleeve for fan motor compressor Electric heater Operation control Rem...

Страница 15: ...ssible Air filter Quality Quantity Polypropylene net Washable x 2 Shock vibration absorber Rubber sleeve for fan motor Rubber sleeve for fan motor compressor Electric heater Operation control Remote c...

Страница 16: ...1 0 00 0 33 0 88 0 00 0 00 0 00 0 00 SRK35ZS WB 11 5 1 21 0 00 0 33 0 88 0 00 0 00 0 00 0 00 SRK50ZS WB 12 0 1 21 0 00 0 33 0 88 0 00 0 00 0 00 0 00 SRK20ZS WT 11 5 1 21 0 00 0 33 0 88 0 00 0 00 0 00...

Страница 17: ...n the right side of the unit 2 To connect the wired remote control the interface kit SC BIKN2 E is required 120 19 60 24 167 45 45 870 290 Outlet for downward piping Refer to the top view 230 3 60 13...

Страница 18: ...7 42 5 40 40 138 4 33 5 15 8 290 540 20 14 6 16 4 260 130 270 Center of gravity Center of gravity Notes 1 The unit must not be surrounded by walls on the four sides 2 The unit must be fixed with ancho...

Страница 19: ...14 6 16 4 145 270 Terminal block 97 7 42 5 15 8 595 275 40 40 138 4 33 5 Center of gravity 69 4 Center of gravity Notes 1 The unit must not be surrounded by walls on the four sides 2 The unit must be...

Страница 20: ...19 18 SRK T 250 3 Remote control Unit mm 60 24 167 a Wireless remote control...

Страница 21: ...ere the average room temperature cannot be detected Place near the equipment to generate heat Place affected by outside air in opening closing the door Place exposed to direct sunlight or wind from ai...

Страница 22: ...2 0mm2 2 cores Under 300m Under 400m Under 600m Upper part Lower part Lower case Sheath Upper cace Board Wiring Upper Lower X Y Sheath Upper cace Board Wiring Upper Lower Y X Tighten the screws after...

Страница 23: ...WHITE RED YELLOW GREEN HEAT EXCHANGER 2 N 3 YELLOW GREEN ONLY 2 2 HEAT EXCHANGER 5 FUSE VARISTOR R AMP TERMINAL BLOCK MOTOR FAN LEFT MOTOR LOUVER MOTOR FLAP RIGHT MOTOR LOUVER HEAT EXCHANGER SENSOR 1...

Страница 24: ...e x number TH4 Discharge pipe temp sensor TH3 Outdoor air temp sensor TH2 Heat exchanger sensor L Reactor FMo Fan motor EEV Electric expansion valve coil CM Compressor motor CNTH CNFAN CNEEV CN20S Con...

Страница 25: ...ctor FMo Fan motor EEV Electric expansion valve coil CM Compressor motor CNTH CNFAN CNEEV CN20S Connector 20S 4 way valve coil Item Description BK Black Mark Color BL Blue RD Red WH White YE Yellow YG...

Страница 26: ...eating 56 dB A Cooling Heating ISO5151 T1 H1 Rated capacity value 10 20 30 40 50 60 70 10 20 30 40 50 60 70 63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000 Sound power level dB M...

Страница 27: ...g 56 dB A Level Heating 58 dB A Cooling Heating ISO5151 T1 H1 10 20 30 40 50 60 70 10 20 30 40 50 60 70 63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000 Sound power level dB Mid o...

Страница 28: ...g 61 dB A Level Heating 61 dB A Cooling Heating ISO5151 T1 H1 10 20 30 40 50 60 70 10 20 30 40 50 60 70 63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000 Sound power level dB Mid o...

Страница 29: ...g 61 dB A Level Heating 63 dB A Cooling Heating ISO5151 T1 H1 10 20 30 40 50 60 70 10 20 30 40 50 60 70 63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000 Sound power level dB Mid o...

Страница 30: ...000 4000 8000 63 125 250 500 1000 2000 4000 8000 Sound pressure level dB Standard 2x10 5 Pa Mid octave band frequency Hz Sound pressure level dB Standard 2x10 5 Pa Mid octave band frequency Hz Mike po...

Страница 31: ...N70 N20 10 20 30 40 50 60 70 10 20 30 40 50 60 70 63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000 Sound pressure level dB Standard 2x10 5 Pa Mid octave band frequency Hz Sound pr...

Страница 32: ...5 250 500 1000 2000 4000 8000 Sound pressure level dB Standard 2x10 5 Pa Mid octave band frequency Hz Sound pressure level dB Standard 2x10 5 Pa Mid octave band frequency Hz Mike position at highest n...

Страница 33: ...0 63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000 Sound pressure level dB Standard 2x10 5 Pa Mid octave band frequency Hz Sound pressure level dB Standard 2x10 5 Pa Mid octave ba...

Страница 34: ...20 30 40 50 60 70 10 20 30 40 50 60 70 63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000 Sound pressure level dB Standard 2x10 5 Pa Mid octave band frequency Hz Sound pressure lev...

Страница 35: ...63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000 Sound pressure level dB Standard 2x10 5 Pa Mid octave band frequency Hz Sound pressure level dB Standard 2x10 5 Pa Mid octave band...

Страница 36: ...125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000 Sound pressure level dB Standard 2x10 5 Pa Mid octave band frequency Hz Sound pressure level dB Standard 2x10 5 Pa Mid octave band f...

Страница 37: ...125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000 Sound pressure level dB Standard 2x10 5 Pa Mid octave band frequency Hz Sound pressure level dB Standard 2x10 5 Pa Mid octave band fr...

Страница 38: ...125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000 Sound pressure level dB Standard 2x10 5 Pa Mid octave band frequency Hz Sound pressure level dB Standard 2x10 5 Pa Mid octave band f...

Страница 39: ...0 63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000 Sound pressure level dB Standard 2x10 5 Pa Mid octave band frequency Hz Sound pressure level dB Standard 2x10 5 Pa Mid octave ba...

Страница 40: ...125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000 Sound pressure level dB Standard 2x10 5 Pa Mid octave band frequency Hz Sound pressure level dB Standard 2x10 5 Pa Mid octave band f...

Страница 41: ...10 20 30 40 50 60 70 63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000 Sound pressure level dB Standard 2x10 5 Pa Mid octave band frequency Hz Sound pressure level dB Standard 2x1...

Страница 42: ...500 1000 2000 4000 8000 Sound pressure level dB Standard 2x10 5 Pa Mid octave band frequency Hz Sound pressure level dB Standard 2x10 5 Pa Mid octave band frequency Hz N50 N30 N40 N60 N70 N20 N50 N30...

Страница 43: ...ssure level dB Standard 2x10 5 Pa Mid octave band frequency Hz Sound pressure level dB Standard 2x10 5 Pa Mid octave band frequency Hz N50 N30 N40 N60 N70 N20 N50 N30 N40 N60 N70 N20 10 20 30 40 50 60...

Страница 44: ...7D 5 PIPING SYSTEM Models SRK20ZS S 25ZS S Model SRK35ZS S Humidity sensor HD pipe pipe 4 way valve 4 way valve 5 PIPING SYSTEM Models SRK20ZS W 25ZS W SRK20ZS WB 25ZS WB SRK20ZS WT 25ZS WT Models SRK...

Страница 45: ...h1 Th21 Gas TH2 Heat exchanger sensor TH1 EEV Capillary tube Heat exchanger Model SRK50ZM S Indoor unit Outdoor unit Flare connection Flare connection Liquid pipe 6 35 Gas pipe 12 7 Service valve Heat...

Страница 46: ...e conditions as follows The net cooling and heating capacity can be obtained in the following way Net capacity Capacity shown on specification Correction factors as follows 1 Coefficient of cooling an...

Страница 47: ...apacity Piping length m Cooling Heating 7 1 0 1 0 10 0 99 1 0 15 0 975 1 0 20 0 965 1 0 25 0 95 1 0 Air inlet temperature of outdoor unit in CWB Adjustment coefficient 15 0 95 0 95 0 94 0 93 0 91 0 88...

Страница 48: ...56 2 34 2 64 2 33 2 70 2 31 2 84 2 44 2 95 2 40 32 2 18 2 07 2 31 2 15 2 50 2 32 2 58 2 31 2 64 2 29 2 79 2 43 2 90 2 38 34 2 11 2 00 2 25 2 12 2 44 2 29 2 53 2 29 2 59 2 27 2 74 2 41 2 85 2 37 35 2...

Страница 49: ...48 18 SRK T 250 8 APPLICATION DATA 1 Installation of indoor unit RLF012A100 Model SRK20 25 35 50 R410A REFRIGERANT USED...

Страница 50: ...49 18 SRK T 250...

Страница 51: ...50 18 SRK T 250...

Страница 52: ...51 18 SRK T 250...

Страница 53: ...52 18 SRK T 250...

Страница 54: ...53 18 SRK T 250...

Страница 55: ...54 18 SRK T 250...

Страница 56: ...55 18 SRK T 250...

Страница 57: ...56 18 SRK T 250 2 Installation of outdoor unit RWC012A068...

Страница 58: ...57 18 SRK T 250...

Страница 59: ...58 18 SRK T 250...

Страница 60: ...59 18 SRK T 250...

Страница 61: ...Where electrical components are being changed At all times the manufacturer s maintenance and service guidelines shall be followed If in doubt consult the manufacturer s technical department for assi...

Страница 62: ...gerants are recovered safely Prior to the task being carried out an oil and refrigerant sample shall be taken in case analysis is required prior to re use of reclaimed refrigerant It is essential that...

Страница 63: ...switch selects the CLEAN operation display brightness adjustment and PRESET operation ON TIMER button This button selects ON TIMER operation TIMER button This button is used for setting the current t...

Страница 64: ...t one unit can be operated with only one remote control a Setting the wireless remote control i Slide the cover and take out the batteries ii Disconnect the switching line next to the battery with wir...

Страница 65: ...n for 15 minutes continuously The wireless remote control displays HIGH POWER mark and the FAN SPEED display disappears a During the HIGH POWER operation the room temperature is not controlled When it...

Страница 66: ...the power suppressed in order to avoid an excessive cooling or heating The unit operate 1 5 higher than the setting temperature during cooling or 2 5 lower than that during heating The wireless remote...

Страница 67: ...uto operation a i ii Cooling Air flow selection Operation mode AUTO HI MED LO Heating Room temp Setting temp 5 C Room temp Setting temp 5 C Setting temp Room temp 5 C Setting temp Room temp 5 C HIGH P...

Страница 68: ...eration is set the unit operates by dropping the outdoor fan speed and the compressor speed 13 Night setback operation When the night setback operation is set the heating operation starts with the set...

Страница 69: ...This function can be used when it is necessary to adjust the brightness of unit display Note 1 When the unit displays self diagnosis or service mode brightness level is always LV2 Brightness level Run...

Страница 70: ...d air are satisfied is satisfied Total compressor operation time After finish of defrost operation C or less for 3 minutes continuously Total compressor operation time 20 115rps 20 115rps 20 86rps 20...

Страница 71: ...ls SRK35 50 Max 17 minutes and 30seconds Depends on an operation condition the time can be longer than 7 minutes 2 7 minutes Hot keep operation i Setting ii Contents of control Signal of wireless remo...

Страница 72: ...is selected during heating cooling or DRY mode the unit is operated in the previous operation mode d Setting temperature can be adjusted within the following range There is the relationship as shown...

Страница 73: ...d direction control is performed a When the vertical wind direction is set at other than the vertical swing the flaps change to the horizontal position b When the horizontal wind direction is set at o...

Страница 74: ...erature is in the range of P2 P3 the speed is reduced by 6 rps at each 30 seconds 2 When the temperature is P3 or higher the compressor is stopped 3 When the outdoor heat exchanger temperature is in t...

Страница 75: ...ature 50 50 44 30 50 Range A Range B 50 44 60 60 27 Release Release SRK20 25 35 SRK50 2 It checks the outdoor temperature TH2 once every hour to judge the operation range When either of the following...

Страница 76: ...with the fuzzy calculation exceeds the upper limit the upper limit value is maintained The lower limit of compressor speed is set to 27 rps and even if the calculated result becomes lower than that a...

Страница 77: ...shown in the figure below 3 Reset conditions 1 2 10 Reset conditions When either of the following condition is satisfied 1 The outdoor air temperature TH2 becomes 6 C 2 The compressor speed is 0 rps...

Страница 78: ...rps 20 rps 20 rps item i ii is satisfied Once the unit is stopped by this function it is not min 1 100 110 C 90 100 C 90 100 C SRK20 35 SRK50 i ii i ii i ii air conditioning has elapsed air condition...

Страница 79: ...st operation ii Contents of control 1 iii Reset condition When the compressor has been turned OFF 2 When the conditions of i above are satisfied the compressor stops Error stop occurs when the compres...

Страница 80: ...G PROCEDURES FOR ELECTRICAL EQUIPMENT 1 Cautions 2 Items to check before troubleshooting 3 Troubleshooting procedure If the air conditioner does not run at all Important YES YES YES NO NO NO NO YES Re...

Страница 81: ...80 18 SRK T 250 09 SRK DB 087D 4 Troubleshooting procedure If the air conditioner runs NO NO NO NO YES YES YES YES 81 82 88 82 88 service service...

Отзывы: