Specifications
Item
Q64TCRT Q64TCRTBW
Output signal
ON/OFF pulse
Rated load voltage
10 to 30VDC
Max. load current
0.1A/point 0.4A/common
Max. inrush current
0.4A 10ms
Leakage current at
OFF
0.1mA or less
Max. voltage drop at
ON
1.0VDC (TYP) 0.1A 2.5VDC (MAX) 0.1A
Transistor
output
Response time
OFF
→
ON: 2ms or less ON
→
OFF: 2ms or less
Insulation method
Between input and grounding
: Transformer insulation
Between input and channel
: Transformer insulation
Dielectric withstand voltage
Between input and grounding
: 500VAC for 1 minute
Between input and channel
: 500VAC for 1 minute
Insulation resistance
Between input and grounding
: 500VDC 20M
or more
Between input and channel
: 500VDC 20M
or more
Current sensor*1
The following current sensor
made by URD Co., Ltd.
Input accuracy
•
CTL-12-S36-8(0.0 to 100.0A)
•
CTL-6-P-H(0.00 to 20.00A)
Input accuracy
Full scale
×
(
±
1.0%)
Heater
disconnection
detection
specifications
Number of alert
delays
———
3 to 255
I/O occupied points *2
16 points/slot
(I/O assignment:
16 intelligent points)
32 points/2 slots
(Default I/O assignment:
16 free 16 intelligent
points)
Connection terminals
18-point terminal block
Two 18-point terminal blocks
Applicable wire size (mm
2
) 0.3
to
0.75
Applicable crimping terminals
R1.25-3,1.25-YS3,RAV1.25-3,V1.25-YS3A
Internal current consumption (A)
0.55
0.64
Weight (kg)
0.20
0.30
Outline dimensions (mm)
27.4 (W)
×
98 (H)
×
112 (D)
55.2 (W)
×
98 (H)
×
112 (D)
*1 : Only the current sensor of URD Co., Ltd. may be used.
*2 : When using the Q64TCRTBW, the device numbers of the I/O signals are
incremented by 16 points due to the empty points of the left-hand side slot.
In this manual, therefore, read the I/O signals as indicated below
depending on the module used.
Example) When the signal is indicated as Yn1
When using Q64TCRT: Y1
When using Q64TCRTBW: Y11
*3 : For the noise immunity, withstand voltage, insulation resistance and others
in the programmable controller system using this module, refer to the
power supply module specifications given in the used CPU module user's
manual.