(4) Refrigerant charging calculation (R2 system)
Sample connection (with 3 BC controller and 6 indoor units) (PURY-P700YSJM-A)
Amount of additional refrigerant to be charged
Refrigerant for extended pipes (field piping) is not factory-charged to the outdoor unit. Add an appropriate amount of refrigerant for each pipes on site.
Record the size of each high pressure pipe and liquid pipe, and the amout of refrigerant that was charged on the outdoor unit for future reference.
Calculating the amount of additional refrigerant to be charged
The amount of refrigerant to be charged is calculated with the size of the on-site-installed hige pressure pipes and liquid pipes, and their length.
Calculate the amount of refrigerant to be charged according to the formula below.
Round up the calculation result to the nearest 0.1kg. (i.e., 16.08 kg = 16.1 kg)
<Amount of additional refrigerant to be charged>
Calculating the amount of additional refrigerant to be charged
Amount of factory charged refrigerant
Outdoor unit model
P200
24.8kg
27.3kg
33.8kg
34.8kg
39.7kg
46.7kg
53.7kg
60.2kg
69.2kg 72.9kg
74.6kg
90.3kg
34.0kg
35.0kg
39.7kg
47.5kg 49.2kg
62.9kg
69.6kg 73.3kg
74.8kg
74.8kg
91.5kg
91.5kg
91.5kg
91.5kg
P250
P300
P350
P400
P450
P500
P550
P600
P650
P700
EP200
EP250
EP300
EP350
EP400
EP450
EP500
EP550
EP600
EP650
EP700
P750
P800
P850
P900
Maximum amount of
refrigerant *1
Maximum amount of
refrigerant *1
Outdoor unit model
The above calculation result of the amount of refrigerant to be charged must become below the value in the table below.
*1 Amount of additional refrigerant to be charged on site
Additional refrigerant
charge
(kg)
=
High pressure
pipe size
Total length of ø 28.58
x 0.36
(m) x 0.36(kg/m)
+
High pressure
pipe size
Total length of ø 22.20
x 0.23
(m) x 0.23(kg/m)
+
High pressure
pipe size
Total length of ø 19.05
x 0.16
(m) x 0.16(kg/m)
+
High pressure
pipe size
Total length of ø 15.88
x 0.11
(m) x 0.11(kg/m)
+
Liquid pipe size
Total length of ø 15.88
x 0.2
(m) x 0.20(kg/m)
+
Liquid pipe size
Total length of ø 12.7
x 0.12
(m) x 0.12(kg/m)
+
Liquid pipe size
Total length of ø 9.52
x 0.06
(m) x 0.06(kg/m)
+
Liquid pipe size
Total length of ø 6.35
x 0.024
(m) x 0.024(kg/m)
+
Total outdoor unit
Model
(E)P200
(E)P250 - (E)P500
(E)P550 - P900
Charged amount per
BC controller
(Standard / Main)
2.0 kg
3.0 kg
5.0 kg
+
Charged amount per
BC controller
(Main) HA-type
2.0 kg
+
BC controller
(Sub) Total units
1 unit
2 units
Charged amount
Charged amount
1.0 kg
2.0 kg
+
Total capacity
of connected
indoor units
-80
81 - 160
2.0 kg
2.5 kg
161 - 330
331 - 390
3.0 kg
3.5 kg
391 - 480
481 - 630
4.5 kg
5.0 kg
631 - 710
711 - 800
6.0 kg
8.0 kg
801 - 890
891 - 1070
9.0 kg
10.0 kg
1071 - 1250
1251 -
12.0 kg
14.0 kg
Outdoor unit
Model
P200
EP200
P250
P300
EP300
EP350
P350
P400
EP250
P450
Charged amount
9.5 kg
11.8 kg
Limitation of the amount of refrigerant to be charged
BC controller (Main BC)
IU
a
IU
C
b
IU
1 : P50
2 : P250
IU
BC controller (Sub BC)
BC controller (Sub BC)
B
c
d
IU
f
D
E
Joint
Joint kit
Joint
A
IU
e
F
H
OU
(Main unit)
OU
(Sub unit)
Reducer (P15-P50)
(attached with BC controller)
G
3 : P15
4 : P20
5 : P140
6 : P200
Outdoor Twinning kit
Sample calculation
Indoor
Outdoor
A: ø28.58 40m
1: 50
a: ø6.35
B: ø9.52
10m
2: 250
b: ø9.52
C:
3: 15
c: ø6.35
ø12.70 20m
4: 20
d: ø6.35
D:
5: 140
e: ø9.52
ø9.52
5m
6: 200
P700
The total length of each liquid line is as follows:
ø28.58: A = 40 m
ø22.2: F = 3 m
ø19.05: G = 1 m
ø12.70: C = 20 m
ø9.52: B + D + E + b + e + f = 35 m
ø6.35: a + c + d = 25 m
Therefore,
<Calculation example>
Additional refrigerant charge
= 40 × 0.36 + 3 × 0.23 + 1 × 0.16 + 20 × 0.12 + 30 × 0.06 + 25 × 0.024 + 5
+ 2 + 2 + 6
= 35.4 kg
f: ø9.52
E: ø9.52
5m
F: ø22.2
3m
10m
5m
5m
10m
5m
5m
G: ø19.05
1m