- 105 -
(2) Correction at frosting and defrosting
Due to frosting at the outdoor heat exchanger and the automatical defrosting operation, the heating capacity of the
outdoor unit should be considered by multiplying the correction factor which shown in the table below.
(2)-1 S series
Table of correction factor at frost and defrost
Outdoor inlet air temp. °C
WB
6
4
2
1
0
-2
-4
-6
-8
-10
-20
Outdoor inlet air temp. °F
WB
43
39
36
34
32
28
25
21
18
14
-4
PUHY-(E)P200YJM-A (-BS)
1.00
0.95
0.84
0.825
0.83
0.87
0.90
0.95
0.95
0.95
0.95
PUHY-(E)P250YJM-A (-BS)
1.00
0.95
0.84
0.825
0.83
0.87
0.90
0.95
0.95
0.95
0.95
PUHY-(E)P300YJM-A (-BS)
1.00
0.93
0.82
0.80
0.82
0.86
0.90
0.90
0.95
0.95
0.95
PUHY-P350YJM-A (-BS)
1.00
0.93
0.85
0.83
0.84
0.86
0.90
0.90
0.95
0.95
0.95
PUHY-(E)P400YJM-A (-BS)
1.00
0.95
0.90
0.87
0.88
0.89
0.90
0.95
0.95
0.95
0.95
PUHY-(E)P450YJM-A (-BS)
1.00
0.98
0.89
0.87
0.89
0.90
0.92
0.95
0.95
0.95
0.95
PUHY-(E)P500YSJM-A(1) (-BS)
1.00
0.98
0.89
0.86
0.89
0.90
0.92
0.95
0.95
0.95
0.95
PUHY-(E)P550YSJM-A (-BS)
1.00
0.94
0.87
0.86
0.87
0.88
0.90
0.90
0.93
0.93
0.93
PUHY-(E)P600YSJM-A(1) (-BS)
1.00
0.94
0.87
0.86
0.87
0.88
0.90
0.90
0.93
0.93
0.93
PUHY-(E)P650YSJM-A (-BS)
1.00
0.94
0.87
0.86
0.87
0.88
0.90
0.90
0.93
0.93
0.93
PUHY-(E)P700YSJM-A(1) (-BS)
1.00
0.98
0.89
0.88
0.89
0.90
0.92
0.95
0.95
0.95
0.95
PUHY-(E)P750YSJM-A (-BS)
1.00
0.98
0.89
0.88
0.89
0.90
0.92
0.95
0.95
0.95
0.95
PUHY-(E)P800YSJM-A(1) (-BS)
1.00
0.98
0.89
0.88
0.89
0.90
0.92
0.95
0.95
0.95
0.95
PUHY-(E)P850YSJM-A (-BS)
1.00
0.94
0.87
0.86
0.87
0.88
0.90
0.90
0.93
0.93
0.93
PUHY-(E)P900YSJM-A (-BS)
1.00
0.94
0.87
0.86
0.87
0.88
0.90
0.90
0.93
0.93
0.93
PUHY-P950YSJM-A (-BS)
1.00
0.94
0.87
0.86
0.87
0.88
0.90
0.90
0.93
0.93
0.93
PUHY-P1000YSJM-A (-BS)
1.00
0.94
0.87
0.86
0.87
0.88
0.90
0.90
0.93
0.93
0.93
PUHY-P1050YSJM-A(-BS)
1.00
0.94
0.87
0.86
0.87
0.88
0.90
0.90
0.93
0.93
0.93
PUHY-P1100YSJM-A(-BS)
1.00
0.94
0.87
0.86
0.87
0.88
0.90
0.90
0.93
0.93
0.93
PUHY-P1150YSJM-A(-BS)
1.00
0.94
0.87
0.86
0.87
0.88
0.90
0.90
0.93
0.93
0.93
PUHY-P1200YSJM-A(-BS)
1.00
0.94
0.87
0.86
0.87
0.88
0.90
0.90
0.93
0.93
0.93
PUHY-P1250YSJM-A(-BS)
1.00
0.94
0.87
0.86
0.87
0.88
0.90
0.90
0.93
0.93
0.93
(2)-3 HP (ZUBADAN) series
Table of correction factor at frost and defrost
Outdoor inlet air temp.
Outdoor inlet air temp.
PUHY-HP200,250,400,500Y(S)HM
F
WB
C
WB
-25
-13
0.95
-10
14
0.92
-8
18
0.87
-6
21
0.87
-4
25
0.87
-2
28
0.87
0
32
0.85
1
34
0.85
2
36
0.85
4
39
0.95
6
43
1.00
(2)-2 Y series
Table of correction factor at frost and defrost
Outdoor inlet air temp. °C
WB
6
4
2
1
0
-2
-4
-6
-8
-10
-15
Outdoor inlet air temp. °F
WB
43
39
36
34
32
28
25
21
18
14
5
PUMY-P100VHMB
PUMY-P125VHMB
PUMY-P140VHMB
PUMY-P100YHMB
PUMY-P112YHMB
PUMY-P125YHMB
PUMY-P140YHMB
1.00
1.00
1.00
1.00
1.00
1.00
1.00
0.98
0.98
0.98
0.98
0.98
0.98
0.98
0.86
0.86
0.86
0.86
0.86
0.86
0.86
0.85
0.85
0.85
0.85
0.85
0.85
0.85
0.89
0.90
0.95
0.95
0.95
0.95
0.95
0.89
0.90
0.95
0.95
0.95
0.95
0.95
0.89
0.90
0.95
0.95
0.95
0.95
0.95
0.89
0.90
0.95
0.95
0.95
0.95
0.95
0.89
0.90
0.95
0.95
0.95
0.95
0.95
0.89
0.90
0.95
0.95
0.95
0.95
0.95
0.89
0.90
0.95
0.95
0.95
0.95
0.95