background image

39

Air blows out for a while after

    HEAT operation is stopped.

Phone Calls From Customers

How to Respond

Note

 This is not a malfunction.

    The blower is operating just for cooling down the    
    heated-up air conditioner. This will be done within   
    1 minute.
    This control is conducted only when the HEAT   
    operation is stopped with the electric heater ON.

However, this control is also 

applied to the models which 

has no electric heater.

“STANDBY” will be displayed 

on the remote controller in 

case of 

 and 

.

“DEFROSTING” will be 

displayed on the screen in 

case of 

.

The airflow direction is changed

     during COOL operation.

 If the up/down vane is set to downward in COOL    

    operation, it will be automatically set to horizontal
    blow by the microcomputer in order to prevent 
    water from dropping down. 
    “1 Hr.” will be displayed on the remote controller if   
    the up/down vane is set to downward  with the fan
    speed set to be less than “LOW”. 

The airflow direction is changed

    during HEAT operation.

    (The airflow direction cannot be

    set by remote controller.)

 In HEAT operation, the up/down vane is 

    automatically controlled according to the 
    temperature of the indoor unit’s heat exchanger.
    In the following cases written below, the up/down 
    vane will be set to horizontal blow, and the setting 
    cannot be changed by remote controller.
    1) At the beginning of the HEAT operation
    2) While the outdoor unit is being stopped by
        thermostat or when the outdoor unit gets started
        to operate.
    3) During DEFROST operation
    The airflow direction will be back to the setting of 
    remote controller when the above situations are 
    released.

The airflow direction doesn’t

    change.

    (Up/down vane, left/right louver)

1) Check if the vane is set to a fixed position. 

         (Check if the vane motor connector is 
          removed.)
     2) Check if the air conditioner has a function for
          switching the air direction. 
     3) If the air conditioner doesn’t have that 
         function, “NOT AVAILABLE” will be displayed   
         on the remote controller when “AIR
         DIRECTION” or “LOUVER” button is pressed.

Something
is wrong 
with the 
blower…..

Something
is wrong 
with the 
airflow
direction….

 Check if you set ON/OFF timer.

    The air conditioner starts operating at the time    
    designated if ON timer has been set before.

 Check if any operations are ordered by distant

    control system or the central remote controller.  
    While “CENTRALLY CONTROLLED INDICATOR”
    is  displayed on the remote controller, the air  
    conditioner is under the control of external
    directive.

The air conditioner starts operating even though 
any buttons on the remote controller are not 
pressed.

 Check if you set ON/OFF timer.

    The air conditioner stops operating at the time   
    designated if OFF timer has been set before.

The air conditioner stops even though any 
buttons on the remote controller are not pressed.

There might be a case that 

“CENTRALLY CONTROLLED 

INDICATOR” will not be 
displayed.

There might be a case that 

“CENTRALLY 

CONTROLLED INDICATOR” 

will not be displayed.

 Check if power is recovered from power failure

    (black out).
    The units will automatically start operating when 
    power is recovered after power failure (black out) 
    occurs. This function is called “auto recovery 
    feature from power ”.

Check if any operations are ordered by distant

    control system or the central remote controller. 
    While “CENTRALLY CONTROLLED INDICATOR”  is 
    displayed  on the remote controller, the air conditioner is 
    under the control of external directive.

OCH533A

Содержание PUHZ-SW100VHA-BS.UK

Страница 1: ...of model PUHZ SW75VHA BS PUHZ SW100VHA BS PUHZ SW100YHA BS PUHZ SW120VHA BS PUHZ SW120YHA BS Note This manual describes only service data of the outdoor units PUHZ SW75VHA BS UK PUHZ SW100VHA BS UK PU...

Страница 2: ...20X VM6B EHPT20X YM9B EHST20C VM6HB UK EHST20C YM9HB UK EHST20C VM6B UK EHST20C YM9B UK EHST20C VM6EB UK EHST20C YM9EB UK EHST20C VM6SB UK EHPT20X VM2HB UK EHPT20X VM6HB UK EHPT20X YM9HB UK EHPT20X VM...

Страница 3: ...rench Gas leak detector Charge hose Tools for R410A Contamination inside refrigerant piping can cause deterio ration of refrigerant oil etc If dirt dust or moisture enters into refrigerant cycle that...

Страница 4: ...7 Refrigerant cylinder Only for R410A Top of cylinder Pink Cylinder with syphon 8 Refrigerant recovery equipment 1 Cautions for service 1 Perform service after recovering the refrigerant left in unit...

Страница 5: ...ery device to collect the refrigerant Use new pipes for SW75 SW100 and SW120 models The existing pipe thickness does not meet speci cations or the pipes are damaged 2 4 PRECAUTIONS FOR SALT PROOF TYPE...

Страница 6: ...29 0 17 0 22 0 24 0 27 0 36 0 Nominal dimensions inch Flare nut dimensions Outside diameter Dimension B mm R410A R22 Gauge manifold Charge hose Gas leak detector Refrigerant recovery equipment Refrige...

Страница 7: ...nt level regardless of the length 10m max and 5m min of piping The additional refrigerant charging work during installation often causes prob lems Heretofore it is completely eliminated This unique sy...

Страница 8: ...C 45 C Cooling A35 W7 Outside air temperature Dry bulb 35 C Outside air temperature Wet bulb 24 C Water temperature inlet outlet 12 C 7 C Cooling A35 W18 Outside air temperature Dry bulb 35 C Outside...

Страница 9: ...Single 50Hz 230V OUTDOOR UNIT REFRIGERANT PIPING 1 3 19 A kW W kW min CFM dB dB mm in mm in mm in kg lbs kg lbs L mm in mm in Power supply phase cycle voltage Max current External finish Refrigerant c...

Страница 10: ...ower supply phase cycle voltage Max current External finish Refrigerant control Compressor Model Motor output Starter type Protection devices Crankcase heater Heat exchanger Fan Fan drive No Fan motor...

Страница 11: ...PUHZ SW120VHA BS UK PUHZ SW120YHA UK PUHZ SW120YHA BS UK 4 6 4 8 5 0 5 6 6 2 6 8 7 5 4 6 U V U W W V Service Ref Compressor model Winding Resistance ANB33FNEMT at 20 C 0 19 0 19 0 19 PUHZ SW100VHA UK...

Страница 12: ...500 1000 2000 4000 8000 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE OCTAVE BAND SOUND PRESSURE LEVEL dB 0 dB 0 0002 bar NC 60 NC 50 NC 40 NC 30 NC 20 NC 70 PUHZ SW100VHA UK PUHZ SW100VHA BS...

Страница 13: ...kout Front trunking hole Knockout Power supply wiring hole 2 27Knockout 9 2 40 45 65 92 27 55 23 73 63 Rear piping hole Knockout Rear trunking hole Knockout Power supply wiring hole 2 27Knockout 9 2 E...

Страница 14: ...27Knockout W 92 92 65 45 40 27 55 23 73 63 Front piping hole Knockout Front trunking hole Knockout Power supply wiring hole 2 W27Knockout W 9 2 145 145 220 30 145 81 219 71 71 Bottom piping hole Knock...

Страница 15: ...F1 F2 F3 F4 X51 X52 X54 Switch Function Switch Model Select Switch Model Select Switch Function Switch Switch Function Switch Switch Function Switch Switch Pump Down Connector Emergency Operation Con...

Страница 16: ...n Connector Emergency Operation Connector Connection for Option Connector Connection for Option Connector Connection for Option Connector Connection for Option Connector Connection for Option LED Oper...

Страница 17: ...witch Pump Down Connector Emergency Operation Connector Connection for Option Connector Connection for Option Connector Connection for Option Connector Connection for Option Connector Connection for O...

Страница 18: ...e NOT always against the ground S3 terminal has DC 24 V against S2 terminal However between S3 and S1 these terminals are NOT electrically insulated by the transformer or other device S1 S2 S3 S1 S2 S...

Страница 19: ...flow in heating Pressure sensor 63HS Low pressure switch 63L PUHZ SW100VHA PUHZ SW100VHA BS PUHZ SW100YHA PUHZ SW100YHA BS PUHZ SW75VHA UK PUHZ SW75VHA BS UK PUHZ SW120VHA PUHZ SW120VHA BS PUHZ SW120...

Страница 20: ...tch to ON again 3 Because the unit automatically stops in about 2 to 3 minutes when the refrigerant collecting operation is completed LED1 off LED2 lit be sure to quickly close the gas stop valve If L...

Страница 21: ...heck the symptom and check the installation environment refrigerant amount weather when the trouble occurred matters related to wiring and etc 2 Reset error code logs and restart the unit after nishin...

Страница 22: ...ard V the noise filter Y Refer to 10 7 4 Check connection of reactor DCL or ACL SW75VHA Check connection of LO and NO on the outdoor noise filter circuit board Check connection of R and S on the outdo...

Страница 23: ...oor unit connecting wire Total wiring length 80m including wiring connecting each indoor unit and between indoor and outdoor unit Also check if the connection order of flat cable is S1 S2 S3 3 Check t...

Страница 24: ...minutes after and during defrosting 1 Disconnection or contact failure of connector TH4 TH34 on the outdoor controller circuit board 2 Defective thermistor 3 Defective outdoor controller circuit board...

Страница 25: ...rd U6 Power module Check abnormality by driving power module in case overcurrent is detected UF or UP error condition 1 Outdoor stop valve is closed 2 Decrease of power supply voltage 3 Looseness disc...

Страница 26: ...wiring SW VHA 4 Replace outdoor power circuit board SW VHA 5 Replace outdoor power circuit board SW100 120V YHA 6 Replace outdoor noise filter circuit board SW75VHA 7 Replace outdoor converter circui...

Страница 27: ...1 Disconnection of compressor wiring 2 Defective circuit of current sensor on outdoor power circuit board 3 Decrease of power supply voltage 1 Correct the wiring U V W phase to compressor Refer to 10...

Страница 28: ...ng abnormality If the unit is not normal after replacing indoor controller board in group control indoor controller board of address 0 may be abnormal 1 Contact failure at transmission wire of remote...

Страница 29: ...the other to sub 2 Remote controller is connected with only one indoor unit 3 The address changes to a separate setting 4 6 Diagnose remote controller a When RC OK is displayed remote controllers hav...

Страница 30: ...detects Tcond C or more and compressor operation frequency is less than or equal to 25 Hz Detection is inoperative during defrosting 1 Overcharge of refrigerant 2 Defective refrigerant circuit clogs...

Страница 31: ...perature adjuster turns on the compressor will not stop operating even if tem perature adjuster is turned off Compressor stops operating immediately when turning off by the remote controller 12Normal...

Страница 32: ...nnot be set Are timer settings invalid If the timer can be set WEEKLY SIMPLE or AUTO OFF appears in the remote controller display PLEASE WAIT appears in the remote controller display The initial setti...

Страница 33: ...after turning on the main power Normal The start up diagnosis will be over in around 2 minutes Miswiring of indoor outdoor connecting wire Breaking of indoor outdoor connecting wire S3 Defective indoo...

Страница 34: ...oard are blown Check the wiring of the outdoor unit Check if the wiring is bad Check if the fuses are blown The fuses on the outdoor controller circuit board will be blown when the indoor outdoor conn...

Страница 35: ...oor controller circuit board Replace the outdoor controller circuit board Normal Only the unit which has the refrigerant address 0 supplies power to the remote controller Set the refrigerant address t...

Страница 36: ...act of the remote controller wire Check the voltage of the terminal block TB5 connecting the remote controller wire If it is not between DC 10V and DC16V the indoor controller board must be defective...

Страница 37: ...r FILTER from the display See the operation manual that came with the product for how to clean the filters STANDBY is displayed on the screen This is displayed when the unit starts HEAT operation when...

Страница 38: ...r unit is controlling the airflow amount in order to keep the optimum operating condition A sound similar to water flowing is heard from the unit This is not a malfunction This is the sound which is h...

Страница 39: ...airflow direction doesn t change Up down vane left right louver 1 Check if the vane is set to a fixed position Check if the vane motor connector is removed 2 Check if the air conditioner has a functio...

Страница 40: ...100YHA BS UK PUHZ SW120YHA BS UK 1 2 3 4 5 M Gray Orange Red Yellow Black Parts name Check points Disconnect the connector then measure the resistance with a tester At the ambient temperature 10 30 Th...

Отзывы: