TROUBLESHOOTING

10-1. TROUBLESHOOTING 

<Error code display by self-diagnosis and actions to be taken for service (summary)>

Present and past error codes are logged and displayed on the control board of outdoor unit. Actions to be taken for service, 
which depends on whether or not the trouble is reoccurring at service, are summarized in the table below. Check the contents 
below before investigating details.

Unit conditions at service

Error code

Actions to be taken for service (summary)

The trouble is reoccurring.

Displayed

Judge what is wrong and take a corrective action according to 
“10-3. Self-diagnosis action table”.

Not displayed

Conduct troubleshooting and ascertain the cause of the 
trouble.

The trouble is not reoccurring.

Logged

1

 Consider the temporary defects such as the work of 

protection devices in the refrigerant circuit including 
compressor, poor connection of wiring, noise and etc. Re-
check the symptom, and check the installation environment, 
refrigerant amount, weather when the  trouble occurred, 
matters related to wiring and etc.

2

 Reset error code logs and restart the unit after fi nishing 

service.

3

 There is no abnormality in electrical component, controller 

board, and etc.

Not logged

1

 Re-check the abnormal symptom.

2

 Conduct troubleshooting and ascertain the cause of the 

trouble.

3

 Continue to operate unit for the time being if the cause is 

not ascertained.

4

 There is no abnormality concerning of parts such as 

electrical component, controller board, and etc.

10-2. CHECK POINT UNDER TEST RUN

Before test run

After installation of outdoor unit, piping work and electric wiring work, re-check that there is no water leakage, loosened con-

nections and incorrect polarity.

Measure impedance between the ground and the power supply terminal block (L, N) on the outdoor unit by 500 V Megger 

and check that it is 1.0 M  or over.

Turn on power supply 12 hours before test run in order to protect compressor.

Make sure to read operation manual before test run. (Especially items to secure safety.)

OCH533A

Содержание PUHZ-SW100VHA-BS.UK

Страница 1: ...of model PUHZ SW75VHA BS PUHZ SW100VHA BS PUHZ SW100YHA BS PUHZ SW120VHA BS PUHZ SW120YHA BS Note This manual describes only service data of the outdoor units PUHZ SW75VHA BS UK PUHZ SW100VHA BS UK PU...

Страница 2: ...20X VM6B EHPT20X YM9B EHST20C VM6HB UK EHST20C YM9HB UK EHST20C VM6B UK EHST20C YM9B UK EHST20C VM6EB UK EHST20C YM9EB UK EHST20C VM6SB UK EHPT20X VM2HB UK EHPT20X VM6HB UK EHPT20X YM9HB UK EHPT20X VM...

Страница 3: ...rench Gas leak detector Charge hose Tools for R410A Contamination inside refrigerant piping can cause deterio ration of refrigerant oil etc If dirt dust or moisture enters into refrigerant cycle that...

Страница 4: ...7 Refrigerant cylinder Only for R410A Top of cylinder Pink Cylinder with syphon 8 Refrigerant recovery equipment 1 Cautions for service 1 Perform service after recovering the refrigerant left in unit...

Страница 5: ...ery device to collect the refrigerant Use new pipes for SW75 SW100 and SW120 models The existing pipe thickness does not meet speci cations or the pipes are damaged 2 4 PRECAUTIONS FOR SALT PROOF TYPE...

Страница 6: ...29 0 17 0 22 0 24 0 27 0 36 0 Nominal dimensions inch Flare nut dimensions Outside diameter Dimension B mm R410A R22 Gauge manifold Charge hose Gas leak detector Refrigerant recovery equipment Refrige...

Страница 7: ...nt level regardless of the length 10m max and 5m min of piping The additional refrigerant charging work during installation often causes prob lems Heretofore it is completely eliminated This unique sy...

Страница 8: ...C 45 C Cooling A35 W7 Outside air temperature Dry bulb 35 C Outside air temperature Wet bulb 24 C Water temperature inlet outlet 12 C 7 C Cooling A35 W18 Outside air temperature Dry bulb 35 C Outside...

Страница 9: ...Single 50Hz 230V OUTDOOR UNIT REFRIGERANT PIPING 1 3 19 A kW W kW min CFM dB dB mm in mm in mm in kg lbs kg lbs L mm in mm in Power supply phase cycle voltage Max current External finish Refrigerant c...

Страница 10: ...ower supply phase cycle voltage Max current External finish Refrigerant control Compressor Model Motor output Starter type Protection devices Crankcase heater Heat exchanger Fan Fan drive No Fan motor...

Страница 11: ...PUHZ SW120VHA BS UK PUHZ SW120YHA UK PUHZ SW120YHA BS UK 4 6 4 8 5 0 5 6 6 2 6 8 7 5 4 6 U V U W W V Service Ref Compressor model Winding Resistance ANB33FNEMT at 20 C 0 19 0 19 0 19 PUHZ SW100VHA UK...

Страница 12: ...500 1000 2000 4000 8000 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE OCTAVE BAND SOUND PRESSURE LEVEL dB 0 dB 0 0002 bar NC 60 NC 50 NC 40 NC 30 NC 20 NC 70 PUHZ SW100VHA UK PUHZ SW100VHA BS...

Страница 13: ...kout Front trunking hole Knockout Power supply wiring hole 2 27Knockout 9 2 40 45 65 92 27 55 23 73 63 Rear piping hole Knockout Rear trunking hole Knockout Power supply wiring hole 2 27Knockout 9 2 E...

Страница 14: ...27Knockout W 92 92 65 45 40 27 55 23 73 63 Front piping hole Knockout Front trunking hole Knockout Power supply wiring hole 2 W27Knockout W 9 2 145 145 220 30 145 81 219 71 71 Bottom piping hole Knock...

Страница 15: ...F1 F2 F3 F4 X51 X52 X54 Switch Function Switch Model Select Switch Model Select Switch Function Switch Switch Function Switch Switch Function Switch Switch Pump Down Connector Emergency Operation Con...

Страница 16: ...n Connector Emergency Operation Connector Connection for Option Connector Connection for Option Connector Connection for Option Connector Connection for Option Connector Connection for Option LED Oper...

Страница 17: ...witch Pump Down Connector Emergency Operation Connector Connection for Option Connector Connection for Option Connector Connection for Option Connector Connection for Option Connector Connection for O...

Страница 18: ...e NOT always against the ground S3 terminal has DC 24 V against S2 terminal However between S3 and S1 these terminals are NOT electrically insulated by the transformer or other device S1 S2 S3 S1 S2 S...

Страница 19: ...flow in heating Pressure sensor 63HS Low pressure switch 63L PUHZ SW100VHA PUHZ SW100VHA BS PUHZ SW100YHA PUHZ SW100YHA BS PUHZ SW75VHA UK PUHZ SW75VHA BS UK PUHZ SW120VHA PUHZ SW120VHA BS PUHZ SW120...

Страница 20: ...tch to ON again 3 Because the unit automatically stops in about 2 to 3 minutes when the refrigerant collecting operation is completed LED1 off LED2 lit be sure to quickly close the gas stop valve If L...

Страница 21: ...heck the symptom and check the installation environment refrigerant amount weather when the trouble occurred matters related to wiring and etc 2 Reset error code logs and restart the unit after nishin...

Страница 22: ...ard V the noise filter Y Refer to 10 7 4 Check connection of reactor DCL or ACL SW75VHA Check connection of LO and NO on the outdoor noise filter circuit board Check connection of R and S on the outdo...

Страница 23: ...oor unit connecting wire Total wiring length 80m including wiring connecting each indoor unit and between indoor and outdoor unit Also check if the connection order of flat cable is S1 S2 S3 3 Check t...

Страница 24: ...minutes after and during defrosting 1 Disconnection or contact failure of connector TH4 TH34 on the outdoor controller circuit board 2 Defective thermistor 3 Defective outdoor controller circuit board...

Страница 25: ...rd U6 Power module Check abnormality by driving power module in case overcurrent is detected UF or UP error condition 1 Outdoor stop valve is closed 2 Decrease of power supply voltage 3 Looseness disc...

Страница 26: ...wiring SW VHA 4 Replace outdoor power circuit board SW VHA 5 Replace outdoor power circuit board SW100 120V YHA 6 Replace outdoor noise filter circuit board SW75VHA 7 Replace outdoor converter circui...

Страница 27: ...1 Disconnection of compressor wiring 2 Defective circuit of current sensor on outdoor power circuit board 3 Decrease of power supply voltage 1 Correct the wiring U V W phase to compressor Refer to 10...

Страница 28: ...ng abnormality If the unit is not normal after replacing indoor controller board in group control indoor controller board of address 0 may be abnormal 1 Contact failure at transmission wire of remote...

Страница 29: ...the other to sub 2 Remote controller is connected with only one indoor unit 3 The address changes to a separate setting 4 6 Diagnose remote controller a When RC OK is displayed remote controllers hav...

Страница 30: ...detects Tcond C or more and compressor operation frequency is less than or equal to 25 Hz Detection is inoperative during defrosting 1 Overcharge of refrigerant 2 Defective refrigerant circuit clogs...

Страница 31: ...perature adjuster turns on the compressor will not stop operating even if tem perature adjuster is turned off Compressor stops operating immediately when turning off by the remote controller 12Normal...

Страница 32: ...nnot be set Are timer settings invalid If the timer can be set WEEKLY SIMPLE or AUTO OFF appears in the remote controller display PLEASE WAIT appears in the remote controller display The initial setti...

Страница 33: ...after turning on the main power Normal The start up diagnosis will be over in around 2 minutes Miswiring of indoor outdoor connecting wire Breaking of indoor outdoor connecting wire S3 Defective indoo...

Страница 34: ...oard are blown Check the wiring of the outdoor unit Check if the wiring is bad Check if the fuses are blown The fuses on the outdoor controller circuit board will be blown when the indoor outdoor conn...

Страница 35: ...oor controller circuit board Replace the outdoor controller circuit board Normal Only the unit which has the refrigerant address 0 supplies power to the remote controller Set the refrigerant address t...

Страница 36: ...act of the remote controller wire Check the voltage of the terminal block TB5 connecting the remote controller wire If it is not between DC 10V and DC16V the indoor controller board must be defective...

Страница 37: ...r FILTER from the display See the operation manual that came with the product for how to clean the filters STANDBY is displayed on the screen This is displayed when the unit starts HEAT operation when...

Страница 38: ...r unit is controlling the airflow amount in order to keep the optimum operating condition A sound similar to water flowing is heard from the unit This is not a malfunction This is the sound which is h...

Страница 39: ...airflow direction doesn t change Up down vane left right louver 1 Check if the vane is set to a fixed position Check if the vane motor connector is removed 2 Check if the air conditioner has a functio...

Страница 40: ...100YHA BS UK PUHZ SW120YHA BS UK 1 2 3 4 5 M Gray Orange Red Yellow Black Parts name Check points Disconnect the connector then measure the resistance with a tester At the ambient temperature 10 30 Th...