3. Fixing of horizontal vane
Horizontal vane of each air outlet can be fixed according to the environment, in which it is installed.
Setting procedure
1) Turn off the main power supply (Turn off the breaker).
2) Disconnect the vane motor connector of the direction of the arrow by pressing the unlocking button as shown in the figure
below.)
Electrically insulate the disconnected connector with vinyl tape.
Vane motor
Horizontal vane
Connector
Unlocking button
Vane motor
3) The vane angle can be fixed by turning the vame by hand.
The vane should remain within the angles shown in the
table below.
Measured standard
position of the grille
Horizontal vane
Standard of
horizontal position
Dimension A (mm)
26
29
33
37
Level 30
°
(Min.)
Downward 45
°
Downward 55
°
Downward 70
°
(Max.)
w
Dimension between 26mm and 37mm can be arbitrarily set.
Caution
Do not set the dimension out of the range.
It could cause dew drips and stains on the ceiling, etc. and the unit may be damaged.
<Set range>