PLFY-5
PLFY-P-NCMU-ER4, -NBMU-E2 (November 2015)
© 2015 Mitsubishi Electric US, Inc.
Model
PLFY-P24NBMU-E2
PLFY-P30NBMU-E2
PLFY-P36NBMU-E2
Power source
1-phase 208-230 V 60Hz
Cooling capacity *1
(Nominal)
Btu/h
24,000
30,000
36,000
kW
7.0
8.8
10.5
Power input
kW
0.05
0.05
0.09
Current input
A
0.47
0.50
0.87
Heating capacity *2
(Nominal)
Btu/h
27,000
34,000
40,000
kW
7.9
10.0
11.7
Power input
kW
0.04
0.04
0.08
Current input
A
0.40
0.43
0.80
External finish
Galvanized steel sheet
External dimension H x W x D
in.
11-3/4 x 33-3/32 x 33-3/32
mm
298 x 840 x 840
Net weight
lbs (kg)
60 (27)
Decoration
panel
Model
PLP-40BAU
External finish
Munsell No. (6.4Y 8.9/0.4)
Dimension
H x W x D
in.
1-3/8 x 37-13/32 x 37-13/32
mm
35 x 950 x 950
Net Weight
lbs (kg)
13 (6)
Heat exchanger
Cross fin
Fan
Type x Quantity
Turbo fan x 1
External
static pressure
in.WG
0.000 (208V)
Pa
0
in.WG
0.000 (230V)
Pa
0
Motor type
DC motor
Driving mechanism
Direct-driven
Airflow rate
(Low-Mid2-Mid1-High)
CFM
565 - 636 - 706 - 777
565 - 636 - 742 - 812
777 - 883 - 989 - 1,059
m3 / min
16.0 - 18.0 - 20.0 - 22.0
16.0 - 18.0 - 21.0 - 23.0
22.0 - 25.0 - 28.0 - 30.0
L / s
267 - 300 - 333 - 367
267 - 300 - 350 - 384
367 - 417 - 467 - 500
Sound pressure level (Low-Mid2-Mid1-High)
(measured in anechoic room)
dB <A>
28 - 31 - 34 - 37(208-230V)
28 - 32 - 35 - 37(208-230V)
35 - 38 - 41 - 43(208-230V)
Insulation material
PS
Air filter
PP honeycomb (long life filter, anti-bacterial type)
Protection device
Fuse
Refrigerant control device
LEV
Connectable outdoor unit
R410A CITY MULTI
Diameter of
refrigerant pipe
(O.D.)
Liquid (R410A)
in. (mm)
3/8 (9.52) Flare
Gas (R410A)
in. (mm)
5/8 (15.88) Flare
Field drain pipe size
in. (mm)
O.D. 1-1/4(32)
Drain lift mechanism
in. (mm)
33-7/16 (850)
Standard
attachment
Document
Accessory
Installation Manual, Instruction Book
Optional parts
External heater adapter
CN24RELAY-KIT-CM3
Air outlet shutter plate
PAC-SH51SP-E
High efficiency filter element (MERV 10)
PAC-SH59KF-E
Multi-function casement
PAC-SH53TM-E
i-see sensor corner panel
PAC-SA1ME-E
Flange for fresh air intake
PAC-SH65OF-E
Wireless signal receiver
PAR-SA9FA-E
Remark
Installation
Details on foundation work, duct work, insulation work, electrical wiring, power source switch,
and other items shall be referred to the Installation Manual.
Ventilation Air: Providing sufficient ventilation air is an important part of every building design.
ASHRAE standard 62 provides the minimum ventilation air requirements. Also check local codes.
1. SPECIFICATIONS
Note:
*1 Nominal cooling conditions
*2 Nominal heating conditions
Unit converter
Indoor:
80degF D.B. / 67degF W.B.
(26.7degC D.B. / 19.4degC W.B.)
70degF D.B. (21.1degC D.B.)
kcal/h = kW x 860
BTU/h = kW x 3,412
Outdoor:
95degF D.B. (35degC D.B.)
47degF D.B. / 43degF W.B.
(8.3degC D.B. / 6.1degC W.B.)
cfm = m3/min x 35.31
lbs = kg / 0.4536
Pipe length:
25 ft. (7.6 m)
25 ft. (7.6 m)
*Above specification data is subject to
rounding variation.
Level difference:
0 ft. (0 m)
0 ft. (0 m)
*Due to continuing improvement, above specification may be subject to change without notice.
PLFY-P24NBMU-E2, PLFY-P30NBMU-E2, PLFY-P36NBMU-E2