PLFY-4
PLFY-P-NCMU-ER4, -NBMU-E2 (November 2015)
© 2015 Mitsubishi Electric US, Inc.
Model
PLFY-P08NBMU-E2 *3
PLFY-P12NBMU-E2
PLFY-P15NBMU-E2
PLFY-P18NBMU-E2
Power source
1-phase 208-230 V 60Hz
Cooling capacity *1
(Nominal)
Btu/h
8,000
12,000
15,000
18,000
kW
2.4
3.5
4.4
5.3
Power input
kW
0.03
0.03
0.03
0.04
Current input
A
0.31
0.31
0.31
0.33
Heating capacity *2
(Nominal)
Btu/h
9,000
13,500
17,000
20,000
kW
2.7
4.0
5.0
5.9
Power input
kW
0.02
0.02
0.02
0.03
Current input
A
0.24
0.24
0.24
0.26
External finish
Galvanized steel sheet
External dimension H x W x D
in.
10-3/16 x 33-3/32 x 33-3/32
mm
258 x 840 x 840
Net weight
lbs (kg)
51 (23)
Decoration
panel
Model
PLP-40BAU
External finish
Munsell No. (6.4Y 8.9/0.4)
Dimension
H x W x D
in.
1-3/8 x 37-13/32 x 37-13/32
mm
35 x 950 x 950
Net Weight
lbs (kg)
13 (6)
Heat exchanger
Cross fin
FAN
Type x Quantity
Turbo fan x 1
External static
pressure
in.WG
0.000 (208V)
Pa
0
in.WG
0.000 (230V)
Pa
0
Motor type
DC motor
Driving mechanism
Direct-driven
Airflow rate (Low-
Mid2-Mid1-High)
CFM
494 - 530 - 547 - 565
494 - 530 - 547 - 565
494 - 530 - 547 - 565
494 - 530 - 565 - 636
m3 / min
14.0 - 15.0 - 15.5 - 16.0 14.0 - 15.0 - 15.5 - 16.0 14.0 - 15.0 - 15.5 - 16.0 14.0 - 15.0 - 16.0 - 18.0
L / s
233 - 250 - 259 - 267
233 - 250 - 259 - 267
233 - 250 - 259 - 267
233 - 250 - 267 - 300
Sound pressure level (Low-Mid2-Mid1-High)
(measured in anechoic room)
dB <A>
27 - 29 - 30 - 31(208-
230V)
27 - 29 - 30 - 31(208-
230V)
28 - 29 - 30 - 31(208-
230V)
28 - 29 - 30- 32(208-
230V)
Insulation material
PS
Air filter
PP honeycomb (long life filter, anti-bacterial type)
Protection device
Fuse
Refrigerant control device
LEV
Connectable outdoor unit
R410A CITY MULTI
Diameter of
refrigerant pipe
(O.D.)
Liquid (R410A)
in. (mm)
1/4 (6.35) Flare
Gas (R410A)
in. (mm)
1/2 (12.7) Flare
Field drain pipe size
in. (mm)
O.D. 1-1/4(32)
Drain lift mechanism
in. (mm)
33-7/16 (850)
Standard
attachment
Document
Accessory
Installation Manual, Instruction Book
Optional parts
External heater adapter
CN24RELAY-KIT-CM3
Air outlet shutter plate
PAC-SH51SP-E
High efficiency filter element
(MERV 10)
PAC-SH59KF-E
Multi-function casement
PAC-SH53TM-E
i-see sensor corner panel
PAC-SA1ME-E
Flange for fresh air intake
PAC-SH65OF-E
Wireless signal receiver
PAR-SA9FA-E
Remark
Installation
Details on foundation work, duct work, insulation work, electrical wiring,
power source switch, and other items shall be referred to the Installation
Manual.
Ventilation Air: Providing sufficient ventilation air is an important part of every building design.
ASHRAE standard 62 provides the minimum ventilation air requirements. Also check local
codes.
1. SPECIFICATIONS
Note:
*1 Nominal cooling conditions
*2 Nominal heating conditions
Unit converter
Indoor:
80degF D.B. / 67degF W.B.
(26.7degC D.B. / 19.4degC W.B.)
70degF D.B. (21.1degC D.B.)
kcal/h = kW x 860
BTU/h = kW x 3,412
Outdoor:
95degF D.B. (35degC D.B.)
47degF D.B. / 43degF W.B.
(8.3degC D.B. / 6.1degC W.B.)
cfm = m3/min x 35.31
lbs = kg / 0.4536
Pipe length:
25 ft. (7.6 m)
25 ft. (7.6 m)
*Above specification data is subject to
rounding variation.
Level difference:
0 ft. (0 m)
0 ft. (0 m)
*Due to continuing improvement, above specification may be subject to change without notice.
*3 PLFY-P08NBMU-E2 is not compatible with PUMY-P**NHMU/NKMU outdoor units.
PLFY-P08NBMU-E2, PLFY-P12NBMU-E2, PLFY-P15NBMU-E2, PLFY-P18NBMU-E2