4

3.  Installing the indoor unit

„

 PKFY-P·NHMU-E2

Fig. 3-6

B

A

C

E

D

3.2.3.  Installing the wall mounting fixture

X

 Since the indoor unit weighs near 13 kg, 29lbs, selection of the mounting 

location requires thorough consideration. If the wall does not seem to be 
strong enough, reinforce it with boards or beams before installation.

X

 The mounting fixture must be secured at both ends and at the centre, if 

possible. Never fix it at a single spot or in any nonsymetrical way.

  (If possible, secure the fixture at all the positions marked with a bold 

arrow.)

 Warning:

If possible, secure the fixture at all positions indicated with a bold arrow.

 Caution:

•  The unit body must be mounted horizontally.
•  Fasten at the holes marked with 

S

 as shown by the arrows.

„

 PKFY-P·NHMU-E2 (Fig. 3-4)

Min. 90 mm, 3-35/64 inch (617.6 mm, 24-5/16 inch or greater with optional drain pump 
installation)

Min. 200 mm, 7-7/8 inch

Min. 72 mm, 2-53/64 inch (142.5 mm, 5-39/64 inch or greater with left, rear left, or lower 
left piping, and optional drain pump installation)

Fixing screws (4 × 35 mm, 1-3/8 inch) 

2

Level

Fasten a thread to the hole.

Place the level against the horizontal reference line of the mount board and mount so that it is 
level. Hang a weight from the thread and align with 

V

 EPK of the mount board to permit leveling.

Weight

Mount board 

1

3.3.  When embedding pipes into the wall (Fig. 3-5)

•  The pipes are on the bottom left.
•  When the cooling pipe, drain pipes internal/external connection lines etc are to 

be embedded into the wall in advance, the extruding pipes etc, may have to be 
bent and have their length modified to suit the unit.

•  Use marking on the mount board as a reference when adjusting the length of the 

embedded cooling pipe.

•  During construction, give the length of the extruding pipes etc some leeway.

Mount board 

1

Reference marking for flare connection

Through hole

On-site piping

3.4.  Preparing the indoor unit

*  Check beforehand because the preparatory work will differ depending on the 

exiting direction of the piping.

*  When bending the piping, bend gradually while maintaining the base of the 

piping exiting portion. (Abrupt bending will cause misshaping of the piping.)

Extraction and processing of the piping and wiring (Fig. 3-6)

1. Connection of indoor/outdoor wiring 

”

 See page. 8.

2. Wrap the felt tape 

3

 in the range of the refrigerant piping and drain hose which 

will be housed within the piping space of the indoor unit. 
•  Wrap the felt tape 

3

 securely from the base for each of the refrigerant piping 

and the drain hose. 

•  Overlap the felt tape 

3

 at one-half of the tape width. 

•  Fasten the end portion of the wrapping with vinyl tape.

Liquid pipe

Gas pipe

Indoor/outdoor connection cable

Drain hose

Felt tape 

3

3. Be careful that the drain hose is not raised, and that contact is not made with the 

indoor unit box body. 
Do not pull the drain hose forcefully because it might come out. 

Rear, right and lower piping (Fig. 3-7)

1) Be careful that the drain hose is not raised, and that contact is not made with 

the indoor unit box body. 
Arrange the drain hose at the underside of the piping and wrap it with felt 
tape 

3

2) Securely wrap the felt tape 

3

 starting from the base. (Overlap the felt tape at 

one-half of the tape width.) 

Cut off for right piping. 

Cut off for lower piping. 

Fig. 3-4

A

B

C

D

I

G

F

H

E

Fig. 3-5

B

A

C

D

Fig. 3-7

B

A

1)

2)

Содержание PKFY-P-NHMU-E2

Страница 1: ...efore installing the air conditioner unit FOR INSTALLER English MANUEL D INSTALLATION Avant d installer le climatiseur lire attentivement ce manuel ainsi que le manuel d installation de l appareil ext...

Страница 2: ...sure in the refrigerant line and may result in an explosion and other hazards The use of any refrigerant other than that specified for the system will cause mechanical failure or system malfunction or...

Страница 3: ...purchased locally through the hole A Sleeve B Hole C Indoors D Wall E Outdoors Note The purpose of the hole s inclination is to promote drain flow Fig 2 1 2 1 Outline dimensions Indoor unit Fig 2 1 Se...

Страница 4: ...have their length modified to suit the unit Use marking on the mount board as a reference when adjusting the length of the embedded cooling pipe During construction give the length of the extruding pi...

Страница 5: ...hung securely 5 Fasten by pushing the bottom part of the indoor unit onto the mount board 1 Fig 3 10 Check that the knobs on the bottom of the indoor unit are securely hooked into the mount board 1 6...

Страница 6: ...he flare nut and cap of the indoor unit 2 Make a flare for the liquid pipe and gas pipe and apply refrigerating machine oil available from your local supplier to the flare sheet surface 3 Quickly conn...

Страница 7: ...rain hose by holding on to the base of the hose a shown by arrow and pulling towards yourself b 3 Insert the drain cap Insert a screwdriver etc into the hole at the end of the pipe and be sure to push...

Страница 8: ...Power supply codes of appliance shall not be lighter than design 245IEC57 or 227IEC57 245 IEC 53 or 227 IEC 53 A switch with at least 3 mm 1 8 inch contact separation in each pole shall be provided by...

Страница 9: ...emote controller indoor and outdoor transmission cables Fig 6 3 Connect indoor unit TB5 and outdoor unit TB3 Non polarized 2 wire The S on indoor unit TB5 is a shielding wire connection For specificat...

Страница 10: ...g 7 1 1 Turn on the power at least 12 hours before the test run 2 Press the TEST button twice TEST RUN liquid crystal display 3 Press the Mode selection button Make sure that wind is blown out 4 Press...

Страница 11: ...frig rant diff rent de celui sp cifi pour le climatiseur peut entra ner des d faillances m caniques des dysfonctionnements du syst me ou une panne de l appareil Dans le pire des cas cela peut entra ne...

Страница 12: ...sorte que l ouverture ext rieure soit plus basse que l ouverture int rieure X Ins rer un manchon de 65 80 mm 2 9 16 3 5 32 inch de diam tre non fourni dans l orifice A Manchon B Orifice C C t int rieu...

Страница 13: ...dapt e l appareil Marquer la planche d installation pour r f rence lors de l ajustement de la longueur du tuyau de refroidissement encastr Pendant la construction donner du jeu la longueur des tuyaux...

Страница 14: ...fier que l appareil est correctement accroch 5 Fixer en poussant la partie inf rieure de l appareil int rieur sur la planche d installation 1 Fig 3 10 V rifier que les boutons en bas de l appareil int...

Страница 15: ...pour l installation des tuyaux de r frig rant Fig 4 3 Appareil int rieur 1 Retirer l crou vas et le couvercle de l appareil int rieur 2 Cr er un vasement pour le tuyau de liquide et pour le tuyau de g...

Страница 16: ...A Inclinaison vers le bas B Doit tre plus bas que le point de sortie C Fuite d eau D coulement pi g E Air F Ondul G Extr mit du tuyau d coulement sous l eau H Rigole d coulement I 5 cm 1 31 32 inch ma...

Страница 17: ...e plus long que les autres c bles Les cordons d alimentation des appareils lectriques ne doivent pas tre plus l gers que les dessins 245 IEC 57 ou 227 IEC 57 245 IEC 53 ou 227 IEC 53 Un commutateur av...

Страница 18: ...xt rieurs Fig 6 3 Raccorder l unit int rieure TB5 et l unit int rieure TB3 2 fils non polaris s Le S sur l unit int rieure TB5 est une connexion pour c bles blind Pour les sp cifications techniques de...

Страница 19: ...ppuyer deux fois sur la touche TEST ESSAI Affichage cristaux liquides TEST RUN ESSAI DE FONCTIONNEMENT 3 Appuyer sur la touche Mode selection S lection Mode V rifier si la soufflerie fonctionne 4 Appu...

Страница 20: ......

Страница 21: ...u otros peligros Usar un refrigerante distinto al indicado para el sistema provocar un fallo mec nico un funcionamiento defectuoso del sistema o la aver a de la unidad En el peor de los casos podr a...

Страница 22: ...el orificio interior X Introduzca un manguito por el agujero de 65 80 mm 2 9 16 3 5 32 inch de di metro y comprado en su localidad A Manguito B Agujero C lado interior D Pared E lado exterior Nota El...

Страница 23: ...laca de montaje como referencia cuando vaya a ajustar la longitud del tubo de refrigerante empotrado Durante la construcci n deje un margen en la longitud de los tubos troquelados etc A Placa de monta...

Страница 24: ...da y derecha y aseg rese de que est colgada firmemente 5 Fije la unidad en la placa de montaje 1 empujando la parte inferior de la unidad Fig 3 10 Aseg rese de que los tiradores de la parte inferior d...

Страница 25: ...ar la tuerca de abocardado Utilice dos llaves de apriete para apretar las conexiones de los tubos Utilice el aislante de tuber a de refrigerante suministrado para aislar las conexiones de la unidad in...

Страница 26: ...agua H Canaleta de drenaje I 5 cm 1 31 32 inch o menos entre el extremo del tubo de drenaje y el suelo J Manguera de drenaje K Manguera blanda de PVC di metro interior 15 mm 19 32 inch o tubo r gido...

Страница 27: ...ables de la fuente de alimentaci n del aparato el ctrico no deben ser m s ligeros que el dise o 245 IEC 57 227 IEC 57 245 IEC 53 o el 227 IEC 53 La instalaci n del aire acondicionado debe proporcionar...

Страница 28: ...5 de la unidad interior indica una conexi n de cable blindado Consulte en el manual de instalaci n de la unidad exterior las especificaciones sobre los cables de conexi n Instale el mando a distancia...

Страница 29: ...ST PRUEBA dos veces Indicador del cristal l quido de prueba en funcionamiento TEST RUN EJECUCI N DE PRUEBA 3 Pulse el bot n de selecci n de modo Mode selection Modo Compruebe que sale aire 4 Pulse el...

Страница 30: ......

Страница 31: ......

Страница 32: ...on this manual before handing it to the customer This product is designed and intended for use in the residential commercial and light industrial environment Printed in Japan RG79D482H03 HEAD OFFICE T...

Отзывы: