- 69 -
<Abnormality detected during unit operation: Indoor unit>
Abnormal-
ity display
P1
P2
Meaning of abnormality display and
abnormality troubleshooting
Intake sensor abnormal
1) If thermistor open or short is de-
tected and the compressor enters
the 3 minutes restart prevention
mode and does not return to nor-
mal after 3 minutes, an abnormal-
ity is recognized.
(If returned, returns to normal op-
eration.)
2) Always detected during cool, dry,
and heat operations.
Short: 90
°
C or higher
Open: –40
°
C or lower
Piping sensor abnormal
1) If thermistor short or open is de-
tected and the compressor enters
the 3 minutes restart prevention
mode and does not return to nor-
mal after 3 minutes, an abnormal-
ity is recognized.
(If returned, returns to normal op-
eration.)
2) Always detected during cool, dry,
and heat (except during defrost-
ing) operation.
Short: 90
°
C or higher
Open: –40
°
C or lower
Cause
1
Thermistor characteristics faulty.
2
Connector contact faulty.
(Insertion faulty)
3
Thermistor wiring open or contact
faulty.
4
Indoor controller board faulty.
1
Thermistor characteristics faulty.
2
Connector contact faulty.
(Insertion faulty)
3
Thermistor wiring open or contact
faulty.
4
Faulty refrigerant circuit, etc. has
caused thermistor temperature to rise
to 90
°
C or higher or drop to –40
°
C
or lower.
5
Indoor controller board faulty.
Judgment method and remedy
1
-
3
Check thermistor resistance value
0
°
C ...... 15.0 k
Ω
10
°
C ........ 9.7 k
Ω
20
°
C ........ 6.4 k
Ω
30
°
C ........ 5.3 k
Ω
40
°
C ........ 3.1 k
Ω
Open or faulty contact can be detected
by applying force (pulling, bending) to
lead wire while measuring thermistor re-
sistance.
2
Check for connector faulty contact.
After reinserting connector, turn on
power and recheck operation.
4
Check remote controller room tempera-
ture display.
If there is a difference between actual
room temperature and displayed room
temperature after checking that there
are no problems at
1
-
3
, replace indoor
controller board.
If there are no problems above, there
are no abnormalities.
Turn power off and on and operate.
1
-
3
Check thermistor resistance value.
For characteristic, see above (P1).
2
Check for connector faulty contact.
After reinserting connector, turn on
power and recheck operation.
4
Operate in trail run mode and check pip-
ing temperature with remote controller.
When piping temperature is abnormally
low (cooling) or high (heating), refriger-
ant circuit is probably faulty.
5
Check test run mode piping tempera-
ture with remote controller.
If there is a difference between actual
piping temperature and displayed pip-
ing temperature when there are no ab-
normalities at
1
-
4
, replace indoor con-
troller board. If there is no problem
above, there are no abnormalities.
Turn on power and operate.