background image

En-5

4-1. PURGING PROCEDURES AND LEAK TEST

Fig.

 

Fig.

 

2

Fig.

 

3

Fig.

 

4

Fig.

 

5

Fig.

 

6

3.  FLARING WORK AND PIPE CONNECTION

3-1. FLARING WORK

Pipe

 

diameter

 

(mm)

Nut

 

(mm)

A

 

(mm)

Tightening

 

torque

Clutch

 

type

 

tool

  

for

 

R4

0A

Clutch

 

type

 

tool

  

for

 

R22

Wing

 

nut

 

type

 

tool

  

for

 

R22

N•m

kgf•cm

ø6.35

 

(

/4”)

7

0

 

to

 

0.5

.0

 

to

 

.5

.5

 

to

 

2.0

3.7

 

to

 

7.7

40

 

to

 

80

ø9.52

 

(3/8”)

22

34.3

 

to

 

4

.2 350

 

to

 

420

ø

2.7

 

(

/2”)

26

2.0

 

to

 

2.5

49.0

 

to

 

56.4 500

 

to

 

575

ø

5.88

 

(5/8”)

29

73.5

 

to

 

78.4 750

 

to

 

800

Tilted

 

Uneven

 

Burred

Good

No

 

good

Burr Copper

 

pipe

Spare

 

reamer

Pipe

 

cutter

Smooth

 

all

 

around

Even

 

length

 

all

 

around

Inside

 

is

 

shin-

ing

 

without

 

any

 

scratches.

Flare

 

nut

Die

Copper

 

pipe

Clutch

 

type

Flaring

 

tool

Wing

 

nut

 

type

3-2. PIPE CONNECTION

1) Apply a thin coat of refrigeration oil (G) to the flared ends of the pipes 

and

 

the

 

pipe

 

connections

 

of

 

the

 

outdoor

 

unit.

 

Do

 

not

 

apply

 

refrigeration

 

oil

 

on

 

screw

 

threads.

 

Excessive

 

tightening

 

torque

 

will

 

result

 

in

 

damage

 

on

 

the

 

screw.

2) 

Align

 

the

 

center

 

of

 

the

 

pipe

 

with

 

that

 

of

 

the

 

pipe

 

connections

 

of

 

the

 

out-

door unit, then hand tighten the flare nut 3 to 4 turns

3) Tighten the flare nut with a torque wrench as specified in the tabl

• Over-tightening may cause damage to the flare nut, resulting in refrig-

erant

 

leakage.

 

Be

 

sure

 

to

 

wrap

 

insulation

 

around

 

the

 

piping.

 

Direct

 

contact

 

with

 

the

 

bare

 

piping

 

may

 

result

 

in

 

burns

 

or

 

frostbite.

3-3. INSULATION AND TAPING

Cover

 

piping

 

joints

 

with

 

pipe

 

cover.

2) 

For

 

outdoor

 

unit

 

side,

 

surely

 

insulate

 

every

 

piping

 

including

 

valves.

3) 

Using

 

piping

 

tape

 

(E),

 

apply

 

taping

 

starting

 

from

 

the

 

entry

 

of

 

outdoor

 

unit.

• 

Stop

 

the

 

end

 

of

 

piping

 

tape

 

(E)

 

with

 

tape

 

(with

 

adhesive

 

agent

 

at-

tached).

• 

When

 

piping

 

have

 

to

 

be

 

arranged

 

through

 

above

 

ceiling,

 

closet

 

or

 

where

 

the

 

temperature

 

and

 

humidity

 

are

 

high,

 

wind

 

additional

 

commer-

cially

 

sold

 

insulation

 

to

 

prevent

 

condensation.

4.  PURGING PROCEDURES, LEAK TEST, AND TEST RUN

Copper

 

pipe

Cut

 

the

 

copper

 

pipe

 

correctly

 

with

 

pipe

 

cutter.

 

(Fig.

 

,

 

2)

2) 

Completely

 

remove

 

all

 

burrs

 

from

 

the

 

cut

 

cross

 

section

 

of

 

pipe.

 

(Fig.

 

3)

• 

Aim

 

the

 

copper

 

pipe

 

downward

 

while

 

removing

 

burrs

 

to

 

prevent

 

burrs

 

from

 

dropping

 

in

 

the

 

pipe.

3) Remove flare nuts attached to indoor and outdoor units, then put them 

on

 

pipe

 

having

 

completed

 

burr

 

removal.

 

(Not

 

possible

 

to

 

put

 

them

 

on

 

after flaring work.)

4) 

Flaring

 

work

 

(Fig.

 

4,

 

5).

 

Firmly

 

hold

 

copper

 

pipe

 

in

 

the

 

dimension

 

shown

 

in

 

the

 

table.

 

Select

 

A

 

mm

 

from

 

the

 

table

 

according

 

to

 

the

 

tool

 

selected.

5) 

Check

 

•  Compare the flared work with Fig. 6

•  If flare is noted to be defective, cut off the flared section and do fla -

ing

 

work

 

again.

Remove

 

service

 

port

 

cap

 

of

 

stop

 

valve

 

on

 

the

 

side

 

of

 

the

 

outdoor

 

unit

 

gas

 

pipe.

 

(The

 

stop

 

valves

 

are

 

fully

 

closed

 

and

 

covered

 

in

 

caps

 

in

 

their

 

initial

 

state.)

2) 

Connect

 

gauge

 

manifold

 

valve

 

and

 

vacuum

 

pump

 

to

 

service

 

port

 

of

 

stop

 

valve

 

on

 

the

 

gas

 

pipe

 

side

 

of

 

the

 

outdoor

 

unit.

3) 

Run

 

the

 

vacuum

 

pump.

 

(Vacuumize

 

for

 

more

 

than

 

5

 

minutes.)

4) 

Check

 

the

 

vacuum

 

with

 

gauge

 

manifold

 

valve,

 

then

 

close

 

gauge

 

mani-

fold

 

valve,

 

and

 

stop

 

the

 

vacuum

 

pump.

5) 

Leave

 

as

 

it

 

is

 

for

 

one

 

or

 

two

 

minutes.

 

Make

 

sure

 

the

 

pointer

 

of

 

gauge

 

manifold  valve  remains  in  the  same  position.  Con

fi

rm  that  pressure 

gauge

 

shows

 

-0.

0

 

MPa

 

[Gauge]

 

(-760

 

mmHg).

6) 

Remove

 

gauge

 

manifold

 

valve

 

quickly

 

from

 

service

 

port

 

of

 

stop

 

valve.

7) 

Fully

 

open

 

all

 

stop

 

valves

 

on

 

the

 

gas

 

pipe

 

and

 

the

 

liquid

 

pipe.

 

Operat-

ing

 

without

 

fully

 

opening

 

lowers

 

the

 

performance

 

and

 

this

 

causes

 

trou-

ble.

8) 

Refer

 

to

  

-2.,

 

and

 

charge

 

the

 

prescribed

 

amount

 

of

 

refrigerant

 

if

 

needed.

 

Be

 

sure

 

to

 

charge

 

slowly

 

with

 

liquid

 

refrigerant.

 

Otherwise,

 

composition

 

of

 

the

 

refrigerant

 

in

 

the

 

system

 

may

 

be

 

changed

 

and

 

af-

fect

 

performance

 

of

 

the

 

air

 

conditioner.

9) 

Tighten

 

cap

 

of

 

service

 

port

 

to

 

obtain

 

the

 

initial

 

status.

0

Leak

 

test

 

WARNING

When installing the unit, securely 

connect the refrigerant pipes before 

starting the compressor.

 

CAUTION

When there are the ports which are 

not used, make sure their nuts are 

tightened securely.

Service

 

port

 

cap

(Torque

 

3.7

 

to

 

7.7

 

N•m,

 

40

 

to

 

80

 

kgf•cm)

Stop

 

valve

 

for

 

GAS

Stop

 

valve

 

cap

(Torque

 

9.6

 

to

 

29.4

 

N•m,

 

200

 

to

 

300

 

kgf•cm)

Gauge

 

manifold

 

valve

 

(for

 

R4

0A)

Compound

 

pressure

 

gauge

 

(for

 

R4

0A)

–0.

0

MPa

  

(–760

 

mmHg)

Handle

 

Low

Handle

 

High

Vacuum

 

pump

(for

 

R4

0A)

Charge

 

hose

 

(for

 

R4

0A)

*Close

*Open

Hexagonal

 

wrench

*4

 

to

 

5

 

turns

Stop

 

valve

 

for

 

LIQUID

Pressure

 

gauge

(for

 

R4

0A)

Precautions

 

when

 

using

 

the

 

control

 

valve

When

 

attaching

 

the

 

control

 

valve

 

to

 

the

 

service

 

port,

 

valve

 

core

 

may

 

de-

form

 

or

 

loosen

 

if

 

excess

 

pressure

 

is

 

applied.

 

This

 

may

 

cause

 

gas

 

leak.

Service

 

port

Charge

 

hose

 

(for

 

R4

0A)

Body

Close

Open

Control

 

valve

A

When

 

attaching

 

the

 

control

 

valve

 

to

 

the

 

service

 

port,

 

make

 

sure

 

that

 

the

 

valve

 

core

 

is

 

in

 

closed

 

position,

 

and

 

then

 

tighten

 

part

 

A.

 

Do

 

not

 

tighten

 

part

 

A

 

or

 

turn

 

the

 

body

 

when

 

valve

 

core

 

is

 

in

 

open

 

position.

JG79A662H01_en.indd   5

2012/09/24 (月)   午後 7:00:11

Содержание MXZ-4D83VA

Страница 1: ...e dell unit esterna Per l installazione dell unit interna fare riferimento al relativo manuale di instal lazione Manual de Instala o Para o INSTALADOR Este manual descreve apenas a instala o da unidad...

Страница 2: ...e ventilation in accord ance with EN378 1 n Check that the refrigerant gas does not leak after installation has been completed If refrigerant gas leaks indoors and comes into contact with the flame of...

Страница 3: ...ibility of becoming short cycle install an outlet guide and make sure there is enough space behind of the unit When installing two or more units do not install the units in front or behind each other...

Страница 4: ...200 mm 2 U shape notched holes Base bolt M10 320 mm 2 12 mm 36 mm oval holes Base bolt M10 355 mm 387 mm After the leak test apply insulat ing material tightly so that there is no gap When the piping...

Страница 5: ...necting section of the terminal block 3 Firmly tighten the terminal screws to prevent them from loosening Af ter tightening pull the wires lightly to confirm that they do not move 4 Perform 2 and 3 fo...

Страница 6: ...y hold copper pipe in the dimension shown in the table Select A mm from the table according to the tool selected 5 Check Compare the flared work with Fig 6 If flare is noted to be defective cut off th...

Страница 7: ...ller board to OFF To lock the operation in HEAT mode set the same switch to ON 4 Turn on the main power for the air conditioner Description of the function With this function the operating noise of th...

Страница 8: ...board damage To prevent electronic control P C board damage make sure to perform static elimi nation before operating this function This function does not operate when the outside temperature is 0 C...

Страница 9: ...a plaque du produit Opmerking het serienummer staat op het naamplaatje van het product Nota El n mero de serie se encuentra en la placa que contiene el nombre del producto Nota il numero di serie si t...

Отзывы: