26
9-4. FIXING HORIZONTAL VANE
Horizontal vane of each air outlet can be fixed according to the environment where it is installed.
Setting procedure
1) Turn off a main power supply (Turn off a breaker).
2) Remove the vane motor connector in the direction of the arrow shown below with pressing the unlocking button as in the
figure below.
Insulate the disconnected connector with the plastic tape.
Vane motor
Horizontal vane
Connector
Unlocking button
Vane motor
3) Set the vertical vane of the air outlet by hand slowly within the range in the table below.
Measured standard
position of the grille
Horizontal vane
< Specified range >
Up/down airflow
direction
Horizontal 30°
Downward 45°
Downward 55°
Downward 70°
A
21 mm
25 mm
28 mm
30 mm
The vanes can be set between 21mm and 30 mm.
Caution:
Do not set the up/down vanes passed the specified range. Condensation could form and drop from the ceiling,
or the unit could malfunction.
OCH493D