background image

12

[Drainage by gravity]

1. Insert the drain hose (accessory) into the drain port.

(The drain hose must not be bent more than 45° to prevent the hose from breaking
or clogging.)
The connecting part between the indoor unit and the drain hose may be discon-
nected at the maintenance. Fix the part with the accessory band, not be adhered.

2. Attach the drain pipe (O.D. ø32 PVC TUBE, field supplied).

(Attach the pipe with glue for the hard vinyl chloride pipe, and fix it with the band
(accessory).)

3. Perform insulation work on the drain pipe (O.D. ø32 PVC TUBE) and on the socket

(including elbow).

[Fig. 6-12] (P.4)

 * Drainage by gravity

A

Indoor unit

B

Pipe cover (30 mm [3/16 in]) (accessory)

C

Tie band (accessory)

D

Band fixing part

E

Insertion margin

F

Drain hose (accessory)

G

Drain pipe (O.D. ø32 PVC TUBE, field supplied)

H

Insulating material (field supplied)

I

Max. 145 ± 5 mm

8. Electrical work

8.1. Power supply

Electrical specification

Input capacity Main Switch/Fuse (A)

Power supply

PEA-A12AA4

PEA-A18AA4

(1 phase ~/N, 208/230V, 60Hz

10

20

 Warning:

• The compressor will not operate unless the power supply phase connection

is correct.

• Grounding protection with a no-fuse breaker (earth leakage breaker [ELB]) is

usually installed for 

D

D

D

D

D

.

• The connection wiring between the outdoor and indoor units can be extended

up to a maximum of 50 m [164 ft], and the total extension including the crosso-
ver wiring between rooms is a maximum of 80 m [262 ft].

A switch with at least 3 mm [1/8 in] contact separation in each pole shall be
provided by the air conditioner installation.
* Label each breaker according to purpose (heater, unit etc.).

[Fig. 8-1] (P.5)

A

Indoor unit

B

Outdoor unit

C

Wired remote controller

D

Main switch/fuse

E

Grounding

F

Indoor controller board

G

Radio frequency interface for RF thermostat

8.2. Indoor wire connection

Work procedure
1.Remove 2 screws to detach the electric component cover.
2.Route each cable through the wiring intake into the electric component box. (Pro-

cure power cable and in-out connecting cable locally and use wired remote control
cable supplied with the unit.)

3.Securely connect the power cable and the in-out connecting cable and the wired

remote control cable to the terminal blocks.

4.For radio frequency interface

Connect the electric wires securely to the CN105 (RED) of indoor controller board.
Connect the electric wires securely to the corresponding terminals.

5.Secure the cables with clamps inside the electric component box.
6.Attach the electric component cover as it was.
• Fix power supply cable and indoor/outdoor cable to control box by using buffer

bushing for tensile force. (PG connection or the like.)

 Warning:

• Attach the electrical part cover securely. If it is attached incorrectly, it could

result in a fire, electric shock due to dust, water, etc.

• Use the specified indoor/outdoor unit connecting wire to connect the indoor

and outdoor units and fix the wire to the terminal block securely so that no
stress is applied to the connecting section of the terminal block.  Incomplete
connection or fixing of the wire could result in a fire.

[Fig. 8-2-1] (P.5)

A

Screw holding cover (2pcs)

B

Cover

[Fig. 8-2-2] (P.5)

A

Terminal block box

B

Knockout hole

C

Remove

• When connecting ducts, insert a canvas duct between the main body and the duct.
• Use non-combustible duct components.

 Caution:

The noise from the intake will increase dramatically if intake 

A

A

A

A

A

  is fitted

directly beneath the main body. Intake 

A

A

A

A

A

 should therefore be installed as

far away from the main body as possible.
Particular care is required when using it with bottom inlet specifications.

Install sufficient thermal insulation to prevent condensation forming on
outlet duct flanges and outlet ducts.

To connect the air conditioner main body and the duct for potential equali-
zation.

Keep the distance between the inlet grille and the fan over 850 mm [33-15/
32 in].
If it is less than 850 mm [33-15/32 in], install a safety guard not to touch the
fan.

[Fig. 7-1] (P.5)

A

Air inlet

B

Air outlet

C

Access door

D

Ceiling surface

E

Canvas duct

F

Air filter

G

Inlet grille

7. Duct work

6.6. Confirming drain discharge

s

s

s

s

s

Make sure that the drain-up mechanism operates normally for discharge
and that there is no water leakage from the connections.

• Be sure to confirm the above in a period of heating operation.
• Be sure to confirm the above before ceiling work is done in the case of a new

construction.

1.Remove the water supply port cover on the same side as the indoor unit piping.
2.Fill water into the feed water pump using a feed water tank. In filling, be sure to put

the end of the pump or tank in a drain pan. (If the insertion is incomplete, water may
flow over the machine.)

3.Perform the test run in cooling mode, or turn on the switch SWE on the controller

circuit board. (The drain pump and the fan are forced to operate without any remote
controller operation.) Make sure using a transparent hose that drain is discharged.

4.After confirmation, cancel the test run mode, and turn off the main power.

 

When the

switch SWE has been turned on, turn it off, and attach the water supply port cover
into its original position.

[Fig. 6-13] (P.4)

A

Insert pump's end 2 to 4 cm [13/16 to 1-19/32 in].

B

Remove the water supply port.

C

About 2000 cc

D

Water

E

Filling port

F

Screw

[Fig. 6-14] (P.4)

<Indoor board>

SWE

SWE

ON

OFF

ON

OFF

SWE

SWE

ON

OFF

ON

OFF

6. Refrigerant piping work

10_KB79U390H01_en.p65

10.9.16, 17:48

12

Содержание Mr. Slim PEA-A12AA4

Страница 1: ...nstallation manual thoroughly before installing the air conditioner unit FOR INSTALLER English Français MANUEL D INSTALLATION Veuillez lire le manuel d installation en entier avant d installer ce climatiseur pour éviter tout accident et vous assurer d une utilisation correcte POUR L INSTALLATEUR ...

Страница 2: ...A 50 150 1 31 32 5 29 32 450 17 23 32 450 17 23 32 49 1 15 16 625 24 5 8 777 30 19 32 20 13 16 23 29 32 C B A D B E 200 7 7 8 1 2 90 3 9 16 57 2 1 4 Y X L W A Z Unit mm in Unit mm in Model PEA A12AA4 PEA A18AA4 A 900 35 7 16 1100 43 5 16 B 952 37 1 2 1152 45 3 8 C 998 39 5 16 1198 47 3 16 D 860 33 7 8 1060 41 3 4 E 1000 39 3 8 1200 47 1 4 3 3 Fig 3 2 PUY A NHA 1 PUZ A NHA 100 3 15 16 200 7 7 8 350...

Страница 3: ...ermal insulation field supply I Pull J Flare nut A B C D F G E M L E F L AG H H K L J I J O O N N 20 20 20 20 13 16 13 16 13 16 13 16 Fig 6 3 Fig 6 6 Fig 6 4 Fig 6 5 a Flare nut b Copper tube a Burr b Copper tube pipe c Spare reamer d Pipe cutter Fig 6 7 Fig 6 8 a Flaring tool b Die c Copper tube d Flare nut e Yoke a Smooth all around b Inside is shining without any scratches c Even length all aro...

Страница 4: ...t 1 5 2 m 5 to 7 ft G F F F B C D E E H G K J F I A 25 1 25 1 35 1 13 32 A Indoor unit B Pipe cover 60 mm 3 8 in accessory C Tie band accessory D Visible part E Insertion margin F Drain hose accessory G Drain pipe O D ø32 mm 1 1 4 in PVC TUBE field supplied H Insulating material field supplied I Tie band accessory J Max 180 5 mm 7 3 32 7 32 in K To be gap free The joint section of the insulation m...

Страница 5: ... connecting cable F Washer accessory G Tensile force H Use ordinary bushing I Wired remote controller cable or wiring for radio interface A Terminal block for indoor outdoor unit connecting B Terminal block for wired remote controller C Indoor outdoor unit connecting cable D Wired remote controller cable E Indoor controller board F CN105 RED 5P G Wiring for radio interface Fig 8 2 3 Fig 8 2 4 A Te...

Страница 6: ...r terminal block 1 Indoor outdoor unit connecting cable 3 core 1 5 mm2 AWG 16 or more in con formity with Design 245 IEC 57 2 Indoor terminal block 3 Outdoor terminal block A Indoor terminal block 4 Always install an earth wire 1 core 1 5 mm2 AWG 16 longer than other cables 5 Wired remote controller cable Wire No size mm2 Cable 2C 0 3 This wire accessory of remote controller wire length 10m 32 ft ...

Страница 7: ...pe D Gas pipe E Stop valve F Outdoor unit G Refrigerant gas cylinder operating valve H Refrigerant gas cylinder for R410A with siphon I Refrigerant liquid J Electronic scale for refrigerant charging K Charge hose for R410A L Gauge manifold valve for R410A M Service port 11 1 ...

Страница 8: ...te elec trical work it could result in a fire or an electric shock Attach the electrical part cover to the indoor unit and the service panel to the outdoor unit securely If the electrical part cover in the indoor unit and or the service panel in the outdoor unit are not attached securely it could result in a fire or an electric shock due to dust water etc Be sure to use the part provided or specif...

Страница 9: ...s run for long hours when the air above the ceiling is at high temperature high humidity due point above 79 F 26 C due condensation may be produced in the indoor unit When operating the units in this condition add insulation material 10 20 mm 13 32 to 13 16 in to the entire surface of the indoor unit to avoid due condensation 3 1 Install the indoor unit on a ceiling strong enough to sustain its we...

Страница 10: ...laring work Fig 6 6 P 3 a Flaring tool b Die c Copper tube d Flare nut e Yoke Carry out flaring work using flaring tool as shown below Dimension Pipe diameter A mm in mm in When the tool for R410A is used B mm in Clutch type 6 35 1 4 0 to 0 5 0 to 1 32 9 1 3 8 9 52 3 8 0 to 0 5 0 to 1 32 13 2 17 32 12 7 1 2 0 to 0 5 0 to 1 32 16 6 21 32 15 88 5 8 0 to 0 5 0 to 1 32 19 7 25 32 Firmly hold copper tu...

Страница 11: ...rgin 25 mm 1 in The drain hose must not be bent more than 45 to prevent the hose from breaking or clogging Attach the hose with glue for the hard vinyl chloride pipe and fix it with the band accessory 2 Attach the drain pipe O D ø32 mm 1 1 4 in PVC TUBE field supply Attach the pipe with glue for the hard vinyl chloride pipe and fix it with the band accessory 3 Perform insulation work on the drain ...

Страница 12: ...hing for tensile force PG connection or the like Warning Attach the electrical part cover securely If it is attached incorrectly it could result in a fire electric shock due to dust water etc Use the specified indoor outdoor unit connecting wire to connect the indoor and outdoor units and fix the wire to the terminal block securely so that no stress is applied to the connecting section of the term...

Страница 13: ...ltage used Fig 8 2 3 P 5 A Use conduit to keep the weight of the cable and external force from being applied to the power supply terminal connector B Indoor outdoor unit connecting cable C Conduit D Terminal block box E Knockout hole for indoor outdoor unit connecting cable F Washer accessory G Tensile force H Use ordinary bushing I Wired remote controller cable or wiring for radio interface Fig 8...

Страница 14: ...urning on the main power switch can result in severe damage to internal parts Keep the power switch turned on during the op erational season 9 2 Test run s Refer to the installation manual that comes with each remote controller for details Function table 1 Select unit number 00 Function table 2 Select unit numbers 01 to 04 or all units AL wired remote controller 07 wireless remote controller 1 Whe...

Страница 15: ...ed ON operation lamp does not light up Symptom After LED 1 2 are lighted LED 2 is turned off then only LED 1 is lighted Correct operation Only LED 1 is lighted LED 1 2 blink Only LED 1 is lighted LED 1 2 blinks twice LED 2 blinks once For about 2 minutes after power on operation of the remote controller is not possible due to system start up Correct operation Connector for the outdoor unit s prote...

Страница 16: ...splay Display OUTDOOR UNIT H EXC TEMP OUTDOOR UNIT OUTLET TEMP OUTDOOR UNIT OUTDOOR TEMP Heat exchanger temperature Comp discharge temperature Outdoor ambient temperature Display Outdoor unit information INDOOR UNIT INLET TEMP INDOOR UNIT H EXC TEMP INDOOR UNIT FILTER USE H Indoor room temperature Heat exchanger temperature Filter operation time Display Indoor unit information The filter operation...

Страница 17: ... assurer d utiliser la pièce fournie ou les pièces spécifiées pour l installation Toute pièce défectueuse utilisée pourrait être la cause d un incendie d un choc électrique de l appareil tombant de sa position etc ce qui résulterait en une blessure ou une fuite d eau Aérez le local en cas de fuite de liquide frigorigène en cours de fonctionne ment Tout contact du liquide frigorigène avec une flamm...

Страница 18: ...de l arrivée d air Le détecteur d incendie risque de se déclencher par erreur suite à l alimentation en air chaud pendant le fonctionnement du chauffage En cas de présence de produits chimiques sur les lieux d installation comme dans des usines chimiques ou des hôpitaux une étude approfondie s avère nécessaire avant de procéder à l installation de l appareil Certains produits chimiques peu vent en...

Страница 19: ...Enlever les bavures Fig 6 4 P 3 a Bavure b Tuyau tube en cuivre c Alésoir supplémentaire d Coupe tuyaux Enlever toutes les bavures du tube tuyau coupé Tenir le tuyau tube avec le bout orienté vers le bas pendant que vous enlevez les bavures pour éviter qu elles ne tombent à l intérieur du tuyau 6 2 3 Mettre l écrou en place Fig 6 5 P 3 a Ecrou évasé b Tube en cuivre Enlever les écrous évasés situé...

Страница 20: ...le haut 1 Retirer et jeter le bouchon de caoutchouc qui a été inséré à l extrémité de la tuyau terie de l appareil 2 Evaser l extrémité du tuyau de réfrigérant site 3 Retirer l isolation thermale située sur le tuyau de réfrigérant site et remettre l isola tion à sa position originale Précautions concernant le raccordement des tuyaux de réfrigérant s s s s s Toujours utiliser des soudures non oxyda...

Страница 21: ...ce H Matériel d isolation fourni sur place I 145 5 mm maxi 6 6 Confirmation des décharges d écoulement s s s s s Veiller à ce que le mécanisme de décharge d écoulement fonctionne nor malement et que les raccordements ne présentent aucune fuite Le point ci dessus doit être respecté en mode de chauffage Le point ci dessus doit être respecté avant de procéder aux travaux du plafond dans le cas d une ...

Страница 22: ...ur extérieur C Conduit D Bornier E Ouverture pour câble de connexion de l appareil intérieur extérieur F Rondelle accessoire G Force de tension H Utiliser une bague ordinaire I Câble de la télécommande filaire ou câblage pour l interface radio 8 Installations électriques Fig 8 2 4 P 5 A Bloc terminal pour la connexion de l appareil intérieur extérieur B Bornier de la télécommande filaire C Câble d...

Страница 23: ...d un appareil intérieur a été changée en sélectionnant un autre fonction après l installation toujours indiquer le contenu en saisissant un ou une autre marque dans la case à cocher appropriée des tableaux Mode Signe du filtre Pression statique extérieure Paramètre 100 Hr 2500 Hr Pas d indicateur de signe du filtre 15 Pa 0 06 in WG 35 Pa 0 14 in WG 50 Pa 0 20 in WG Identique au réglage du mode No ...

Страница 24: ...moins 12 heures avant de le faire fonction ner La mise en marche de l appareil immédiatement après sa mise sous tension pour rait provoquer de sérieux dégâts aux éléments internes Ne mettez pas l appareil hors tension pendant la saison de fonctionnement 9 2 Marche d essai s Pour en savoir plus consulter le manuel d installation fourni avec chaque télécommande Type de message A Erreurs détectées pa...

Страница 25: ...de ne peut pas être utilisée parce que le système est mis en route Fonctionnement correct Le connecteur du dispositif de protection de l appareil extérieur n est pas raccordé Câblage inversé ou avec phase ouverte du bornier d alimentation de l appareil extérieur L1 L2 L3 Câblage incorrect entre les appareils intérieur et extérieur polarité incorrecte de S1 S2 S3 Court circuit sur le câble de la té...

Страница 26: ...A 1 Appuyer sur la touche TEST pendant trois se condes pour activer le mode d entretien Affichage Affichage Affichage Affichage Affichage Affichage Affichage Affichage 2 Appuyer sur les touches TEMP de température 3 Sélectionner les données à afficher pour régler l adresse de réfrigérant Informations sur le compresseur Durée cumulative de fonctionnement Nombre ON OFF marche arrêt Courant de foncti...

Страница 27: ......

Страница 28: ...ne number on this manual before handing it to the customer This product is designed and intended for use in the residential commercial and light industrial environment HEAD OFFICE TOKYO BLDG 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN KB79U390H01 ...

Отзывы: