(6) I/O assignment
Set the mounting status of each module in the system.
Diagram 8.6 I/O assignment
Table8.6 I/O assignment list
Item
Parameter No.
Description
Setting range
Default value
Reference
I/O
assignment
Type
0400
H
Set the type of the mounted
module.
Empty/intelli.
No setting
Model
name
Set the model name of the
mounted module. (User memo.
Not used for the CPU module.)
16 characters
No setting
points
Set the number of points of each
slot.
0 points/16 points/32 points/
48 points/64 points/
128 points/256 points/
512 points/1024 points
No setting
Start XY
(Start I/O
No.)
Set the start I/O number of each
slot.
0
H
to 3F0
H
No setting
Standard
setting
Base
model
name
0401
H
Set the model name of the used
main base unit. (User memo. Not
used for the CPU module.)
16 characters
No setting
Power
model
name
Set the model name of the
power supply module mounted
on the main base unit. (User
memo. Not used for the CPU
module.)
16 characters
No setting
Extension
cable
Set the extension cable model
name. (User memo. Not used for
the CPU module.)
16 characters
No setting
Slots
Set the number of slots of the
main base unit.
4
No setting
Switch setting
0407
H
Unusable