Specifications
Item
Q64TCTT
Q64TCTTBW
Output signal
ON/OFF pulse
Rated load voltage
DC10 to 30V
Max. load current
0.1A/1 point 0.4A/common
Max. inrush current
0.4A 10ms
OFF-time leakage
current
0.1mA max.
ON-time max.
voltage drop
DC1.0V(TYP) 0.1A DC2.5V(MAX) 0.1A
Transistor
output
Response time
OFF
∏
ON: 2ms max. ON
∏
OFF: 2ms max.
Insulation system
Across input and earth
: Transformer insulation
Across input and channel : Transformer insulation
Dielectric withstand voltage
Across input and earth
: 500VAC for 1 minute
Across input and channel : 500VAC for 1 minute
Insulation resistance
Across input and earth
: 500VDC 20M
or more
Across input and channel : 500VDC 20M
or more
Current sensor*1
The following current sensor
made by URD Co., Ltd.
Input accuracy
•
CTL-12-S36-8(0.0 to 100.0A)
•
CTL-6-P-H(0.00 to 20.00A)
Input accuracy
Input range width × (±1.0%)
Heater wire
break
detection
specificatios
Alarm delay count
———
3 to 255
Number of occupied I/O points*2
16 points/1 slot
(I/O assignment:
16 intelligent points)
32 points/2 slots
(Default I/O assignment:
16 empty 16 intelligent
points)
Connection terminals
18-point terminal block
18-point terminal block ×2
Applicable wire size (mm)
0.3 to 0.75
Applicable crimping terminals
R1.25-3,1.25-YS3,RAV1.25-3,V1.25-YS3A
Internal current consumption (A)
0.55
0.64
Weight (kg)
0.20
0.30
Outline dimensions (mm)
27.4 (W) × 98 (H) × 112 (D)
55.2 (W) × 98 (H) × 112 (D)
*1 : Only the current sensor of URD Co., Ltd. may be used.
*2 : When using the Q64TCTTBW, the device numbers of the I/O signals are
incremented by 16 points due to the empty points of the left-hand side slot.
In this manual, therefore, read the I/O signals as indicated below
depending on the module used.
Example) When the signal is indicated as Yn1
When using Q64TCTT: Y1
When using Q64TCTTBW: Y11
*3 : For the noise immunity, withstand voltage, insulation resistance and others
in the PLC system using this module, refer to the power supply module
specifications given in the used CPU module user's manual.