5
*1
For the connector type, use a male D-Sub 9 pin. The PROFIBUS cable must
be created by the user. (for information regarding the cable wiring, refer to
Item 5.2.)
The size of the screw which can be used for the connector is #4-40 UNC.
No.
Name
Description
Remark
(a)
LED
Displays the A1SJ71PB93D status.
Name
Display description
RUN
Displays the A1SJ71PB93D operation status.
On: Normal
Off: Module WDT error occurrence
ERR.
On: Parameter setting error or module error
occurrence
Off: Normal
SYNC
On: During SYNC mode
FREEZE
On: During FREEZE mode
DIA
On: During extended fault notification
processing
BF
On: Before data communication or
communication error detected
Off: During data communication
TEST
On: During execution of self-diagnostics
B6 to B0
Indicate the station number of the host in
binary.
Example: Station No. 85 (55
H
)
(b)
PROFIBUS
interface
connector
Connector for connecting the table for the PROFIBUS-DP
network.
*1
B0
B1
B2
B3
B4
B5
B6