5. WIRING

5.1 Precautions Against Wiring

As one of the requirements to give full play to A1SJ71PB93D’s functions 
and make up the system with high reliability, it is necessary to have an 
external wiring unsusceptible to an influence of noise.  Precautions 
against external wiring of A1SJ71PB93D is described below.

(1) Do not route the wire of A1SJ71PB93D close to or bundle it 

together with the main circuit and high-tension lines, or the load-
carrying lines from other than the PLC. Otherwise, the module may 
be susceptible to an influence of noise and surge induction. 

(2) The wires from the input/output modules of the PLC should be 

away from the communication cable as far as possible as shown in 
the figure below.

(3) Grounding

(a) When the A1SJ71PB93D is used, the FG and LG terminals of 

the power supply module of the PLC should basically be 
grounded.

(b) If communication cannot be performed after grounding 

because of abnormal voltage applied to the FG terminal, the 
module may be used without grounding.

Communication cable

Shielded
covering

Wiring of output module

Wiring of input  
module

Power supply

module

PLC CPU

Output module

Output module

Input module

A1SJ71PB93D

Input module

Содержание MELSEC-A A1SJ71PB93D

Страница 1: ...ose programmable controller MELSEC Series 2001 MITSUBISHI ELECTRIC CORPORATION PROFIBUS DP Slave Module Prior to use please read both this manual and detailed manual thoroughly and familiarize yoursel...

Страница 2: ...the PROFIBUS DP the status of the faulty station is as follows Configure an interlock circuit in the sequence program using the communication status information input X1 so that the system can operat...

Страница 3: ...ment outside the range of the general specifications may cause electric shock fire malfunction and damage to or deterioration of the product Load the module by securely inserting the module fixing hoo...

Страница 4: ...Unless the cable is thus protected or secured the module or the cable could be damaged when the cable swings moves or it is strained with careless pulls or it could cause malfunction when the cable co...

Страница 5: ...e controller in all directions Failure to do so can cause a malfunction Be sure to shut off all phases of the external power supply before mounting or removing the module Failure to do so may result i...

Страница 6: ...NDED OR EXCLUDED BY INSTRUCTIONS PRECAUTIONS OR WARNING CONTAINED IN MITSUBISHI S USER INSTRUCTION AND OR SAFETY MANUALS TECHNICAL BULLETINS AND GUIDELINES FOR the PRODUCT Prohibited Application Prohi...

Страница 7: ...s provided that the usage of the PRODUCT is limited only for the specific applications agreed to by Mitsubishi and provided further that no special quality assurance or fail safe redundant or other sa...

Страница 8: ...COMPLIANCE WITH EMC AND LOW VOLTAGE DIRECTIVES SAFETY PRECAUTIONS Chinese CONDITIONS OF USE FOR THE PRODUCT This manual confers no industrial property rights or any rights of any other kind nor does i...

Страница 9: ...S 1 OVERVIEW 1 2 PERFORMANCE SPECIFICATIONS 1 3 INSTALLATION 3 3 1 Handling Precautions 3 4 PART NAMES AND SETTINGS 4 5 WIRING 6 5 1 Precautions Against Wiring 6 5 2 PROFIBUS Cable Wiring 7 6 OUTLINE...

Страница 10: ...equipment certain measures may be necessary Please refer to one of the following manuals User s manual for the CPU module used User s manual hardware for the CPU module or base unit used The CE mark o...

Страница 11: ...Model A1SJ71PB93D PROFIBUS DP station type Slave station Transmission specifications Electrical standards and characteristics Complies with EIA RS485 Medium Shielded twisted cable Type A Network conf...

Страница 12: ...dule user s manual Transmission specifications Maximum number of repeaters network 3 units 2 Maximum number of stations segment 32 stations including repeaters Number of connection nodes segments 32 S...

Страница 13: ...e it is made of resin 2 Do not remove the PCB of each module from its case This may cause a failure in the module 3 Be careful not to let foreign objects such as wire burrs enter the module during wir...

Страница 14: ...4 4 PART NAMES AND SETTINGS Following is an explanation of the A1SJ71PB93D part names and settings b a...

Страница 15: ...us On Normal Off Module WDT error occurrence ERR On Parameter setting error or module error occurrence Off Normal SYNC On During SYNC mode FREEZE On During FREEZE mode DIA On During extended fault not...

Страница 16: ...e the module may be susceptible to an influence of noise and surge induction 2 The wires from the input output modules of the PLC should be away from the communication cable as far as possible as show...

Страница 17: ...PROFIBUS cable Type A with braided shield 3 Termination resistor Pin No Name Application 1 SHIELD Shield Protective Ground 2 Vacancy 3 RxD TxD P Receive Transmit Data P 4 Vacancy 5 DGND 1 Data Ground...

Страница 18: ...8 6 OUTLINE DRAWINGS Unit mm inch 4 0 16 130 5 12 93 6 3 69 6 5 0 26 34 5 1 36...

Страница 19: ...9 MEMO...

Страница 20: ...s Bouvets F 92741 Nanterre Cedex France Tel 33 1 5568 5568 South Africa Circuit Breaker Industries Ltd Private Bag 2016 ZA 1600 Isando South Africa Tel 27 11 928 2000 China Mitsubishi Electric Automat...

Отзывы: