![Mitsubishi ME96SSR-MB Скачать руководство пользователя страница 28](http://html1.mh-extra.com/html/mitsubishi/me96ssr-mb/me96ssr-mb_user-manual_1809301028.webp)
3.Setting
3.6 Setting Menu 5:
Pulse and Alarm Settings (Setting Upper/Lower Limit Alarm, Motor Starting Current
Mask Function, Pulse Output, etc.)
- 27 -
Set the output function of Pulse/Alarm output 1.
When the ME-4210-SS96 optional plug-in module is not installed,
this display will be skipped.
Please refer to page 56 for the correspondence between Alarm output
and Alarm item.
⑨
Pulse/Alarm
output 1
PULSE
AL
(
Pulse output
) (
Alarm output
)
Set the item that is output to pulse output 1.
In the following cases, this display will be skipped.
・
ME-4210-SS96 optional plug-in module is not installed.
・
Not set “PULSE” to
⑨
Pulse/Alarm output 1.
Display
Setting value
Section (A)
Section (B)
Section (C)
Active energy (Imported)
OFF
Active energy (Exported)
OFF
Reactive energy (Imported, Lag)
Reactive energy (Imported, Lead)
Reactive energy (Exported, Lag)
Reactive energy (Exported, Lead)
Periodic active energy 1
OFF
Periodic active energy 2
OFF
non (No output)
OFF
OFF
⑩
Pulse output 1
output item
Note: The segment shown in
The left table flickers
according to the selected
element.
Section (A)
Section (B)
Section (C)
SET
DISPLAY
Set the pulse value of pulse output 1.
Pulse value is selected from the table below, according to total
load power[kW].
In the following cases, this display will be skipped.
・
ME-4210-SS96 optional plug-in module is not installed.
・
Not set “PULSE” to
⑨
Pulse/Alarm output 1.
・
Set “non” to
⑩
Pulse output 1 output item.
α
x (VT primary voltage) x (CT primary current)
Total load power[kW] =
1000
*1: For 3-phase 4-wire setting, the VT primary voltage is calculated using the phase to neutral voltage.
*2: For 1-phase 3-wire setting, the VT primary voltage is calculated using the phase to neutral voltage.
*3: For direct voltage setting, the direct voltage is used for calculation instead of the VT primary voltage.
Total load
[kW]
Possible pulse unit settings
Less than 10
1
0.1
0.01
0.001
10 or higher but less than 100
10
1
0.1
0.01
100 or higher but less than 1000
100
10
1
0.1
kWh/pulse
1000 or higher but less than 10000
1
0.1
0.01
0.001
10000 or higher but less than 100000
10
1
0.1 0.01
100000 or higher
100
10
1
0.1
MWh/pulse
Note 1: W hen
⑩
Pulse output 1 output item is set to "non", this setting will be skipped.
Note 2: The factory default setting values are minimum values for the pulse unit that can be set.
Note 3: For reactive power, kW in the above table needs to be read as kvar, kW h needs to
be read as kvarh, and MWh needs to be read as Mvarh.
⑪
Pulse output 1
pulse unit
α
:
1 1-phase 2-wire
2
1-phase
3-wire
3
3-phase
3-wire
3 3-phase 4-wire
DISPLAY
SET
DISPLAY
SET