2 Specification and function
14
FX
3U
-64CCL User's Manual
2. Specification and function
DESIGN PRECAUTIONS
•
For the status of each station when the main unit stops calculation or when a communication error occurs in the data link, thoroughly
read the description of data link processing time in the CC-Link master module manual. Construct an interlock circuit in the sequence
program using the communication status information (BFM, SB, SW) so that the system always works conservatively.
Erroneous outputs and malfunctions may cause accidents.
1) Setting to hold or clear the input information against data link error.
Remote outputs (RY) and remote registers (RWw) are held or cleared in accordance with the setting of BFM #32.
0 (default): Data prior to the error is held.
Other than 0: Data prior to the error is cleared.
2) Setting to hold or clear the data against a stop in the main unit.
Remote inputs (RX) and remote registers (RWr) are held or cleared in accordance with the setting of BFM #33.
0 (default): Data prior to the stop is held.
Other than 0: Data prior to the stop is cleared.
•
When executing control (data changes) to an operating PLC, construct an interlock circuit in the sequence program so that the entire
system operates conservatively.
In addition, when executing control such as program changes and operation status changes (status control) to an operating PLC,
thoroughly read the manual and sufficiently confirm safety in advance.
Especially in control from external equipment to a PLC in a remote place, problems in the PLC may not be able to be handled
promptly due to abnormality in data transfer.
Construct an interlock circuit in the sequence program. At the same time, determine the actions in the system between the external
equipment and the PLC (Master station contains) for protection against abnormalities in data transfer.
•
Make sure to include the following safety circuits outside the PLC to ensure safe system operation even during external power supply
problems or PLC failure.
•
Otherwise, malfunctions may cause serious accidents.
1) Above all, the following components should be included: an emergency stop circuit, a protection circuit, an interlock circuit for
opposite movements (such as normal vs. reverse rotation), and an interlock circuit (to prevent damage to the equipment at the
upper and lower positioning limits).
2) Note that when the PLC main unit detects an error during self diagnosis, such as a watchdog timer error, all outputs are turned off.
Also, when an error that cannot be detected by the PLC main unit occurs in an input/output control block, output control may be
disabled.
External circuits and mechanisms should be designed to ensure safe machinery operation in such cases.
DESIGN PRECAUTIONS
•
Observe the following items. Failure to do so may cause incorrect data-writing through noise to the PLC and result in PLC failure,
machine damage or other accident.
1) Do not bundle the control line together with or lay it close to the main circuit or power line. As a guideline, lay the control line at
least 100mm (3.94") or more away from the main circuit or power line.
Noise may cause malfunctions.
2) Ground the shield wire or shield of a shielded cable.
Do not use common grounding with heavy electrical systems (refer to Subsection 5.1.2).
•
Do not apply excessive pressure to the power supply terminal block or CC-Link connection terminal block.
Excessive pressure may cause damage or error.
DISPOSAL PRECAUTIONS
•
Please contact a certified electronic waste disposal company for the environmentally safe recycling and disposal of your device.
TRANSPORTATION PRECAUTIONS
•
The product is a precision instrument. During transportation, avoid any impacts. Failure to do so may cause failures in the product.
After transportation, verify the operations of the product.