2 Specification and function
2.4 Communication function
16
FX
3U
-64CCL User's Manual
• Expanded cyclic setting and number of link points
2.4
Communication function
2.4.1
Data transfer between 64CCL and master station
Data is transferred using FROM/TO instructions via the buffer memory (or direct specification of buffer
memory) between the FX
3G
/FX
3U
/FX
3UC
PLC and the 64CCL. Data is replaced with internal devices (such as
M, R and D), and used in sequence programs.
Cyclic transmission and extended cyclic transmission are available between the master station and the
64CCL.
2.4.2
Summary of accessing the FX
3U
/FX
3UC
main unit from another station QCPU (Q
mode) station.
The FX
3U
/FX
3UC
which is connected to the 64CCL can be accessed via CC-Link from QCPU (Q mode)
master / local station when GX Developer (Ver. 8.72A or later) is used.
Accessing permits write and read, verify, carry out device batch monitoring and complete device test.
CC-Link Ver.1.10
CC-Link Ver.2.00
Expanded cyclic setting
Single
Double
Quadruple
Octuple
Occupies 1 station
bit (RX)
32 points
32 points
64 points
128 points
bit (RY)
32 points
32 points
64 points
128 points
word (RWw)
4 points
8 points
16 points
32 points
word (RWr)
4 points
8 points
16 points
32 points
Occupies 2 stations
bit (RX)
64 points
96 points
192 points
-
bit (RY)
64 points
96 points
192 points
word (RWw)
8 points
16 points
32 points
word (RWr)
8 points
16 points
32 points
Occupies 3 stations
bit (RX)
96 points
160 points
-
-
bit (RY)
96 points
160 points
word (RWw)
12 points
24 points
word (RWr)
12 points
24 points
Occupies 4 stations
bit (RX)
128 points
224 points
-
-
bit (RY)
128 points
224 points
word (RWw)
16 points
32 points
word (RWr)
16 points
32 points
FX
3U
extension bus
TO instruction
TO instruction
FROM instruction
FROM instruction
CC-Link
Cyclic,
Expanded cyclic
FX
3G
/FX
3U
/FX
3UC
main unit
M (auxiliary relay) etc.
M (auxiliary relay) etc.
D (data resister) etc.
D (data resister) etc.
FX
3U
-64CCL
RX: Remote input
RY: Remote output
RWw(Remote register)
RWr(Remote register)
BFM (Buffer memory)
Q master station
RX: Remote input
RY: Remote output
RWw(Remote register)
RWr(Remote register)
Содержание FX3U-64CCL
Страница 1: ...FX3U 64CCL USER S MANUAL ...
Страница 2: ......
Страница 6: ... 4 MEMO ...
Страница 11: ...5 FX3U 64CCL User s Manual Table of Contents Warranty 69 Revised History 70 ...
Страница 77: ......