4 Installation
4.1 DIN rail mounting
22
FX
3U
-64CCL User's Manual
4.1
DIN rail mounting
The product may be mounted on a 35mm wide DIN46277 (DIN rail).
1
Fit the upper edge (A in the figure to the right) of the DIN
rail mounting groove onto the DIN rail.
2
Push the product onto the DIN rail.
• An interval space of 1 to 2 mm (0.04" to 0.08") between each unit is necessary.
3
Connect the extension cable.
Connect the extension cable (B in the figure to the right) to
the main unit, I/O extension unit/block or special function
unit/block on the left side of the product.
For information on the extension cable connection proce-
dure, refer to the respective product PLC manual.
→
Refer to the FX
3G
Hardware Edition
→
Refer to the FX
3U
Hardware Edition
→
Refer to the FX
3UC
Hardware Edition
• Example of anchoring
B
FX
3G
/FX
3U
Series main unit
DIN rail
Other extension
equipment
FX
3U
-64CCL
1 to 2mm
(0.04" to 0.08")
1 to 2mm
(0.04" to 0.08")
DIN rail
FX
2NC
-CNV-IF or
FX
3UC
-1PS-5V
1 to 2mm
(0.04" to 0.08")
1 to 2mm
(0.04" to 0.08")
FX
3UC
Series
main unit
FX
3U
-64CCL
Other extension
equipment