FX2NC Series Programmable Controllers
Outputs 6.
6-6
6.2.1
Reliability tests
The test results in table 6.4 were gathered from a 1 sec ON/OFF test cycle. Please note that
the over current induced by in-rush greatly reduces the relay contacts service life. The rated life
for an inductive AC load such as a contactor or solenoid valve is 500,000 operations at 20VA.
Table 6.5 :
20VA
35VA
80VA
Load capacity
0.2A/100VAC
0.1A/200VAC
0.35A/100V AC
0.17A/240V AC
0.8A/100V AC
0.4A/240V AC
Life of contact (cycles)
3,000,000
1,000,000
200,000
Example load (Mitsubishi contactor)
S-K10 to S-K95
S-K100 to S-K150
S-K180,S-K400