FX2NC Series Programmable Controllers
Outputs 6.
6-2
6.1.1
Response times
OFF times increase as the load current decreases.
For improved response times use a 'dummy' resistor, see Figure 6.1. If a response time of 0.5
ms or better is required when using 'light loads' use a 'dummy' resistor and ensure the signal
line has a current greater than 60mA/24V DC.
Figure 6.1 :Dummy load
+Y
Y
Dummy
load
Load
5 to 30V DC
Source