FX
2N
-32CCL CC-Link Interface Block
Setting of Remote Device Stations 4
4-3
4.2
List of number of remote points and remote Nos.
In the FX
2N
-32CCL, the number of remote points vary depending on the selected number of stations (1 to 4).
•
Thirty-two remote input points and 32 remote output points are available in one station. However, the
upper 16 points of the final station are occupied by the CC-Link as the system area.
•
Four read points and four write points are available as remote registers in one station.
Table of number of remote points and remote Nos. in accordance with selected number of stations
Number
of
stations
Type
Remote input
Remote output
Remote register for
write
Remote register for
read
1
User area
RX00 to RX0F
(16 points)
RY00 to RY0F
(16 points)
RWr0 to RWr3
(4 points)
RWw0 to RWw3
(4 points)
System area
RX10 to RX1F
(16 points)
RY10 to RY1F
(16 points)
2
User area
RX00 to RX2F
(48 points)
RY00 to RY2F
(48 points)
RWr0 to RWr7
(8 points)
RWw0 to RWw7
(8 points)
System area
RX30 to RX3F
(16 points)
RY30 to RY3F
(16 points)
3
User area
RX00 to RX4F
(80 points)
RY00 to RY4F
(80 points)
RWr0 to RWrB
(12 points)
RWw0 to RWwB
(12 points)
System area
RX50 to RX5F
(16 points)
RY50 to RY5F
(16 points)
4
User area
RX00 to RX6F
(112 points)
RY00 to RY6F
(112 points)
RWr0 to RWrF
(16 points)
RWw0 to RWwF
(16 points)
System area
RX70 to RX7F
(16 points)
RY70 to RY7F
(16 points)
Содержание FX2N-32CCL
Страница 1: ...USER S MANUAL CC Link INTERFACE BLOCK FX2N 32CCL ...
Страница 8: ...FX2N 32CCL CC Link Interface Block Contents vi 6 3 Program in master PC 6 5 6 4 Program in FX PC 6 11 ...
Страница 18: ...FX2N 32CCL CC Link Interface Block Specifications 2 2 6 Memo ...
Страница 26: ...FX2N 32CCL CC Link Interface Block Setting of Remote Device Stations 4 4 4 Memo ...
Страница 39: ...FX2N 32CCL CC Link Interface Block Assignment of Buffer Memory BFM 5 5 13 ...
Страница 54: ...FX2N 32CCL CC Link Interface Block Programming Examples 6 6 14 Memo ...
Страница 55: ...FX2N 32CCL CC Link Interface Block ...