FX
2N
-32CCL CC-Link Interface Block
Assignment of Buffer Memory (BFM) 5
5-12
5.4
System area of remote I/O
As to the number of remote I/O points (RX00 to RX7F/RY00 to RY7F) in the FX
2N
-32CCL, the range and the
number of points vary depending on the selected number of stations (1 to 4).
The upper 16 points of the final station are occupied by the CC-Link system as the system area, so cannot be
used as the user area. (
☞
4.2) The tables below show assignment of the system area.
"n" indicates the number of occupied stations.
(Example: When three stations are occupied, the device Nos. are "RY50 to RY5F" and "RX50 to RX5F".)
Master station
→
→
→
→
FX Dedicated to read
Device No.
Description
RY(2n-1)0
Unusable
RY(2n-1)1
Unusable
RY(2n-1)2
Unusable
RY(2n-1)3
Unusable
RY(2n-1)4
Unusable
RY(2n-1)5
Unusable
RY(2n-1)6
Unusable
RY(2n-1)7
Unusable
RY(2n-1)8
Initial data processing completion flag
RY(2n-1)9
Initial data processing request flag
RY(2n-1)A
Error reset request flag
RY(2n-1)B
Undefined
RY(2n-1)C
Reserved (unusable)
RY(2n-1)D
Reserved (unusable)
RY(2n-1)E
Reserved (unusable)
RY(2n-1)F
Reserved (unusable)
FX
→
→
→
→
Master station Dedicated to write
Device No.
Description
RX(2n-1)0
Unusable
RX(2n-1)1
Unusable
RX(2n-1)2
Unusable
RX(2n-1)3
Unusable
RX(2n-1)4
Unusable
RX(2n-1)5
Unusable
RX(2n-1)6
Unusable
RX(2n-1)7
Unusable
RX(2n-1)8
Initial data processing request flag
RX(2n-1)9
Initial data processing completion flag
RX(2n-1)A
Error status flag
RX(2n-1)B
Remote ready
RX(2n-1)C
Reserved (unusable)
RX(2n-1)D
Reserved (unusable)
RX(2n-1)E
Reserved (unusable)
RX(2n-1)F
Reserved (unusable)
Содержание FX2N-32CCL
Страница 1: ...USER S MANUAL CC Link INTERFACE BLOCK FX2N 32CCL ...
Страница 8: ...FX2N 32CCL CC Link Interface Block Contents vi 6 3 Program in master PC 6 5 6 4 Program in FX PC 6 11 ...
Страница 18: ...FX2N 32CCL CC Link Interface Block Specifications 2 2 6 Memo ...
Страница 26: ...FX2N 32CCL CC Link Interface Block Setting of Remote Device Stations 4 4 4 Memo ...
Страница 39: ...FX2N 32CCL CC Link Interface Block Assignment of Buffer Memory BFM 5 5 13 ...
Страница 54: ...FX2N 32CCL CC Link Interface Block Programming Examples 6 6 14 Memo ...
Страница 55: ...FX2N 32CCL CC Link Interface Block ...