![Mitsubishi FREQROL-E700 Скачать руководство пользователя страница 82](http://html1.mh-extra.com/html/mitsubishi/freqrol-e700/freqrol-e700_manual_1809269082.webp)
5-16
Operation
1
Screen at power-ON
The monitor display appears.
2
AU signal assignment (current input; proceed to step 3 for voltage input)
Set Pr. 160 to "0" to enable extended parameters. Set "4" in any of Pr.178 to Pr.184 to assign the AU signal.
Turn on the AU signal.
3
Quick setup mode settings
Press
and
together for 0.5s. "
" appears and the [PRM] indicator flashes.
4
Operation mode selection
Turn
until
appears. The [PU] and [PRM] indicators flash.
5
Operation mode settings
Press
to finalize the setting. (Set Pr. 79 to "4".)
"
" and "
" flash alternately. [PU] and [EXT] indicators are on.
6
Start
Press
. [RUN] flashes quickly as no frequency command has been issued.
7
Acceleration → constant speed
To set with voltage input, slowly turn the potentiometer (frequency setting potentiometer) completely clockwise.
To set with current input, input 20mA of current.
The frequency value in the display increases in accordance with the Pr. 7 Acceleration time and "
" (60.00Hz)
appears.
The [RUN] indicator is on during forward rotation and slowly flashes during reverse rotation.
8
Deceleration
To set with voltage input, slowly turn the potentiometer (frequency setting potentiometer) completely counter-clockwise.
To set with current input, input 4mA of current.
The frequency value in the display increases in accordance with the Pr. 8 Deceleration time, "
" (00.00Hz)
appears, and the motor stops operating. The [RUN] indicator flashes quickly.
9
Stop
Press
. [RUN] turns OFF.
● The frequency is initially set to 60Hz when the frequency setting potentiometer is turned completely clock-
wise to its maximum setting (voltage input). (Change with Pr. 125)
● Set Pr. 73 analog input selection to "0" when a signal of 10VDC is input into terminal 2. The initial value is
"1 (0-5V input)".
● The frequency is initially set to 60Hz when 20mA of current is input.
POINT
Operation example
Operate at 60Hz.