![Mitsubishi FREQROL-E700 Скачать руководство пользователя страница 41](http://html1.mh-extra.com/html/mitsubishi/freqrol-e700/freqrol-e700_manual_1809269041.webp)
3-9
3
3.5.2 Pr. 9 Electronic thermal O/L relay
Configure the current value for the electronic thermal O/L relay to enable motor overheating protection. This can
help you achieve optimal protection capability for various operating conditions such as low-speed operation and
reduced motor cooling capacity.
Pr.
Name
Initial value
Setting range
Description
9
Electronic thermal O/L relay Inverter rated current
*1
0 to 500A
Set the rated motor current.
This function detects the motor overload (overheating) and trips the inverter by stopping the operation of the
transistor at the inverter output side.
● Set the rated current value (A) of the motor in Pr. 9.
(If the motor has both 50Hz and 60Hz rating and the Pr. 3 Base frequency is set to 60Hz, set the 1.1 times of
the 60Hz rated motor current.)
● Set "0" in Pr. 9 when you do not want to operate the electronic thermal O/L relay, e.g. when using an external
thermal relay with the motor. (Note that the output transistor protection of the inverter functions (E.THT).)
*1 The inverter rated current is configured to 85% for values of 0.75K or less.
Operation example
1
Screen at power-ON
The monitor display appears.
2
Changing the operation mode
Press
to choose the PU operation mode. The [PU] indicator turns on.
3
Parameter setting mode
Press
to choose the parameter setting mode.
4
Selecting the parameter number
Turn
until
(Pr. 9) is selected.
5
Reading settings
Press
to read the present setting. "
" (0.68A (initial value)) appears.
6
Changing the setting
Turn
to change the setting to "
" (0.63A).
7
Parameter settings
Press
to finalize the setting.
The parameter number and setting flashes.
* Configure parameter settings in accordance with your environment.
Содержание FREQROL-E700
Страница 1: ...Your First Inverter Satellite Training Series PART2...
Страница 2: ......
Страница 10: ...MEMO...
Страница 32: ...2 14 MEMO...
Страница 46: ...3 14 MEMO...
Страница 106: ...Manual Revision History Date of creation Sub number Description Mar 2016 A Initial release...
Страница 107: ......