3-8
3.5 How to configure parameters
3.5.1 Parameter clear/All parameter clear
Parameter settings may have been changed if the inverter is used.
Use this procedure to restore parameters to their initial values.
Setting
Description
0
Not executed.
1
Set parameters back to the initial values. (Parameter clear sets back all parameters except calibration
parameters, terminal function selection parameters to the initial values.) Refer to the parameter list for
information on the availability of clear parameter and clear all parameters functions for each parameter.
Operation
Display
1
Screen at power-ON
The monitor display appears.
2
Changing the operation mode
Press
to choose the PU operation mode.
PU indication is lit.
3
Parameter setting mode
Press
to choose the parameter setting
mode.
PRM indication is lit.
(The parameter number read previously appears.)
4
Selecting the parameter number
Turn
until
(
) appears
Parameter clear
All parameter clear
5
Reading settings
Press
to read the present setting.
" "(initial value) appears.
6
Changing the setting
Turn
to change it to the set value " ".
7
Parameter settings
Press
to finalize the setting.
"1" and "Pr.CL"/"ALLC" flashes.
Parameter clear
All parameter clear
● Check the values of several parameter settings when the clear all parameters function cannot be performed.
Pr. 77 "0", Pr. 79 "0", Pr. 340 "10", and Pr. 551 "9999"
POINT