PARAMETERS
139
<Setting>
Refer to the following list and set the parameters:
Setting
Signal
Name
Functions
Relevant Parameters
Pr. 59 = 0
Low-speed operation command
Pr. 4 to Pr. 6
Pr. 24 to Pr. 27
Pr. 232 to Pr. 239
0
RL
Pr. 59 = 1, 2*
Remote setting (setting clear)
Pr. 59
Pr. 59 = 0
Middle-speed operation command
Pr. 4 to Pr. 6, Pr. 24 to Pr. 27, Pr. 232 to
Pr. 239
1
RM
Pr. 59 = 1, 2*
Remote setting (deceleration)
Pr. 59
Pr. 59 = 0
High-speed operation command
Pr. 4 to Pr. 6, Pr. 24 to Pr. 27,
Pr. 232 to Pr. 239
2
RH
Pr. 59 = 1, 2*
Remote setting (acceleration)
Pr. 59
3
RT
Second function selection
Pr. 44 to Pr. 50
4
AU
Current input selection
Refer to page 10
5
JOG
Jog operation selection
Pr. 15, Pr. 16
6
CS
Automatic restart after instantaneous power failure selection
Pr. 57, Pr. 58, Pr. 162 to Pr. 165
7
OH
External thermal relay input**
The externally provided overheat protection thermal relay,
motor-embedded temperature relay or the like is operated to
stop the inverter.
Refer to page 163
10
X10
FR-HC connection (inverter operation enable)
Pr. 30, Pr. 70
11
X11
FR-HC connection (instantaneous power failure detection)
(Only when FR-A5NR option is fitted)
Pr. 30, Pr. 70
12
X12
PU operation external interlock
Pr. 79
13
X13
External DC dynamic braking start
Pr. 10 to Pr. 12
14
X14
PID control valid terminal
Pr. 128 to Pr. 134
16
X16
PU-external operation switch-over
Pr. 79
17
X17
Load pattern selection forward/reverse rotation boost
Pr. 14
24
X24
PID forward-reverse action switching function
(NA, EC versions only)
Pr. 500 to Pr. 516
9999
No function
*: When Pr. 59 = "1" or "2", the functions of the RL, RM, RH and RT signals change as listed above.
**: Operated when the relay contact "opens".
Note: 1. One function can be assigned to two or more terminals. In this case, the terminal inputs are
OR’ed.
2. The speed command priorities are higher in order of jog, multi-speed setting (RH, RM, RL) and
AU.
3. When HC connection (inverter operation enable signal) is not selected, the MRS terminal shares
this function.
4. Use common terminals to assign the multi-speeds (7 speeds) and remote setting. They cannot
be set individually.
(Common terminals are used since these functions are designed for speed setting and need not
be set at the same time.)
5. When FR-HC connection inverter operation enable (X10) signal is not assigned, the MRS
terminal shares this function.
6. When "7" is set in Pr. 79 and the PU operation external interlock (X12) signal is not assigned, the
MRS signal acts as this function.
7. When the load pattern selection forward/reverse rotation boost (X17) signal is not assigned, the
RT signal shares this function.