[2] (E)M350 to 500
(1) When routing the wiring through the front of the unit
(2) When routing the wiring through the bottom of the unit
Ⓑ
Ⓒ
Ⓐ
Ⓒ
Ⓐ
Ⓑ
Power cable size (mm
2
)
Knockout hole to be used
2, 3.5, 5.5
Knockout hole 2
8, 14
Knockout hole 4
21, 26, 33
Knockout hole 3
84, 67, 53
Knockout hole 5
Ⓐ
Cable strap
Ⓑ
Power cable
Ⓒ
Transmission cable
The length of the section after the cable access hole must be at least 1100 mm (43 in).
<Notice>
・
Do not remove the ground wire that connects Main Box and Inverter Box.
・
Install the transmission cable as shown in the figure above so that the cable is long enough for the Main Box to be
moved for servicing.
・
If there are any gaps around the power cable and transmission cable, please be sure to fill these in with a suitable
material to prevent snow from entering, which may cause damage to the electrical parts, and to protect your hands
from direct contact with cables.
・
When putting the power cable through the knockout hole without using a conduit tube, deburr the hole and protect
the power cable with protective tape.
・
Use a conduit tube to narrow down the opening if there is a possibility of small animals entering the unit.
・
When taking the conduit tube out from the bottom part of the unit, caulk around the tube opening to prevent water
infiltration.
Fill the gap.