9-2. Pipe selection
Use refrigerant piping made of phosphorus deoxidized copper (copper and copper alloy
seamless pipes) that meets local requirements. Pipe joints should also meet local
requirements. Keep the inner and outer surfaces of the pipes clean and free of sulphur,
oxides, dust/dirt, shaving particles, oils, moisture, or any other contaminants.
-Contaminants on the inside of the refrigerant piping will cause the refrigerant oil to deteriorate
and cause the compressor to malfunction.
Use refrigerant pipes for use with R32 refrigerant system. Piping for systems for use with other types of refrigerants
may not be able to be used.
Use refrigerant pipes with the thicknesses specified in the table below.
Size [mm (in)]
Minimum wall thickness [mm (mil)]
Type
ø6.35 (ø1/4)
0.8 (32)
Type-O
ø9.52 (ø3/8)
0.8 (32)
Type-O
ø12.7 (ø1/2)
0.8 (32)
Type-O
ø15.88 (ø5/8)
1.0 (40)
Type-O
ø19.05 (ø3/4)
1.2 (48)
Type-O
1.0 (40)
Type-1/2H or H
ø22.2 (ø7/8)
1.0 (40)
Type-1/2H or H
ø25.4 (ø1)
1.0 (40)
Type-1/2H or H
ø28.58 (ø1-1/8)
1.0 (40)
Type-1/2H or H
ø31.75 (ø1-1/4)
1.1 (44)
Type-1/2H or H
ø34.93 (ø1-3/8)
1.2 (48)
Type-1/2H or H
ø41.28 (ø1-5/8)
1.4 (56)
Type-1/2H or H
9-3. Twinning kit selection
9-3-1. 2-Branch Joint Pipe
A 2-Branch Joint Pipe is used to connect multiple indoor units to a port.
Hybrid City Multi system
・
Connect the pipes on site, referring to the HBC controller Installation Manual.
・
CMY-Y102SS-G2 is used in an R2 system, and cannot be used in a Hybrid City Multi system.
9-3-2. Joint Pipe Kit
A Joint Pipe Kit is used to connect an indoor unit of P100 model or above.
Hybrid City Multi system
・
Connect the pipes on site, referring to the HBC controller Installation Manual.
・
CMY-R160-J1 is used in an R2 system, and cannot be used in a Hybrid City Multi system.