WT09050X01
7-2. Multiple unit installation
・
When installing multiple units, make sure to take into consideration factors such as providing enough space for
people to pass through, ample space between blocks of units, and sufficient space for airflow. (The areas marked
with
Ⓐ
in the figures below must be left open.)
・
In the same way as with the single unit installation, add the dimension that exceeds the height limit (shown as "h1"
through "h3" in the figures) to L1, L2, and L3 as shown in the tables below.
・
If there are walls in the front and rear of the block of units, up to six units (three units for units M500 and EM500)
can be installed consecutively side by side, and a space of 1000 mm (39-3/8 in) or more must be left between each
block of six units.
・
When the amount of drain water is excessive, drain water comes out of the outdoor unit along the panel during
heating operation.
(1) Side-by-side installation
When the distances between the units (L4) need to
be small
When the distance behind the block of units (L2) needs
to be small
h2
L2
L1
h1
L4
Ⓐ
Ⓐ
h2
h1
L1
L2
L4
Ⓐ
Ⓐ
Required minimum distance [mm (in)]
L1 (Front)
L2 (Rear)
L4 (Between)
450 (17-3/4) + h1 300 (11-13/16) + h2
30 (1-3/16)
Required minimum distance [mm (in)]
L1 (Front)
L2 (Rear)
L4 (Between)
450 (17-3/4) + h1
100 (3-15/16) + h2
100 (3-15/16)
(2) Face-to-face installation
When there are walls in the front and rear of the
block of units
When there is a wall on either the right or left side of the
block of units
h1
h2
L1
L4
L4
L2
Ⓐ
Ⓐ
h3
L4
L3
L4
Required minimum distance [mm (in)]
L1 (Front)
L2 (Rear)
L4 (Between)
450 (17-3/4) + h1
100 (3-15/16) + h2
450 (17-3/4)
Required minimum distance [mm (in)]
L3 (Right/Left)
L4 (Between)
15 (5/8) + h3
450 (17-3/4)
Unit height
Unit height
Unit height
Unit height
Unit height
Unit height
Unit height