Mitsubishi AJ65S-64AD-U-H-JE Скачать руководство пользователя страница 14

 

8

 

 6. Wiring 

 

 

6.1 Wiring precautions 

To obtain maximum performance from the functions of AJ65SBT-64AD and 
improve the system reliability, an external wiring with high durability against noise 
is required. 
The precautions when performing external wiring are as follows: 

(1) Use separate cables for the AC and AJ65SBT-64AD external input signals, 

in order not to be affected by the AC side surge or conductivity. 

(2) Do not bundle or place with load carrying wires other than the main circuit 

line, high voltage line or programmable controller. Noises, surges, or 
conductivity may affect the system. 

(3) Place a one-point grounding on the programmable controller side for the 

shielded line or shielded cable. However, depending on the external noise 
conditions, it may be better have a grounding externally. 

 

6.2 Module connection example 

 

V+

I+

COM

SLD

500k

500k

250

V+

I+

COM

SLD

500k

500k

250

FG1

CH1

*4

*1 Shield

*1 Shield

*5

*3

CH4

*2

Signal source 0 to ±10 V

For voltage input

Signal source 0 to ±20mA

For current input

AG

 

 

*1 Use a two-core twisted shield line for the power cable. 
*2 Indicates the AJ65SBT-64AD input resistor. 
*3 For the current input, be sure to connect the (V+) and (I+) terminals. 
*4 When noise or ripple occurs with the external cable, connect a condenser with 

about 0.1 to 0.47µF (25V or higher voltage-resistant product) between the 
terminal V and COM. 

*5 Always perform grounding for FG1. When there is a lot of noise, it may be 

better ground AG as well. 
If the grounding wiring (grounding yes/no) is changed after the offset and gain 
are set, perform the setting of the offset/gain values again. 

 

Содержание AJ65S-64AD-U-H-JE

Страница 1: ...the Mitsubishi general purpose programmable controller MELSEC Series Prior to use please read both this manual and detailed manual thoroughly and familiarize yourself with the product MODEL AJ65S 64A...

Страница 2: ...derate injury or property damage Under some circumstances failure to observe the precautions given under CAUTION may lead to serious consequences Observe the precautions of both levels because they ar...

Страница 3: ...z Ground the FG and FG1 terminals to the protective ground conductor dedicated to the programmable controller Failure to do so may result in malfunction z Tighten any unused terminal screws within th...

Страница 4: ...or retightening the terminal screws Failure to do so may cause the module to fail or malfunction Undertightening the terminal screws can cause short circuit or malfunction Overtightening can damage th...

Страница 5: ...tion 2 3 Sep 2006 IB NA 0800138 E Partial correction SAFETY PRECAUTIONS Chapter 3 Chapter 7 Dec 2006 IB NA 0800138 F Partial correction Chapter 6 Oct 2008 IB NA 0800138 G Partial correction SAFETY PRE...

Страница 6: ...nverter Module Type AJ65SBT 64AD User s Manual SH 080106 13JR18 Compliance with the EMC and Low Voltage Directives 1 For programmable controller system To configure a system meeting the requirements o...

Страница 7: ...2 Shock durability Conforming to JIS B 3502 IEC 61131 2 147m s2 3 times each in 3 directions Usage environment No corrosive gas Usage height 3 Less than 2000m less than 6562ft Installation area Within...

Страница 8: ...RWw 4 points each Communication cable CC Link dedicated cable Dielectric withstand voltage Between power supply communication system batch and analog input batch 500VAC 1 minute Isolation system Acros...

Страница 9: ...30 minutes after power is turned ON 1 Digit indicates digital value 2 Current value indicates value of instant input current that does not break module inner electrical resistance 2 3 Checking hardwar...

Страница 10: ...ower supply shutoff or watchdog timer error occurred RUN LED Test mode On Indicates that the SELECT SET switch is in the SET position Flashing 0 1s intervals indicate that the input range setting is n...

Страница 11: ...F OFF OFF ON 2 OFF OFF OFF OFF OFF ON OFF 3 OFF OFF OFF OFF OFF ON ON 4 OFF OFF OFF OFF ON OFF OFF 10 OFF OFF ON OFF OFF OFF OFF 11 OFF OFF ON OFF OFF OFF ON 64 ON ON OFF OFF ON OFF OFF Example To set...

Страница 12: ...l the A series programmable controller in the following environments 1 Locations where the ambient temperature is outside the range of 0 to 55 C 2 Locations where the ambient humidity is outside the r...

Страница 13: ...C Link dedicated cable between the AJ65SBT 64AD and master module as shown below DA DB DG SLD FG DA DB DG SLD FG DA DB DG SLD FG Termination resistor CC Link dedicated cable Master module side AJ65SBT...

Страница 14: ...cable However depending on the external noise conditions it may be better have a grounding externally 6 2 Module connection example V I COM SLD 500k 500k 250 V I COM SLD 500k 500k 250 FG1 CH1 4 1 Shie...

Страница 15: ...u t 1 0 5 L RUNL ERR CH1 24G DA 24V DG SLD DB AJ65SBT 64AD I V COM COM SLD TEST I V I V TEST SELECT PW RUN 2 3 4 OFFSET GAIN FG I V AG SLD COM COM FG1 SET CH3 CH2 CH1 4 STATION NO 1 B RATE 1 2 2 4 8...

Страница 16: ...s Barcelona Spain Tel 34 93 565 3131 France Mitsubishi Electric Europe B V French Branch 25 Boulevard des Bouvets F 92741 Nanterre Cedex France TEL 33 1 5568 5568 South Africa Circuit Breaker Industri...

Отзывы: